Plan Review Notes
Plan Review Notes For Project Z22050024
Project Number Z22050024
Review Stop PU
Sequence Number 1
Notes
Date Text
2022-06-07 12:17:31REVIEW COMMENTS AS FOLLOWS:
  
 -WHY DOES THE 4 INCH WATER MAIN PIPE ON SITE NEED TO BE
 ABANDONED, AND WHAT DOES IT CURRENTLY FEED?
  
 -PGD PLAN DOES NOT SHOW PAVEMENT RESTORATION FOR SEWER
 LATERAL.
  
 -SHOW SEWER PIPE CONTINUATION TO RIGHT OF WAY AND
 CONNECTION TO CITY SANITARY SEWER MAIN.
  
 -COULD NOT FIND PROJECT NARRATIVE IN SUBMITTAL PACKAGE.
  
 -WILL THERE BE FIRE SPRINKLERS IN PROPOSED BUILDING?
  
 -IS EXISTING SEWER INFRASTRUCTURE SUFFICIENT FOR THE
 ADDITIONAL WASTEWATER DEMAND?
  
 -IDENTIFY DASHED AND DOTTED LINE RUNNING EAST AND WEST
 THROUGH THE SOUTHERN FPL EASEMENTS. ADD CALLOUT WITH
 LABELING AND INCLUDE ON LEGEND.
  
 -RELOCATE PROPOSED METER BOX OUT OF SIDEWALK AND IN
 GRASS LANDSCAPING. IF NEW LOCATION IS ON PRIVATE
 PROPERTY MAY NEED UTILITY EASEMENT IF NONE CURRENTLY
 EXIST THERE.
  
 -UPON FURTHER REVIEW AT FORMAL ENGINEERING SUBMITTAL,
 PROPOSED WATER SERVICE DESIGN MAY NEED TO TAP OFF WATER
 MAIN IN OKEECHOBEE BLVD.