| Date |
Text |
| 2022-06-08 20:30:31 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. |
| | |
| | 2. FLOOD ZONE. THE PROPOSED FINISHED FLOOR ELEVATION OF |
| | 18.50 FT NAVD IS NOTED. ACCORDING TO THE ADOPTED FLOOD |
| | INSURANCE RATE MAPS (FIRMS), THE PROPOSED BUILDING IS |
| | IN FLOOD ZONE AE, WITH A BASE FLOOD ELEVATION OF 13.4 |
| | FT NAVD. THE FIRST FLOOR OF THE BUILDING AND ALL |
| | ASSOCIATED MECHANICAL EQUIPMENT (CHILLERS, GENERATORS |
| | ETC.) SHALL BE 24 INCHES (FREEBOARD) ABOVE THE BASE |
| | FLOOD ELEVATION. THE PROPOSED FINISHED FLOOR ELEVATION |
| | OF 18.50 FT NAVD WILL MEET THAT REQUIREMENT. |
| | |
| | 3. GREASE INTERCEPTOR. A GREASE INTERCEPTOR MAY BE |
| | REQUIRED. FOR INFORMATION ON THE REQUIRED TYPE, SIZE |
| | AND LOCATION, PLEASE CONTACT RYAN BROWN, CHIEF PLUMBING |
| | INSPECTOR, DEVELOPMENT SERVICES DEPARTMENT, AT (561) |
| | 805-6692, OR BY EMAIL: [email protected] |
| | |
| | 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, |
| | FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, |
| | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, |
| | SITE IRRIGATION, ETC. |
| | |
| | 5. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT |
| | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL |
| | HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION |
| | OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING, |
| | CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT |
| | (561) 805 6659, OR BY EMAIL: [email protected] |
| | |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |