| 2022-10-26 10:45:21 | CASE NO. FSPR 22-08 2ND RESUBMITTAL REVIEW |
| | RESIDENCES OF PALM BEACH WEST |
| | 401 SOUTH DIXIE HIGHWAY |
| | |
| | - CONTACT ERIC SCHNEIDER @ (561) 822-1446, |
| | [email protected] |
| | |
| | - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN |
| | WRITTEN FORMAT. |
| | |
| | - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF THREE |
| | (3) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG AND |
| | .PDF FORMAT OF ALL PLANS. PLEASE NOTE THAT CHANGES ON |
| | THE RESUBMITTED PLANS OR THE SUBMITTAL OF |
| | INFORMATION/PLANS TO ADDRESS THE COMMENTS MAY RESULT IN |
| | ADDITIONAL COMMENTS. |
| | |
| | - THE PPRC COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND |
| | RESUBMITTED TO THE PLANNING DIVISION. STAFF WILL REVIEW |
| | THE APPLICATION AND IF SUFFICIENT WILL SCHEDULE YOU FOR |
| | THE NEXT AVAILABLE DOWNTOWN ACTION COMMITTEE MEETING. |
| | PLEASE NOTE THAT RESUBMITTALS MAY BE SCHEDULED FOR AN |
| | ADDITIONAL PPRC MEETING. |
| | |
| | - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT |
| | RECEIVED A RESPONSE TO THE COMMENTS WITHIN 60 DAYS FROM |
| | THE DATE OF THESE COMMENTS (BY DECEMBER 26, 2022), THE |
| | PLANNING DIVISION MAY NOTIFY THE APPLICANT THAT THE |
| | CASE IS CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL |
| | REQUIRE A NEW DEVELOPMENT APPLICATION. |
| | |
| | - PLEASE NOTE THAT SINCE PREVIOUSLY ISSUED COMMENTS |
| | WERE NOT BE SUFFICIENTLY ADDRESSED, THE APPLICANT WILL |
| | BE ASSESSED A RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF |
| | THE ORIGINAL APPLICATION FEE ($500). |
| | |
| | 1) REPEAT COMMENT: THE SURVEY SHOWS PROPERTY ALONG FERN |
| | STREET AND SOUTH DIXIE HIGHWAY THAT WERE ACQUIRED BY |
| | MAINTENANCE MAPS BY THE CITY AND FDOT, RESPECTIVELY. |
| | THIS PROPERTY NEEDS TO BE EXCLUDED FROM THE OVERALL |
| | PROPERTY CALCULATIONS FOR THE SITE, INCLUDING FAR AND |
| | OPEN SPACE. ALL DATA TABLES AND PLANS NEED TO BE |
| | UPDATED ACCORDINGLY. |
| | |
| | 2) APPENDIX A OF THE TRANSPORTATION ELEMENT OF THE |
| | COMPREHENSIVE PLAN AND TABLE X-1 CONTAINED IN SECTION |
| | 94-305.D OR THE ZONING AND LAND DEVELOPMENT REGULATIONS |
| | ARE THE LIST OF REQUIRED THOROUGHFARE RIGHT-OF-WAY |
| | SETBACKS. THE TABLES REQUIRE A ROADWAY SETBACK OF 100 |
| | FEET FROM THE CENTERLINE OF QUADRILLE BOULEVARD IN |
| | ADDITION TO THE SETBACKS REQUIRED BY THE ZONING |
| | DISTRICT. A PORTION OF THE BUILDING ALONG QUADRILLE |
| | BOULEVARD DOES NOT COMPLY WITH THE COMPREHENSIVE PLAN |
| | AND ZONING AND LAND DEVELOPMENT REGULATION REQUIREMENT. |
| | REGARDLESS OF WHETHER THE LANGUAGE IN THE COMPREHENSIVE |
| | PLAN OR THE ZONING AND LAND DEVELOPMENT REGULATIONS |
| | WERE A SCRIVENER'S ERROR, THE LANGUAGE IS IN BOTH |
| | DOCUMENTS. THE PROPOSAL IS NOT CONSISTENT WITH THE |
| | COMPREHENSIVE PLAN. THE OPTIONS ARE 1) AMEND THE |
| | DEVELOPMENT PLAN TO BE CONSISTENT WITH THE |
| | COMPREHENSIVE PLAN OR 2) THE COMPREHENSIVE PLAN (AND |
| | ZONING AND LAND DEVELOPMENT REGULATIONS) NEED TO BE |
| | AMENDED. |
| | |
| | 3) UPDATED COMMENT: THE ELEVATIONS MUST ACCURATELY SHOW |
| | THE BUILDING FEATURES THAT ARE SHOWN ON THE PLAN |
| | SHEETS, TO INCLUDE DIMENSIONS (EX. GARAGE OPENINGS, |
| | FACADE WIDTHS, ETC.). FOR EXAMPLE, THERE ARE NO DOORS |
| | SHOWN ANYWHERE ON THE BUILDING ELEVATIONS. PLEASE |
| | INCLUDE HARD LINE (NOT JUST COLOR) ELEVATIONS. **** THE |
| | GROUND FLOOR ELEVATION DRAWINGS DO NOT MATCH THE FLOOR |
| | PLAN. DOORS ARE EITHER NOT SHOWN OR THEY ARE IN THE |
| | WRONG LOCATIONS. ADDITIONALLY, THE SUPPORT COLUMN |
| | SEPARATING THE IN AND OUT LANES AT THE FERN STREET |
| | GARAGE ENTRANCE ARE NOT SHOWN. |
| | |
| | 4) THE PROJECT IS REQUESTING NUMEROUS VARIANCES FROM |
| | THE DMP REQUIREMENTS WITHOUT PROVIDING ADEQUATE |
| | JUSTIFICATION AS TO WHY STAFF SHOULD SUPPORT THE THEM. |
| | THE NEW PORTION OF THE PROJECT OCCUPIES ALMOST THE |
| | ENTIRETY OF A CITY BLOCK AFTER THE ABANDONMENT OF THE |
| | ALLEY, SO THE REQUESTS ARE VARIANCES OF CONVENIENCE AND |
| | DO NOT FOSTER A DESIRABLE RELATIONSHIP WITH THE |
| | SURROUNDING PROPERTIES IN THE DMP. **** STAFF WILL |
| | AWAIT THE UPDATED VARIANCE JUSTIFICATION SUBSEQUENT TO |
| | THE PPRC COMMENTS BEING SUFFICIENTLY ADDRESSED. |
| | |
| | 5) CONDITION: VERIFICATION THAT THE 3-FOOT FPL UTILITY |
| | EASEMENT IS ABANDONED WILL NEED TO BE PROVIDED PRIOR TO |
| | ZONING APPROVING THE BUILDING PERMIT. |
| | |
| | 6) UPDATED COMMENT: THANK YOU FOR DESCRIBING HOW THE |
| | TRASH WILL BE SERVICED. WHILE THE TURNING DIAGRAM FOR |
| | THE COMPACTOR PICK UP WAS PROVIDED, NO TURNING DIAGRAMS |
| | WERE PROVIDED FOR THE OTHER FACILITIES. |
| | |
| | 7) REPEAT COMMENT: PROVIDE THE TPS LETTER FROM PALM |
| | BEACH COUNTY ENGINEERING. |
| | |
| | 8) REPEAT COMMENT: PROVIDE EITHER VERIFICATION THAT THE |
| | PROPOSED TOWER IS NOT WITHIN THE FLIGHT PATH, OR A |
| | LETTER FROM THE FAA OF NO OBJECTION/APPROVAL OF THE |
| | HEIGHT. |
| | |
| | 9) REPEAT COMMENT: PROVIDE THE UPDATED SCAD APPROVAL |
| | FOR THE INCREASED UNIT COUNT. |
| | |
| | 10) REPEAT COMMENT: THANK YOU FOR PROVIDING THE FDOT |
| | PRE-APPLICATION LETTER. PLEASE PROVIDE A COPY OF THE |
| | TRAFFIC STUDY THAT INCLUDES THE INTERSECTION OF |
| | QUADRILLE BOULEVARD AND FERN STREET AND THE NEED FOR A |
| | NORTHBOUND RIGHT TURN LANE THAT WAS PROVIDED TO FDOT AS |
| | WELL AS THE FDOT RESPONSE TO THE TRAFFIC STUDY. THE |
| | FDOT RESPONSE IS REQUIRED PRIOR TO THE SCHEDULING THE |
| | APPLICATION FOR DAC SINCE IF A TURN LANE IS REQUIRED, |
| | THEN THE PLANS NEED TO CHANGE. |
| | |
| | 11) THE BUILDING IS SHOWN EXTENDING PAST THE PROPERTY |
| | LINE ALONG SOUTH DIXIE HIGHWAY ON THE ARCHITECTURAL |
| | PLANS, WHICH IS NOT PERMITTED. ONLY CERTAIN HORIZONTAL |
| | ENCROACHMENTS ARE PERMITTED. |
| | |
| | INCENTIVES |
| | |
| | 12) CONDITION: PRIOR TO THE APPROVAL OF ANY BUILDING |
| | PERMITS, THE APPLICANT SHALL PROVIDE VERIFICATION TO |
| | THE PLANNING DIVISION THAT THE TDRS FOR THE FULL |
| | PROJECT HAVE BEEN ACQUIRED. |
| | |
| | 13) REPEAT COMMENT: THIS PROJECT IS UTILIZING TDRS AND |
| | CONTAINS MORE THAT 25% OF THE SQUARE FOOTAGE IN |
| | RESIDENTIAL USE. PLEASE PROVIDE HOW THE PROJECT |
| | COMPLIES WITH SECTION 94-134 DOWNTOWN MASTER PLAN |
| | HOUSING INCENTIVE PROGRAM. |
| | |
| | 14) UPDATED COMMENT: AS PART OF RECEIVING THE TDRS AND |
| | FOLLOWING THE DOWNTOWN MASTER PLAN HOUSING INCENTIVE |
| | PROGRAM, THE BUILDING THAT IS ELIGIBLE FOR HISTORIC |
| | DESIGNATION LOCATED AT 401 SOUTH DIXIE HIGHWAY IS |
| | REQUIRED TO BE INTEGRATED INTO THE NEW DEVELOPMENT IN A |
| | MANNER WHICH MAINTAINS THE INTEGRITY OF THE HISTORIC |
| | STRUCTURE. WHILE THE RESUBMITTAL CHANGES HAVE BROUGHT |
| | THE BUILDING CLOSER TO COMPLIANCE, THE CITY'S HISTORIC |
| | PRESERVATION PLANNER HAS REVIEWED THE RESUBMITTAL AND |
| | STILL DOES NOT FIND THAT THE EXISTING BUILDING IS |
| | INTEGRATED INTO THE NEW DEVELOPMENT. THIS IS NOT A |
| | REQUIREMENT FOR WHICH A VARIANCE IS PERMITTED. |
| | |
| | A. THE DEVELOPMENT TEAM AND STAFF MET ON OCTOBER 12, |
| | 2022 TO DISCUSS THE RECENT SUBMITTAL AND THE HISTORIC |
| | PRESERVATION PLANNER PROVIDED WHAT IS ACCEPTABLE TO |
| | PROVIDE THE TRANSITION BETWEEN THE TWO BUILDINGS. THIS |
| | SHALL BE SHOWN ON THE RESUBMITTAL AS THE CURRENT PLANS |
| | DO NOT COMPLY. |
| | B. AS STATED IN A PREVIOUS COMMENT, THE ELEVATION |
| | DRAWING DOES NOT MATCH THE SITE PLAN. ONLY ONE DOOR |
| | (STAIRWAY EXIT) IS SHOWN ON THE SITE PLAN, WHILE |
| | MULTIPLE DOORS, WHICH WOULD COMPLY WITH THE INTEGRATION |
| | REQUIREMENT, ARE SHOWN ON THE ELEVATION. |
| | C. CONDITION: THE BUILDING AT 401 SOUTH DIXIE HIGHWAY |
| | SHALL BE PAINTED A COMPATIBLE COLOR TO THE NEW |
| | BUILDING. |
| | |
| | ZONING COMPLIANCE |
| | |
| | 15) UPDATED COMMENT: PLEASE CLARIFY THE FOLLOWING FOR |
| | FAR (NOTE: SITE AREAS NOT UPDATED TO EXCLUDE THE |
| | PREVIOUSLY DEDICATED ROW, SO ALL VALUES WILL CHANGE): |
| | |
| | A. THE MEZZANINE LEVEL STAIR AREAS ARE REQUIRED TO BE |
| | COUNTED TOWARD THE FAR REQUIREMENT. |
| | B. THERE IS A DOOR TO ACCESS THE CORRIDOR FROM THE |
| | TOWNHOMES ON LEVELS 4 AND 6, WHICH WILL REQUIRE THE |
| | CORRIDOR AREA TO BE COUNTED AS FAR. |
| | |
| | 16) REPEAT COMMENT: THE PROJECT IS SHOWN AS CREATING A |
| | NEW INTERIOR PARCEL LINE BETWEEN THE EXISTING 401 SOUTH |
| | DIXIE BUILDING AND THE NEW BUILDING. THE QGD 10-25 |
| | REQUIRES A 20-FOOT SETBACK ABOVE THE 8TH STORY (104 |
| | FEET) FROM THE INTERIOR PARCEL LINE. THIS DOES NOT |
| | OCCUR ON EITHER PORTION OF THE NEW BUILDING THAT IS |
| | ABOVE THIS HEIGHT. STAFF IS NOT PREPARED TO SUPPORT |
| | THIS SETBACK VARIANCE. |
| | |
| | 17) REPEAT COMMENT: PROVIDE VERIFICATION THAT THE |
| | PROPOSED ZERO SETBACK FROM THE INTERIOR PROPERTY LINES |
| | COMPLIES WITH NFPA REQUIREMENTS. **** THIS NEEDS TO BE |
| | VERIFIED AT TIME OF SITE PLAN SO THAT STAFF CAN VERIFY |
| | THAT THE BUILDING CAN BE BUILT AS PROPOSED. |
| | |
| | 18) REPEAT COMMENT: STAFF IS NOT PREPARED TO SUPPORT A |
| | SETBACK FROM SOUTH DIXIE HIGHWAY LESS THAN THE REQUIRED |
| | 27 FEET FOR THE PARKING USES ON LEVEL 6 AND THE 66 FEET |
| | FOR LEVEL 9 OF THE TOWER. **** THIS WAS NOT AMENDED ON |
| | THE CURRENT RESUBMITTAL; HOWEVER, STAFF IS AWAITING THE |
| | RESUBMITTED PLANS BASED ON THE OCTOBER 12, 2022 MEETING |
| | TO RE-EVALUATE THIS COMMENT. |
| | |
| | 19) REPEAT COMMENT: STAFF IS NOT PREPARED TO SUPPORT A |
| | SETBACK FROM GARDENIA LESS THAN THE REQUIRED 27 FEET |
| | FOR THE PARKING USES ON LEVEL 6. **** THIS WAS NOT |
| | AMENDED ON THE CURRENT RESUBMITTAL; HOWEVER, STAFF IS |
| | AWAITING THE RESUBMITTED PLANS BASED ON THE OCTOBER 12, |
| | 2022 MEETING TO RE-EVALUATE THIS COMMENT. |
| | |
| | 20) UPDATED COMMENT: THE BUILDING FOOTPRINT TABLES, AND |
| | DIAGRAMS DO NOT SHOW THE LEVEL 8 AND 9 AMENITY AREAS. |
| | LEVEL 3 IS SHOWN EXCEEDING THE PERMITTED MAXIMUM |
| | BUILDING FOOTPRINT. AN INCREASE IN THE BUILDING |
| | FOOTPRINT IS NOT PERMITTED AS A VARIANCE, SO THE |
| | FOOTPRINT AREA MUST BE REDUCED. (NOTE: SITE AREAS NOT |
| | UPDATED TO EXCLUDE THE PREVIOUSLY DEDICATED ROW, SO ALL |
| | VALUES WILL CHANGE) **** LEVEL 1 WILL ALSO NOT COMPLY |
| | WITH THE ROW AREA REMOVED. |
| | |
| | 21) UPDATED COMMENT: THE TABLES WITH THE ACTIVE USE |
| | DIAGRAMS ARE INCORRECT. NOTE: STAFF IS NOT PREPARED TO |
| | SUPPORT WAIVERS FOR GROUND FLOOR OR LINER ACTIVE USES. |
| | |
| | A. QUADRILLE BOULEVARD IS MISLABELED AS PRIMARY |
| | PEDESTRIAN ON THE TABLE. IT IS AN AVENUE, WHICH |
| | REQUIRES 60% ACTIVE USES AS IS CORRECTLY LISTED. |
| | B. STAFF WILL REVIEW THE ACTIVE USE PERCENTAGES UPON |
| | RESUBMITTAL OF THE PLANS. |
| | |
| | 22) REPEAT COMMENT: THE DRAWINGS SHOW THAT THE GARDENIA |
| | FRONTAGE DOES NOT COMPLY WITH THE MINIMUM PLANAR BREAK |
| | REQUIREMENTS. STAFF IS NOT PREPARED TO SUPPORT BUILDING |
| | DESIGNS THAT DO NOT PROVIDE THE REQUIRED PLANAR BREAKS. |
| | **** 20% PLANAR BREAK IS REQUIRED. |
| | |
| | A. GARDENIA GROUND FLOOR - THE PLANAR BREAK DIAGRAM |
| | INCORRECTLY DEPICTS THE BUILDING FRONTAGE THAT IS USED |
| | TO DETERMINE THE PLANAR BREAK REQUIREMENTS. THE PLANAR |
| | BREAK IS BASED ON THE PROVIDED BUILDING FRONTAGE |
| | (387.17 FEET) NOT THE BUILDABLE FRONTAGE AS LISTED. |
| | B. THE TWO INSETS, GENERALLY 7 FEET IN WIDTH, DO NOT |
| | MEET THE MINIMUM 3-FOOT PLANAR BREAK DEPTH AND MAY NOT |
| | BE COUNTED TOWARD MEETING THE PLANAR BREAK REQUIREMENT |
| | ON ANY FLOOR. PLEASE NOTE THAT HORIZONTAL PROJECTIONS |
| | DO NOT QUALIFY AS PLANAR BREAK DEPTH. |
| | C. PROVIDE THE DEPTH DIMENSION FROM THE EASTERN STAIRS |
| | ALONG GARDENIA TO THE MAIN BUILDING FA??ADE SO STAFF |
| | CAN VERIFY THAT IT COMPLIES WITH THE 3-FOOT DEPTH |
| | MINIMUM. STAFF HAS SCALED THE DRAWINGS AND IT SEEMS TO |
| | BE AT LEAST 3 FEET IN DEPTH. |
| | D. GARDENIA GROUND FLOOR - 77.43 FEET REQUIRED; 63.33 |
| | FEET PROVIDED. 14.1 FEET SHY |
| | E. GARDENIA GROUND FLOORS - 78.83 FEET REQUIRED; 70.75 |
| | FEET PROVIDED. 8.1 FEET SHY |
| | |
| | 23) UPDATED COMMENT: FACADES LESS THAN OR EQUAL TO 3 |
| | FEET FROM A SIDE LOT LINE AND NOT ABUTTING AN ADJACENT |
| | BUILDING SHALL INCORPORATE A PLANAR BREAK OR MULTIPLE |
| | PLANAR BREAKS A MINIMUM OF 8 INCHES IN DEPTH. THE |
| | CUMULATIVE HORIZONTAL LENGTH OF ALL PLANAR BREAKS SHALL |
| | BE GREATER THAN OR EQUAL TO 5% OF THE FACADE WIDTH. |
| | INFORMATION TO VERIFY COMPLIANCE HAS NOT BEEN PROVIDED |
| | ON THE PLANS. THIS INCLUDES THE DIMENSION TO THE NEW |
| | INTERIOR PROPERTY LINE ON EITHER SIDE OF THE 401 SOUTH |
| | DIXIE BUILDING AS WELL AS THE DEPTH AND LENGTH OF THE |
| | PLANAR BREAKS. PLEASE NOTE THAT HORIZONTAL PROJECTIONS |
| | DO NOT QUALIFY AS PLANAR BREAK DEPTH. TABLE IV-4 DOES |
| | NOT SPECIFY A MINIMUM TOWER LENGTH WHERE PLANAR BREAKS |
| | ARE REQUIRED. THE 150-FOOT LENGTH CITED IN THE RESPONSE |
| | ONLY APPLIES TO THE GROUND FLOOR AND PODIUM. |
| | |
| | 24) REPEAT COMMENT: THERE ARE HORIZONTAL PROJECTIONS |
| | SHOWN ON THE PLANS. THANK YOU FOR PROVIDING THE DEPTHS; |
| | HOWEVER, THEY NEED TO BE LABELED AS TO WHAT THEY ARE SO |
| | THAT STAFF CAN VERIFY COMPLIANCE WITH THE CODE |
| | ALLOWANCES. **** ACKNOWLEDGED IS NOT AN ADEQUATE |
| | RESPONSE. |
| | |
| | A. AT THE GROUND FLOOR, HORIZONTAL PROJECTIONS THAT |
| | HAVE A MINIMUM CUMULATIVE HORIZONTAL LENGTH OF 50% OF |
| | THE BUILDING FRONTAGE SHALL BE PROVIDED. THIS IS NOT |
| | SHOWN ON ANY ELEVATION, TABLE OR PLAN VIEW. |
| | B. PLEASE CLARIFY THAT THE ENTRY CANOPY WAS REMOVED. IT |
| | IS UNCLEAR ON THE PLANS. NO INFORMATION WAS PROVIDED ON |
| | ITS HEIGHT FROM GRADE. |
| | |
| | 25) THE SETBACK ALONG GARDENIA STREET DOES NOT MEET THE |
| | MINIMUM 12 FEET REQUIRED FROM THE BACK OF CURB. THE |
| | ARCHITECTURAL PLAN SHOWS THE 12-FOOT SETBACK FROM THE |
| | FRONT OF THE CURB AND THE CIVIL PLAN SHOWS THE SETBACK |
| | AT 11.2 FEET FROM THE BACK OF THE CURB. |
| | |
| | 26) THE PORTION OF THE EAST SIDE OF THE BUILDING NORTH |
| | OF THE UTILITY VAULT ROOM ALONG SOUTH DIXIE HIGHWAY |
| | DOES NOT MEET THE MINIMUM 12 FEET REQUIRED FROM THE |
| | BACK OF CURB. THE ARCHITECTURAL PLAN SHOWS THE 12-FOOT |
| | DIMENSION FROM THE BACK OF THE CURB TO THE INSIDE WALL |
| | AND THE CIVIL PLAN SHOWS THE 12-FOOT DIMENSION FROM THE |
| | FACE OF THE CURB TO THE EXTERIOR WALL. NEITHER MEETS |
| | THE MINIMUM SETBACK. |
| | |
| | STREETSCAPE |
| | |
| | 27) REPEAT COMMENT: THE TRANSFORMERS AND SWITCH |
| | CABINETS SHOWN ON THE LANDSCAPE AND CIVIL PLANS |
| | ADJACENT TO SOUTH DIXIE HIGHWAY ARE NOT PERMITTED. |
| | THESE ARE NOT PERMITTED WITHIN YOUR STREETSCAPE AREA. |
| | NOTE: THIS IS NOT SHOWN ON THE ARCHITECTURAL PLANS. |
| | **** NOTE: THERE IS AN UNUSED AREA ADJACENT TO THE |
| | TRASH ROOM IN THE PARKING AREA THAT SHOULD BE USED FOR |
| | AN ELECTRICAL ROOM FOR THESE ITEMS. |
| | |
| | 28) INADEQUATE INFORMATION WAS PROVIDED TO VERIFY THAT |
| | THE PROJECT COMPLIES WITH ALL THE PROVISIONS OF SECTION |
| | 94-113. - LANDSCAPE AND STREETSCAPE REQUIREMENTS. THIS |
| | INCLUDES: |
| | |
| | A. REPEAT COMMENT: EXTERIOR LIGHTING - NOT PROVIDED TO |
| | BACK OF CURB. **** THIS NEEDS TO BE FOR THE ENTIRE |
| | SITE, INCLUDING 401 SOUTH DIXIE, AND COMPLY WITH THE |
| | REQUIREMENT OF SECTION 94-113.B. |
| | B. REPEAT COMMENT: SITE VISIBILITY TRIANGLE |
| | REQUIREMENTS - NOT PROVIDED FOR DRIVEWAY ENTRANCES. |
| | C. UPDATED COMMENT: STREETSCAPE REQUIREMENTS. |
| | I. THE STREETLIGHTS DO NOT MEET THE CITY STANDARD FOR |
| | HEIGHT OR STYLE. |
| | II. NO CROSS SECTIONS PROVIDE TO VERIFY THAT THE |
| | SIDEWALK ELEVATIONS ARE MAINTAINED ACROSS THE DRIVEWAYS |
| | (CROSS SECTION LOCATION TAGS WERE NOT PROVIDED FOR |
| | STAFF TO VERIFY WHERE THE CROSS SECTION IS). |
| | III. THE STREET TREES ALONG FERN STREET EXCEED THE |
| | MAXIMUM SPACING OF 30 FEET ON CENTER. STAFF WILL NOT |
| | SUPPORT A VARIANCE TO THIS REQUIREMENT. THE AREAS ON |
| | EITHER SIDE OF THE BUILDING ENTRANCE AND THE BULB OUT |
| | BY THE MICRO MOBILITY STATION FAIL TO MEET THIS |
| | STANDARD. |
| | |
| | 29) UPDATED COMMENT: THANK YOU FOR PROVIDING THE |
| | BICYCLE REQUIREMENTS FOR THE NEW BUILDING; HOWEVER, THE |
| | TABLE DID NOT INCLUDE THE REQUIRED STREETSCAPE BICYCLE |
| | REQUIREMENTS AND HOW THIS IS COMPLIED WITH. |
| | |
| | 30) REPEAT COMMENT: THANK YOU FOR PROVIDING THE TYPE OF |
| | BICYCLE RACK PROPOSED. THE PLANS DO NOT MEET THE |
| | MINIMUM DIMENSIONS THAT ARE SHOWN ON THE PROVIDED |
| | INSTALLATION DETAIL. THE PLANS MUST SHOW THE CORRECT |
| | DIMENSIONS. ADDITIONALLY, THE ORIENTATION OF THE |
| | BICYCLE RACKS DOES NOT PERMIT CONVENIENT PARKING OF THE |
| | BICYCLES. |
| | |
| | A. THERE ARE THREE CITY INSTALLED BICYCLE RACKS THAT |
| | EXIST ALONG FERN STREET IN FRONT OF THE 401 SOUTH DIXIE |
| | BUILDING THAT NO LONGER APPEAR ON THE PLANS. THESE |
| | SHOULD NOT BE REMOVED AND COUNT TOWARD MEETING THE |
| | STREETSCAPE REQUIREMENT. |
| | B. THE TWO RACKS SHOWN AT GARDENIA AND SOUTH DIXIE ARE |
| | NOT LOCATED ADJACENT TO A BUILDING ENTRANCE. THESE (IF |
| | MEETING THE REQUIRED NUMBERS) SHALL BE PLACED CLOSER TO |
| | A BUILDING ENTRANCE. |
| | C. THE TWO RACKS SHOWN IN FRONT OF 401 SOUTH DIXIE ARE |
| | LOCATED DIRECTLY IN FRONT OF A BUILDING ENTRANCE AND |
| | NEED TO BE RELOCATED. |
| | D. THE TWO RACKS AT THE CORNER OF GARDENIA AND |
| | QUADRILLE SHALL BE RELOCATED TO AN AREA ALONG QUADRILLE |
| | THAT IS VISIBLE FROM THE ENTRANCE TO THE RETAIL. |
| | |
| | 31) THANK YOU FOR SHOWING THE EXISTING BICYCLE LANE |
| | ALONG FERN STREET. THE DRAWINGS SHOW THAT THE TWO NEW |
| | BULB OUTS ON EITHER OF THE ENTRANCES TO THE GARAGE |
| | BLOCK THE BICYCLE LANE, WHICH IS NOT PERMITTED. |
| | |
| | 32) CONDITION: MAINTENANCE AGREEMENTS WILL BE REQUIRED |
| | FOR ALL LANDSCAPING, TREE GRATES, STRUCTURAL SOIL AND |
| | IRRIGATION. |
| | |
| | DESIGN/ARCHITECTURE |
| | |
| | 33) REPEAT COMMENT: THE DESIGN INTENT OF THE QUADRILLE |
| | GARDEN DISTRICT IS FOR PROJECTS TO HAVE A HIGH |
| | PERCENTAGE OF LANDSCAPING AND TREE CANOPY. THE PROJECT |
| | AS PRESENTED DOES NOT APPEAR TO MEET EITHER ONE OF |
| | THESE STANDARDS. **** THE OPEN SPACE TABLES SHOW THAT |
| | THE VEGETATION MINIMUMS ARE NOT MET, WHICH DIRECTLY |
| | CONTRADICTS THE DISTRICT DESIGN INTENT. STAFF WILL NOT |
| | SUPPORT A VARIANCE TO REDUCE THE OPEN SPACE VEGETATED |
| | AREA MINIMUMS. |
| | |
| | 34) REPEAT COMMENT: THE PROPOSED LOADING AREA ENTRANCE |
| | ALONG GARDENIA IS DIRECTLY ACROSS FROM THE PROPOSED |
| | LOBBY ENTRANCE OF THE APPROVED AC MARRIOT HOTEL. THE |
| | PROPOSED DESIGN PRESENTS A NEGATIVE IMPACT TO AN |
| | APPROVED NEIGHBORING PROJECT. THE RESPONSE STATES THAT |
| | THE ELEVATION IN THIS AREA IS STILL BEING WORKED ON. |
| | |
| | PARKING |
| | |
| | 35) BASED ON THE CHANGES DISCUSSED AT THE OCTOBER 12, |
| | 2022 MEETING AND NOT SHOWN ON THE PLANS, STAFF WILL NOT |
| | BE PERFORMING A FULL PARKING REVIEW UNTIL THE UPDATED |
| | PLANS ARE SUBMITTED. |
| | |
| | 36) REPEAT COMMENT: THE PROPOSED DEVELOPMENT PLAN |
| | REMOVES ALL OF THE CURRENT SURFACE PARKING FOR THE 401 |
| | SOUTH DIXIE BUILDING (NOTE - PART OF THE REQUIRED |
| | PARKING WAS ALREADY SOLD OFF, CREATING A PARKING |
| | DEFICIENCY, WHICH VIOLATES THE ZONING AND LAND |
| | DEVELOPMENT REGULATIONS). PROVIDE A PARKING TABLE WITH |
| | A BREAKDOWN OF THE USES WITHIN THE 401 SOUTH DIXIE |
| | BUILDING AND THE REQUIRED NUMBER OF PARKING SPACES. |
| | |
| | 37) CONDITION: PRIOR TO ISSUANCE OF ANY PERMIT THAT |
| | REMOVES PARKING FOR THE 401 SOUTH DIXIE BUILDING, A |
| | PARKING PLAN THAT CLEARLY DEMONSTRATES THAT THE MINIMUM |
| | REQUIRED PARKING FOR 401 SOUTH DIXIE IS PROVIDED MUST |
| | BE SUBMITTED TO AND APPROVED BY THE PLANNING DIVISION. |
| | THE PARKING SHALL COMPLY WITH ALL APPLICABLE |
| | REGULATIONS. |
| | |
| | 38) UPDATED COMMENT: THE PARKING TABLES NEED TO PROVIDE |
| | LINE ITEMS FOR TANDEM AND COMPACT SPACES. |
| | |
| | 39) PLEASE PROVIDE THE ANGLE FOR THE PARKING SPACES ON |
| | THE LEVEL 1 GARAGE SO THAT STAFF CAN VERIFY THAT THE |
| | AISLE WIDTHS MEET CODE MINIMUMS. |
| | |
| | 40) FOR RESIDENTIAL USES, TANDEM PARKING MAY COUNT AS |
| | TWO SPACES, PROVIDED BOTH SPACES ARE DEDICATED TO THE |
| | SAME RESIDENTIAL UNIT, AND A RESTRICTIVE COVENANT IS |
| | RECORDED ON CITY APPROVED FORMS, AND RECORDED IN THE |
| | PUBLIC RECORDS. THE TANDEM SPACES ARE NOT PERMITTED TO |
| | BE COMBINED WITH GUEST SPACES. PLEASE NOTE, IF CODE |
| | COMPLIANT TANDEM SPACES ARE PROVIDED, THEY MAY NOT |
| | INCLUDE WHEEL STOPS BETWEEN THE SPACES. |
| | |
| | 41) PLEASE CONSIDER INCLUDING EV CHARGING SPACES FOR |
| | ALL THE USER GROUPS. THIS SHOULD ALSO INCLUDE PREWIRING |
| | THE GARAGE AND INCLUDING EXTRA AREA FOR PANELS IN THE |
| | ELECTRIC ROOM FOR FUTURE EV INSTALLATIONS. |
| | |
| | 42) THE PARKING SPACE DETAIL FOR REGULAR PARKING |
| | INCORRECTLY SHOWS THE STRIPES AS BLUE, NOT WHITE. |
| | PLEASE CORRECT. |
| | |
| | 43) UPDATED COMMENT: THANK YOU FOR MARKING THE GUEST |
| | PARKING ON THE PLANS. HOW DO GUESTS ACCESS THE GUEST |
| | SPACES BEHIND THE GATE? |
| | |
| | 44) REPEAT COMMENT: THERE ARE DEAD END PARKING ROWS ON |
| | MULTIPLE LEVELS, WHICH ARE NOT PERMITTED WITHOUT A |
| | TURNAROUND SPACE OR IF ALL SPACES ON THAT LEVEL ARE |
| | ASSIGNED PARKING. **** THE RESPONSE STATES THAT ALL |
| | DEAD END ROWS HAVE A TURNAROUND SPACE. THIS DOES NOT |
| | OCCUR ON ANY OF THE PARKING LEVELS WITH DEAD END |
| | PARKING ROWS. |
| | |
| | 45) UPDATED COMMENT: ONE EXISTING METERED ON-STREET |
| | PARKING SPACES ON FERN STREET IS SHOWN AS BEING |
| | REMOVED. YOU NEED TO PROVIDE VERIFICATION FROM THE THE |
| | CITY'S PARKING ADMINISTRATOR OF HIS APPROVAL TO |
| | PERMANENTLY REMOVE THE PARKING SPACE AND ANY |
| | CONDITIONS, INCLUDING FEE, THAT ARE REQUIRED PRIOR |
| | SCHEDULING A HEARING BEFORE THE DAC. **** PLEASE NOTE |
| | THAT THE RESPONSE INCORRECTLY STATES THAT THERE ARE |
| | THREE ON-STREET PARKING SPACES ON SOUTH DIXIE. THE |
| | PLANS CORRECTLY SHOW THE TWO SPACES. |
| | |
| | 46) UPDATED COMMENT: THE RESPONSE STATES THAT THE |
| | ON-STREET AREA IN FRONT OF THE RESIDENTIAL BUILDING |
| | ENTRANCE WILL BE A RESIDENTIAL DROP OFF; HOWEVER, THE |
| | RESPONSE TO THE PREVIOUS COMMENT STATES THAT THERE WILL |
| | BE FIVE PARALLEL PARKING SPACES, WHICH IS ALSO SHOWN ON |
| | THE PLANS. BOTH CANNOT OCCUR. THE SPACES WILL EITHER BE |
| | METERED PARKING SPACES OR THE CITY'S PARKING |
| | ADMINISTRATOR APPROVAL OF THEIR REMOVAL, WITH ANY |
| | CONDITIONS, MUST BE PROVIDED PRIOR TO SCHEDULING A |
| | HEARING BEFORE THE DAC. |
| | |
| | 47) REPEAT COMMENT: NONE OF THE DRIVEWAY OPENING COMPLY |
| | WITH THE REQUIREMENT THAT CURB CUTS, PARKING ENTRANCES, |
| | EXITS, AND DRIVEWAYS SHALL NOT BE WIDER THAN 25 FEET AS |
| | MEASURED PARALLEL TO THE STREET AT THE CURB. |
| | |
| | A. STAFF UNDERSTANDS THAT THE TRUCK MANEUVERING MAY |
| | REQUIRE AN OPENING GREATER THAN 25 FEET; HOWEVER, STAFF |
| | IS NOT PREPARED TO SUPPORT THE REDUCED OPENING WIDTH. |
| | B. STAFF IS NOT PREPARED TO SUPPORT A WAIVER TO THE |
| | MAIN BUILDING ENTRY DRIVE WHICH IS SHOWN AROUND 40 FEET |
| | ON FERN STREET. FERN STREET IS CLASSIFIED AS A PRIMARY |
| | PEDESTRIAN STREET. THE PROPOSED DRIVEWAY WIDTH DOES NOT |
| | PROMOTE A FAVORABLE PEDESTRIAN EXPERIENCE. |
| | |
| | 48) REPEAT COMMENT: A PORTION OF THE ENTRANCE RAMP IS |
| | GREATER THAN 14 PERCENT SLOPE, WHICH REQUIRES A |
| | BREAK-OVER TRANSITION. **** THIS NEEDS TO BE SHOWN WITH |
| | THESE PLANS SO THAT VERIFICATION IS PROVIDED THAT THE |
| | PLANS CONTINUE TO MEET CODE WHEN THE BREAK-OVER |
| | TRANSITION IS PROVIDED. |
| | |
| | 49) REPEAT COMMENT: THE BICYCLE ROOMS SHOWN IN THE |
| | PLANS SHALL BE PROVIDED AT A LARGER SCALE WITH |
| | DIMENSIONS AND THE SPECIFIC RACK SYSTEM THAT IS |
| | PROPOSED. |
| | |
| | 50) CONDITION: THE BUILD OUT OF THE RETAIL AREA |
| | REQUIRES THE PROVISION OF A SHOWER AND CHANGING |
| | FACILITY. |
| | |
| | 51) REPEAT COMMENT: THE TRUCK TURN PLANS MUST NOT ONLY |
| | SHOW THE AC MARRIOT CHANGES TO THE GARDENIA |
| | RIGHT-OF-WAY BUT ALSO A SHEET THAT SHOWS THE TURNING |
| | MOVEMENTS FOR THE EXISTING GARDENIA RIGHT-OF-WAY. THE |
| | PLAN FOR THE FUTURE CONFIGURATION OF GARDENIA SHOWS THE |
| | TRUCKS CLIPPING THE PARALLEL PARKING SPACES, WHICH DOES |
| | NOT FUNCTION IF CARS ARE PARKED IN THE SPACES. |
| | |
| | 52) SHOW TRAFFIC CONTROL AIDES AT THE BOTTOM OF THE |
| | FERN STREET RAMP AND THE SOUTH DIXIE EXIT TO STOP |
| | TRAFFIC PRIOR TO THE PEDESTRIAN CROSSING LOCATIONS AND |
| | AT THE SOUTH DIXIE ENTRANCE TO WARN DRIVERS TO SLOW |
| | WHEN ENTERING THE GARAGE DUE TO THE TWO PARKING SPACES |
| | THAT BACK AT THE ENTRANCE. |
| | |
| | OPEN SPACE |
| | |
| | 53) THE RESPONSE STATES THAT THE OPEN SPACE TABLES WILL |
| | BE UPDATED IN THE NEXT SUBMITTAL. AS SUCH STAFF DID NOT |
| | SPEND TIME REVIEWING THE CURRENT TABLES TO VERIFY |
| | COMPLIANCE. |
| | |
| | 54) UPDATED COMMENT: PROVIDE THE HEIGHT DIMENSION |
| | (ELEVATION TAGS) OF ALL FEATURES ABOVE LEVEL 9 IN A |
| | PLAN VIEW. |
| | |
| | 55) REPEAT COMMENT: THE PRIVATE OPEN SPACE TABLES ON |
| | SHEETS A0.01 AND A0.09 SHOW DIFFERENT VALUES. (NOTE: |
| | SITE AREAS NOT UPDATED TO EXCLUDE THE PREVIOUSLY |
| | DEDICATED ROW, SO ALL VALUES WILL CHANGE) ALL TABLES |
| | NEED TO SHOW CONSISTENT, ACCURATE INFORMATION. |
| | |
| | |
| |