2022-10-05 12:32:32PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -C301 CALLS FOR 6 INCH DCDA BUT THERE IS 8 INCH POINT
 OF SERVICE VALVE AND 8 INCH PIPE. NOT SURE IF 6 INCH
 SIZE IS INTENTIONAL, BUT IT WOULD BE BILLED AS 8 INCH
 FIRELINE.
 -C301 RESIDENTIAL SERVICE ENLARGEMENT LOOKS TO HAVE THE
 WORDS ABOVE GROUND BLOCKED SO THAT IT IS UNREADABLE
 BELOW USC APPROVED ONLY. PLEASE SHOW ABOVE GROUND
 WORDING CLEARLY.
 -AT ENGINEERING DEVELOPMENT SUBMITTAL, DESIGN OF WATER
 SERVICES MAY NEED REVISION OR ADJUSTMENT UPON FURTHER
 REVIEW.
 -ALL EXISTING UTILITIES IN GARDENIA MAY NOT BE SHOWN.
 PLEASE VERIFY AT ENGINEERING DEVELOPMENT SUBMITTAL.
 -THE FOOTPRINT OF THE 6 INCH DOMESTIC METER BUILD IS
 LIKELY MUCH LARGER THAN SHOWN ON C301.
 -HISTORIC PICTURES OF SOUTHEAST AREA OF EXISTING 3
 STORY BUILDING SHOW DOORS ADJACENT TO PROPOSED BIKE
 RACKS. ENSURE THAT BIKE RACKS WILL NOT BLOCK PEDESTRIAN
 TRAFFIC FROM FUNCTIONAL DOORWAYS.
 -SHEET C300 EAST SIDE OF BUILDING. DOOR SHOULD NOT OPEN
 INTO RIGHT OF WAY. THIS IS A REPEAT COMMENT THAT STILL
 HAS NOT BEEN RESOLVED THOUGH IT HAS BEEN ACKNOWLEDGED
 IN RESPONSE LETTERS. VINCE NOEL HAS ALSO PROVIDED
 SIMILAR REVIEW COMMENTS ABOUT IT.
 RESPECTFULLY,
 MARK HURLEY [email protected]