| Notes |
| Date |
Text |
| 2022-10-05 12:32:32 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | -C301 CALLS FOR 6 INCH DCDA BUT THERE IS 8 INCH POINT | | | OF SERVICE VALVE AND 8 INCH PIPE. NOT SURE IF 6 INCH | | | SIZE IS INTENTIONAL, BUT IT WOULD BE BILLED AS 8 INCH | | | FIRELINE. | | | -C301 RESIDENTIAL SERVICE ENLARGEMENT LOOKS TO HAVE THE | | | WORDS ABOVE GROUND BLOCKED SO THAT IT IS UNREADABLE | | | BELOW USC APPROVED ONLY. PLEASE SHOW ABOVE GROUND | | | WORDING CLEARLY. | | | -AT ENGINEERING DEVELOPMENT SUBMITTAL, DESIGN OF WATER | | | SERVICES MAY NEED REVISION OR ADJUSTMENT UPON FURTHER | | | REVIEW. | | | -ALL EXISTING UTILITIES IN GARDENIA MAY NOT BE SHOWN. | | | PLEASE VERIFY AT ENGINEERING DEVELOPMENT SUBMITTAL. | | | -THE FOOTPRINT OF THE 6 INCH DOMESTIC METER BUILD IS | | | LIKELY MUCH LARGER THAN SHOWN ON C301. | | | -HISTORIC PICTURES OF SOUTHEAST AREA OF EXISTING 3 | | | STORY BUILDING SHOW DOORS ADJACENT TO PROPOSED BIKE | | | RACKS. ENSURE THAT BIKE RACKS WILL NOT BLOCK PEDESTRIAN | | | TRAFFIC FROM FUNCTIONAL DOORWAYS. | | | -SHEET C300 EAST SIDE OF BUILDING. DOOR SHOULD NOT OPEN | | | INTO RIGHT OF WAY. THIS IS A REPEAT COMMENT THAT STILL | | | HAS NOT BEEN RESOLVED THOUGH IT HAS BEEN ACKNOWLEDGED | | | IN RESPONSE LETTERS. VINCE NOEL HAS ALSO PROVIDED | | | SIMILAR REVIEW COMMENTS ABOUT IT. | | | RESPECTFULLY, | | | MARK HURLEY [email protected] |
| |