| 2022-12-05 15:31:55 | -PROVIDE VERTICAL DATUM AND DATUM CONVERSION |
| | INFORMATION (NAVD 1988 AND NGVD 1929). |
| | -?? SHOW PROJECT ADDRESS ON ALL PLAN SHEETS. |
| | -?? PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE |
| | STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC. |
| | - PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND |
| | DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND |
| | SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH |
| | PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE |
| | AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS, |
| | BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO |
| | BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS, |
| | DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS, |
| | ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT |
| | ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF |
| | SANITARY SEWER LINES. |
| | - GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR |
| | SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE |
| | PROFILE VIEW. |
| | -?? PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER |
| | AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD |
| | DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS. PLEASE |
| | INCLUDE FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION & |
| | TELECOMMUNICATION FACILITIES INCLUDING PIPE SIZE AND |
| | MATERIAL LOCATED IN THE RIGHT-OF-WAY. |
| | - PROVIDE FIRE FLOW TEST DATA. |
| | -PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER ALONG |
| | ENTIRE PROJECT FRONTAGE WHERE CONNECTION IS PROPOSED |
| | (CONDITION OF SITE PLAN APPROVAL). |
| | -CUT AND CAP UTILITIES NOT IN USE AND REMOVE ANY |
| | ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY |
| | ROW. |
| | - WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL |
| | BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY |
| | PROPOSED LENGTH IN FEET. |
| | - CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY |
| | SEWER ARE REQUIRED. |
| | -PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE |
| | JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET. |
| | -ADD NOTE TO PLANS SPECIFYING CITY???S DOWNSTREAM LIFT |
| | STATION NUMBER. (PROJECT FALLS WITHIN LIMITS OF LIFT |
| | STATION 40) |
| | -PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR |
| | PROPOSED SANITARY LATERALS. |
| | -PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN |
| | OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER. |
| | - EXISTING MANHOLES THAT ARE PROPOSED TO HAVE NEW |
| | CONNECTIONS WILL NEED TO BE REHABBED |
| |