| 2022-07-13 09:25:26 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: |
| | |
| | -VERIFY SEMI TRUCKS CAN ENTER GARDENIA FROM QUADRILLE |
| | AND EXIT GARDENIA ONTO DIXIE SAFELY. |
| | |
| | -THERE ARE SOME EXISTING UTILITY EASEMENTS NEAR THE |
| | WEST SIDE OF THE PROPERTY. WHAT IS HAPPENING TO THEM? |
| | |
| | -ON UTILITY PLAN, SHOW ALL EXISTING WATER AND SEWER |
| | SERVICES AND LABEL WHAT IS HAPPENING TO THEM. |
| | |
| | -BACKFLOW ASSEMBLIES SHOULD ON PRIVATE PROPERTY AND NOT |
| | IN RIGHT OF WAY. |
| | |
| | -PAVEMENT RESTORATION MAY BE NEEDED ON GARDENIA, FERN, |
| | AND DIXIE DUE TO PROPOSED UTILITY WORK IN ROAD. THERE |
| | MAY ALSO BE WATER SERVICES NEEDING REMOVAL IN THOSE |
| | AREAS. |
| | |
| | -THERE SEEMS TO BE AN EXISTING FIRELINE BACKFLOW |
| | ASSEMBLY NEAR THE NORTHWEST AREA OF PROPERTY. PLEASE |
| | ACCOUNT FOR IT IN PLANS. |
| | |
| | -METERS OVER 2 INCH SIZE NEED BE ABOVE GROUND. ADD |
| | ABOVE GROUND WORDING ON LABELS OF UTILITY PLAN. |
| | |
| | -DEMO PLAN SHOWS LARGE EXISTING VAULT IN FRONT OF 415 |
| | S. DIXIE. WHAT TYPE OF UTILITY IS IT AND WHAT WILL |
| | HAPPEN TO IT? |
| | |
| | -ON C102 TRUCK TURN PLAN, PLEASE SHOW CURBING AND |
| | PARKING SPACES ON SOUTH SIDE OF GARDENIA FROM QUADRILLE |
| | TO DIXIE. |
| | |
| | -THERE ARE MANY EXISTING CITY PARKING SPOTS AND A BIKE |
| | PATH ON SOUTH SIDE OF FERN ST. WILL ANY OF THOSE BE |
| | AFFECTED BY THE PROJECT? |
| | |
| | -3 INCH METER REQUIRES 4 INCH TAP AND SERVICE LINE PER |
| | WPB STANDARD DETAILS. |
| | |
| | -SHOW UTILITY EASEMENT AROUND METERED WATER SERVICE ON |
| | PRIVATE PROPERTY. BACKFLOW ASSEMBLY SHOULD NOT BE IN |
| | UTILITY EASEMENT. |
| | |
| | -ON UTILITY PLAN, LEADER LINE FOR FPL DUCT BANK DOES |
| | NOT APPEAR POINTED CORRECTLY. |
| | |
| | -SEVERAL POSSIBLE CONFLICTS BETWEEN DUCT BANK IN ROW |
| | AND OTHER UTILITIES. |
| | |
| | -CONSIDER PARALLEL/DUAL BACKFLOW ASSEMBLIES ON DOMESTIC |
| | WATER SERVICES TO MINIMIZE WATER OUTAGES DURING |
| | BACKFLOW MAINTENANCE. |
| | |
| | -FOOTPRINT OF METERS AND BACKFLOWS MAY BE LARGER THAN |
| | SHOWN ON UTILITY PLAN. |
| | |
| | -SHOW EXISTING UTILITIES FOR NORTHEAST 3 STORY BUILDING |
| | ON CIVIL PLANS. |
| | |
| | -C300 UTILITY NOTE 4, WATER SERVICE LINES OVER 2 INCH |
| | SIZE NEED BE DIP. |
| | |
| | -IS SEPARATE METERED IRRIGATION WATER SERVICE NEEDED? |
| | |
| | -ON CIVIL PLANS 401 S. DIXIE IS NOT SEPARATED FROM REST |
| | OF BLOCK WITH PROPERTY LINES. WILL ENTIRE BLOCK BE ONE |
| | PROPERTY? |
| | |
| | --FIRELINE BACKFLOW NEED BE ON PRIVATE PROPERTY, OUT OF |
| | RIGHT OF WAY, AND MUST COMPLY WITH ALL NFPA RULES |
| | REGARDING LOCATION. |
| | |
| | -ADD NOTE TO UTILITY PLAN: LINESTOPS OR INSERTION |
| | VALVES MAY BE REQUIRED AS DIRECTED BY CITY WPB OR EOR |
| | TO MINIMIZE WATER OUTAGES TO CUSTOMERS. |
| | |
| | -ADD WATER SERVICE STANDARD DETAILS 4 AND 4.1 TO CIVIL |
| | PLAN SET |
| | |
| | -ADD STANDARD DETAIL GS-5 TO CIVIL PLAN SET |
| | |
| | -ADD WATER AND SEWER DEMAND CALCULATIONS TO UTILITY |
| | PLAN. |
| | |
| | -LABEL S. QUADRILLE BLVD ON CIVIL PLANS. |
| | |
| | |
| | |
| |