Plan Review Notes
Plan Review Notes For Project Z22050021
Project Number Z22050021
Review Stop PU-CS
Sequence Number 3
Notes
Date Text
2022-08-16 15:22:12PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
  
 -NOT SATISFIED WITH RESPONSE TO REVIEW COMMENT NUMBER 4
 IN LETTER DATED 12AUG2022. BACKFLOW ASSEMBLY LOCATIONS
 ARE NOT ACCEPTABLE. THE MOST CONCERNING IS THE LONG
 DISTANCE FROM THE METERS, POINT OF SERVICE, AND
 PROPERTY LINES. NEED DISTANCE REDUCED SUBSTANTIALLY ON
 THEM.
  
 -PAVEMENT RESTORATION BOUNDARIES IN RIGHT OF WAY MAY
 STILL BE SMALLER THAN REQUIRED. WILL REVIEW FURTHER AT
 ENGINEERING DEVELOPMENT SUBMITTAL.
  
 -WILL REVIEW CUT AND CAP LOCATIONS AT ENGINEERING
 DEVELOPMENT SUBMITTAL. MAY HAVE TO CUT BACK FURTHER
 THAN PROPOSED.
  
 -AS REQUESTED IN RESPONSE FOR REVIEW COMMENT NUMBER 9
 IN LETTER DATED 12AUG2022, MORE INFO ABOUT DIMENSIONS
 AND FOOTPRINT OF LARGE METERED WATER SERVICES CAN BE
 FOUND IN WPB STANDARD DETAILS WS4, WS4.1, AND AWWA M6
 MANUAL PG 49 TABLE 4 DASH 1.
  
 -ENSURE THAT ANY LIGHT POSTS IN LT1 ARE LOCATED MINIMUM
 3 FEET AWAY FROM UTILITIES SUCH AS WATER METER BOXES.
  
 RESPECTFULLY,
  
 MARK HURLEY
 [email protected]
  