Plan Review Notes
Plan Review Notes For Project Z22050021
Project Number Z22050021
Review Stop PU-CS
Sequence Number 2
Notes
Date Text
2022-07-14 11:08:00-STILL COULD NOT FIND VISUAL BOUNDARIES OF PAVEMENT
 RESTORATION ON THE ADJACENT ROADWAYS WHERE UTILITY
 EXCAVATION IS PROPOSED. PLEASE MAKE SURE COMPLIES WITH
 OVERSEEING AGENCY REQUIREMENTS AND SHOW ON CIVIL PLANS.
 -THERE ARE STILL MANY UNACCOUNTED FOR UTILITIES SUCH AS
 METERED WATER SERVICES AND SEWER LATERALS WHERE REMOVAL
 IS NOT SHOWN ON DEMO OR UTILITY PLANS. WILL LIKELY NEED
 TO GO INTO DIXIE HWY FOR SOME OF THAT REMOVAL.
 -COULD NOT FIND THE WORDING ABOVE GROUND ON LABELS FOR
 PROPOSED 3 INCH AND LARGER WATER METERS. PLEASE ADD TO
 CIVIL PLANS. SHEET C300 SHOWS AT LEAST THREE SUCH
 METERS.
 -BACKFLOW LOCATIONS ARE NOT ACCEPTABLE. THE MOST
 CONCERNING IS THE LONG DISTANCE FROM THE METERS, POINTS
 OF SERVICE, AND PROPERTY LINES. NEED DISTANCE REDUCED
 SUBSTANTIALLY ON THEM.
 -IF FIRE HYDRANT NEAR NORTH PROPERTY LINE IS NOT
 EXISTING, ADD WORDING PROPOSED ON LABEL. IF PROPOSED IT
 DOES NOT SEEM TO MEET REQUIREMENTS OF NOTE 3 ON WPB
 STANDARD DETAIL P8.
 -320 LAKEVIEW AVE IS LISTED IN UTILITY BILLING SYSTEM
 AS HAVING EXISTING 6 INCH FIRELINE. SHOW AND LABEL ON
 CIVIL PLANS.
 -WILL 3 X 10 FPLE IN FAR NE CORNER OF PROPERTY REMAIN?
 -PLEASE ADD VISUAL GRAPHIC MEASUREMENT SCALES TO
 ENLARGEMENTS ON SHEET C300.
 -FOOTPRINTS OF THE 3 AND 4 INCH METERED WATER SERVICES
 ARE LIKELY MUCH LARGER THAN SHOWN ON SHEET C300.
 REFERENCE WPB SD WS3 FOR SOME UNDERSTANDING OF
 DIMENSIONS.
 -ANY PROPOSED CHANGES TO CITY WPB STREET LIGHTING OR
 IRRIGATION ELECTRIC PANELS REQUIRES SEPARATE APPROVAL.
 -APPLICANT SHOULD BE AWARE THAT THERE ARE OVERHEAD
 UTILITIES RUNNING FROM PROPERTY SOUTH ACROSS
 OKEECHOBEE.
 -ARE THE STREET LIGHTS AT NORTH AND SOUTH SIDES OF
 PROPERTY INTENDED TO REMAIN?
 -WILL THE BIKE RACKS AND STREET FURNITURE SHOWN ON LH1
 PREVENT OR IMPEDE USE OF THE PROPOSED SIDEWALKS? ON
 A1.01 THEY LOOK FINE SO PLEASE ALSO MAKE SURE PLAN
 LOCATIONS MATCH.
 -PROPOSED WATER SERVICE DESIGNS ARE NONSTANDARD AND MAY
 NEED ADJUSTMENT UPON FURTHER REVIEW AT ENGINEERING
 DEVELOPMENT SUBMITTAL. FURTHERMORE THE PROPOSED
 LOCATIONS OF THE WATER SERVICES MAY CONFLICT WITH OTHER
 PROJECT ELEMENTS. RECOMMEND FURTHER REFINEMENT OF WATER
 SERVICES DURING PPRC TO PREVENT FUTURE PROBLEMS. CAN
 CONTACT [email protected] FOR SOME ASSISTANCE OR
 GUIDANCE.
 -SHEETS C102 AND C103 SHOWS TRUCKS ENTERING NORTH
 ENTRANCE FROM THE EAST, BUT IT WOULD SEEM THAT MOST
 TRUCKS WOULD ORIGINATE FROM THE WEST NEAR I95 TRAVELING
 EAST. IS THE INTENT FOR TRUCKS TO GO AROUND THE BLOCK
 FIRST, AND IF SO, HOW WILL THEY KNOW TO DO THAT BEFORE
 TURNING INTO SOUTHERN ENTRANCE?
 -SHEET C104 REFUSE TRUCK SIDE LOOKS LIKE A SMALL CAR
 WAS USED FOR DIAGRAM INSTEAD OF A LARGER REFUSE TRUCK.
  