| 2022-07-14 11:08:00 | -STILL COULD NOT FIND VISUAL BOUNDARIES OF PAVEMENT |
| | RESTORATION ON THE ADJACENT ROADWAYS WHERE UTILITY |
| | EXCAVATION IS PROPOSED. PLEASE MAKE SURE COMPLIES WITH |
| | OVERSEEING AGENCY REQUIREMENTS AND SHOW ON CIVIL PLANS. |
| | -THERE ARE STILL MANY UNACCOUNTED FOR UTILITIES SUCH AS |
| | METERED WATER SERVICES AND SEWER LATERALS WHERE REMOVAL |
| | IS NOT SHOWN ON DEMO OR UTILITY PLANS. WILL LIKELY NEED |
| | TO GO INTO DIXIE HWY FOR SOME OF THAT REMOVAL. |
| | -COULD NOT FIND THE WORDING ABOVE GROUND ON LABELS FOR |
| | PROPOSED 3 INCH AND LARGER WATER METERS. PLEASE ADD TO |
| | CIVIL PLANS. SHEET C300 SHOWS AT LEAST THREE SUCH |
| | METERS. |
| | -BACKFLOW LOCATIONS ARE NOT ACCEPTABLE. THE MOST |
| | CONCERNING IS THE LONG DISTANCE FROM THE METERS, POINTS |
| | OF SERVICE, AND PROPERTY LINES. NEED DISTANCE REDUCED |
| | SUBSTANTIALLY ON THEM. |
| | -IF FIRE HYDRANT NEAR NORTH PROPERTY LINE IS NOT |
| | EXISTING, ADD WORDING PROPOSED ON LABEL. IF PROPOSED IT |
| | DOES NOT SEEM TO MEET REQUIREMENTS OF NOTE 3 ON WPB |
| | STANDARD DETAIL P8. |
| | -320 LAKEVIEW AVE IS LISTED IN UTILITY BILLING SYSTEM |
| | AS HAVING EXISTING 6 INCH FIRELINE. SHOW AND LABEL ON |
| | CIVIL PLANS. |
| | -WILL 3 X 10 FPLE IN FAR NE CORNER OF PROPERTY REMAIN? |
| | -PLEASE ADD VISUAL GRAPHIC MEASUREMENT SCALES TO |
| | ENLARGEMENTS ON SHEET C300. |
| | -FOOTPRINTS OF THE 3 AND 4 INCH METERED WATER SERVICES |
| | ARE LIKELY MUCH LARGER THAN SHOWN ON SHEET C300. |
| | REFERENCE WPB SD WS3 FOR SOME UNDERSTANDING OF |
| | DIMENSIONS. |
| | -ANY PROPOSED CHANGES TO CITY WPB STREET LIGHTING OR |
| | IRRIGATION ELECTRIC PANELS REQUIRES SEPARATE APPROVAL. |
| | -APPLICANT SHOULD BE AWARE THAT THERE ARE OVERHEAD |
| | UTILITIES RUNNING FROM PROPERTY SOUTH ACROSS |
| | OKEECHOBEE. |
| | -ARE THE STREET LIGHTS AT NORTH AND SOUTH SIDES OF |
| | PROPERTY INTENDED TO REMAIN? |
| | -WILL THE BIKE RACKS AND STREET FURNITURE SHOWN ON LH1 |
| | PREVENT OR IMPEDE USE OF THE PROPOSED SIDEWALKS? ON |
| | A1.01 THEY LOOK FINE SO PLEASE ALSO MAKE SURE PLAN |
| | LOCATIONS MATCH. |
| | -PROPOSED WATER SERVICE DESIGNS ARE NONSTANDARD AND MAY |
| | NEED ADJUSTMENT UPON FURTHER REVIEW AT ENGINEERING |
| | DEVELOPMENT SUBMITTAL. FURTHERMORE THE PROPOSED |
| | LOCATIONS OF THE WATER SERVICES MAY CONFLICT WITH OTHER |
| | PROJECT ELEMENTS. RECOMMEND FURTHER REFINEMENT OF WATER |
| | SERVICES DURING PPRC TO PREVENT FUTURE PROBLEMS. CAN |
| | CONTACT [email protected] FOR SOME ASSISTANCE OR |
| | GUIDANCE. |
| | -SHEETS C102 AND C103 SHOWS TRUCKS ENTERING NORTH |
| | ENTRANCE FROM THE EAST, BUT IT WOULD SEEM THAT MOST |
| | TRUCKS WOULD ORIGINATE FROM THE WEST NEAR I95 TRAVELING |
| | EAST. IS THE INTENT FOR TRUCKS TO GO AROUND THE BLOCK |
| | FIRST, AND IF SO, HOW WILL THEY KNOW TO DO THAT BEFORE |
| | TURNING INTO SOUTHERN ENTRANCE? |
| | -SHEET C104 REFUSE TRUCK SIDE LOOKS LIKE A SMALL CAR |
| | WAS USED FOR DIAGRAM INSTEAD OF A LARGER REFUSE TRUCK. |
| | |
| |