Plan Review Notes
Plan Review Notes For Project Z22050021
Project Number Z22050021
Review Stop PU
Sequence Number 2
Notes
Date Text
2022-07-14 17:00:13-CALL OUT POINT OF SERVICE AND SHOW THE UTILITY LINES
 WITHIN THE PROPERTY AS PRIVATE WHERE APPLICABLE.
 -ON DEMO SHEET ADD NOTE TO "CUT AND CAP AT THE MAIN"
 FOR ALL EXISTING WATER SERVICES AND SANITARY LATERALS
 TO BE ABANDONED.
 - PROVIDE CALCULATIONS ON PLANS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM
 AND PEAK) AND FIRE FLOW DEMANDS ON PLAN SHEET.
 CALCULATIONS SHALL BE PER FAC 64E-6 FOR SEWER AND PER
 FAC 64-E.008 FOR WATER.
 -SHOW STATIONING AND HORIZONTAL SEPARATION CLEARANCE
 BETWEEN PROPOSED UTILITIES AND EXISTING UTILITIES
 AND/OR BASELINE.
  