| Plan Review Notes For Project Z22050021 |
| Project Number |
Z22050021 |
|
| Review Stop |
PU |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-07-14 17:00:13 | -CALL OUT POINT OF SERVICE AND SHOW THE UTILITY LINES | | | WITHIN THE PROPERTY AS PRIVATE WHERE APPLICABLE. | | | -ON DEMO SHEET ADD NOTE TO "CUT AND CAP AT THE MAIN" | | | FOR ALL EXISTING WATER SERVICES AND SANITARY LATERALS | | | TO BE ABANDONED. | | | - PROVIDE CALCULATIONS ON PLANS OF EXISTING AND | | | PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM | | | AND PEAK) AND FIRE FLOW DEMANDS ON PLAN SHEET. | | | CALCULATIONS SHALL BE PER FAC 64E-6 FOR SEWER AND PER | | | FAC 64-E.008 FOR WATER. | | | -SHOW STATIONING AND HORIZONTAL SEPARATION CLEARANCE | | | BETWEEN PROPOSED UTILITIES AND EXISTING UTILITIES | | | AND/OR BASELINE. | | | |
| |