| 2022-06-08 13:56:11 | -VERTICAL BACKFLOW ASSEMBLIES ARE NONSTANDARD AND |
| | SUBJECT TO FURTHER REVIEW AT FORMAL ENGINEERING |
| | SUBMITTAL. |
| | |
| | -WHAT IS THE CLEARANCE DISTANCE BETWEEN PROPOSED |
| | EASTERN BUILDING WALLS AND EXISTING BUILDING WALLS OF |
| | 801 S. OLIVE? |
| | |
| | -WHAT IS HAPPENING TO THE EXISTING BELLSOUTH AND |
| | INGRESS EGRESS EASEMENTS? IF THEY ARE REMAINING, VERIFY |
| | APPLICANT HAS APPROVAL TO BUILD STRUCTURES IN THEM. |
| | |
| | -COULD NOT FIND GREASE TRAP FOR CAF? AND RESTAURANT ON |
| | ENGINEERING PLAN. WHERE WILL THEY BE LOCATED? |
| | |
| | -WATER UTILITY DESIGN IS NOT ACCEPTABLE. NEED DOMESTIC |
| | METER OUTSIDE BUILDING FOOTPRINT AND CLOSE TO PROPERTY |
| | LINE. CITY WATER MAIN SHOULD NOT TRAVERSE PROPERTY AND |
| | BE UNDER A BUILDING. |
| | |
| | -PAVEMENT RESTORATION OF OKEECHOBEE AND LAKEVIEW ARE |
| | NOT SHOWN. |
| | |
| | -SHOW EXISTING UTILITIES AND LABEL WHAT IS HAPPENING TO |
| | THEM. |
| | |
| | -VERIFY EXISTING SEWER MAIN SIZING IS SUFFICIENT. |
| | |
| | -WPB GIS SAYS SOME EXISTING SEWER MAINS IN AREA ARE |
| | OLDER. APPLICANT MAY BE REQUIRED TO IMPROVE THEM AS |
| | ADVISED BY CITY OR ENGINEER OF RECORD. |
| | |
| | -DOMESTIC WATER METER NEEDS TO BE INSTALLED ABOVE |
| | GROUND PER STANDARD DETAIL WS3 IF SIZED 3 INCH OR |
| | LARGER. SHOW AND LABEL IT ON ENGINEERING PLAN. |
| | |
| | -DOMESTIC RPZ NEEDS TO BE OUTSIDE BUILDING, AND CLOSE |
| | TO PROPERTY LINE AND DOMESTIC WATER METER. |
| | |
| | -ADD STANDARD DETAIL P8 TO ENGINEERING PLAN SET, AND |
| | VERIFY PROPOSED FIRE HYDRANT LOCATION MEETS |
| | REQUIREMENTS OF P8. |
| | |
| | -CANNOT READ NUMBER UNITS ON VISUAL SCALE MEASUREMENT |
| | ICON ON UTILITY PLAN. PLEASE MAKE READABLE. |
| | |
| | -ADD STANDARD DETAIL WS3 TO ENGINEERING PLAN SET. |
| | |
| | -SHOW AND LABEL ANY EXISTING OR PROPOSED EASEMENTS |
| | INCLUDING SIDEWALK EASEMENTS AND UTILITY EASEMENTS. |
| | |
| | -JUSTIFICATION STATEMENT STATED: HOWEVER, THE INTERIOR |
| | CEILING AND EXTERIOR PILASTERS CURRENTLY A PART OF THE |
| | BUILDING AT 320 LAKEVIEW WILL BE PRESERVED AND REUSED |
| | IN THE DESIGN OF THE GROUND FLOOR COMMERCIAL SPACE AS |
| | DISCUSSED WITH FRIEDERIKE MITTNER, CITY HISTORIC |
| | PRESERVATION PLANNER. PLEASE ADD THAT NOTE TO |
| | DEMOLITION PLAN AND SHOW WHERE THOSE ARE LOCATED. |
| | |
| | -ENSURE THAT THE CIVIL PLANS, LANDSCAPING PLANS, AND |
| | ARCHITECTURE PLANS MATCH WITH REGARDS TO GENERAL DESIGN |
| | LAYOUT. THE HARDSCAPE AND LANDSCAPE AREAS NEAR THE |
| | PROPERTY LINES SEEM DIFFERENT. |
| | |
| |