Plan Review Notes
Plan Review Notes For Project Z22050021
Project Number Z22050021
Review Stop PU-CS
Sequence Number 1
Notes
Date Text
2022-06-08 13:56:11-VERTICAL BACKFLOW ASSEMBLIES ARE NONSTANDARD AND
 SUBJECT TO FURTHER REVIEW AT FORMAL ENGINEERING
 SUBMITTAL.
  
 -WHAT IS THE CLEARANCE DISTANCE BETWEEN PROPOSED
 EASTERN BUILDING WALLS AND EXISTING BUILDING WALLS OF
 801 S. OLIVE?
  
 -WHAT IS HAPPENING TO THE EXISTING BELLSOUTH AND
 INGRESS EGRESS EASEMENTS? IF THEY ARE REMAINING, VERIFY
 APPLICANT HAS APPROVAL TO BUILD STRUCTURES IN THEM.
  
 -COULD NOT FIND GREASE TRAP FOR CAF? AND RESTAURANT ON
 ENGINEERING PLAN. WHERE WILL THEY BE LOCATED?
  
 -WATER UTILITY DESIGN IS NOT ACCEPTABLE. NEED DOMESTIC
 METER OUTSIDE BUILDING FOOTPRINT AND CLOSE TO PROPERTY
 LINE. CITY WATER MAIN SHOULD NOT TRAVERSE PROPERTY AND
 BE UNDER A BUILDING.
  
 -PAVEMENT RESTORATION OF OKEECHOBEE AND LAKEVIEW ARE
 NOT SHOWN.
  
 -SHOW EXISTING UTILITIES AND LABEL WHAT IS HAPPENING TO
 THEM.
  
 -VERIFY EXISTING SEWER MAIN SIZING IS SUFFICIENT.
  
 -WPB GIS SAYS SOME EXISTING SEWER MAINS IN AREA ARE
 OLDER. APPLICANT MAY BE REQUIRED TO IMPROVE THEM AS
 ADVISED BY CITY OR ENGINEER OF RECORD.
  
 -DOMESTIC WATER METER NEEDS TO BE INSTALLED ABOVE
 GROUND PER STANDARD DETAIL WS3 IF SIZED 3 INCH OR
 LARGER. SHOW AND LABEL IT ON ENGINEERING PLAN.
  
 -DOMESTIC RPZ NEEDS TO BE OUTSIDE BUILDING, AND CLOSE
 TO PROPERTY LINE AND DOMESTIC WATER METER.
  
 -ADD STANDARD DETAIL P8 TO ENGINEERING PLAN SET, AND
 VERIFY PROPOSED FIRE HYDRANT LOCATION MEETS
 REQUIREMENTS OF P8.
  
 -CANNOT READ NUMBER UNITS ON VISUAL SCALE MEASUREMENT
 ICON ON UTILITY PLAN. PLEASE MAKE READABLE.
  
 -ADD STANDARD DETAIL WS3 TO ENGINEERING PLAN SET.
  
 -SHOW AND LABEL ANY EXISTING OR PROPOSED EASEMENTS
 INCLUDING SIDEWALK EASEMENTS AND UTILITY EASEMENTS.
  
 -JUSTIFICATION STATEMENT STATED: HOWEVER, THE INTERIOR
 CEILING AND EXTERIOR PILASTERS CURRENTLY A PART OF THE
 BUILDING AT 320 LAKEVIEW WILL BE PRESERVED AND REUSED
 IN THE DESIGN OF THE GROUND FLOOR COMMERCIAL SPACE AS
 DISCUSSED WITH FRIEDERIKE MITTNER, CITY HISTORIC
 PRESERVATION PLANNER. PLEASE ADD THAT NOTE TO
 DEMOLITION PLAN AND SHOW WHERE THOSE ARE LOCATED.
  
 -ENSURE THAT THE CIVIL PLANS, LANDSCAPING PLANS, AND
 ARCHITECTURE PLANS MATCH WITH REGARDS TO GENERAL DESIGN
 LAYOUT. THE HARDSCAPE AND LANDSCAPE AREAS NEAR THE
 PROPERTY LINES SEEM DIFFERENT.
  