2022-05-09 11:43:04Z22040056 - 550 QUADRILLE - MINOR AMEND? 1ST REVIEW
  
 COMMENTS FROM RICK ROSSANO, SR. PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPARTMENT AT 561-494-1098
 [email protected]
 O INDICATE HOW EXISTING AND PROPOSED INFRASTRUCTURE FOR
 THE ONE WEST PALM PROJECT MAY BE IMPACTED BY THE
 PROPOSED DROPOFF AND REVISIONS.
 O CLOUD PROPOSED REVISIONS AND DATE REVISED CIVIL
 SHEETS.
  
  
 COMMENTS FROM MARK HURLEY, CUST. SVC. SUPERVISOR,
 PUBLIC UTILITIES, [email protected], 561-822-2262:
  
 -ANY CHANGES MAY AFFECT E19010014.
  
 -ADD ABOVE GROUND WORDING TO 8 INCH METER LABELS.
  
 -RELOCATE TAP FOR EASTERN 8 INCH METER TO THE WEST NEAR
 THE METER, SO THAT EXTRANEOUS PIPE IS ELIMINATED.
  
 -ARE ANY GREASE TRAPS NEEDED AT 4TH ST.?
  
 -CLEARLY SHOW AND LABEL PROPERTY LINES ON CIVIL PLANS.
  
 -THERE IS A CLEANOUT IN FRONT OF A DOOR ON 4TH ST.
 MAINTENANCE MAY IMPEDE USE OF DOOR.
  
 -DROP MANHOLE MAY BE NEEDED AT MH2 ON 4TH ST.
  
 -PROPOSED SEWER POINT OF SERVICES NEED BE REVIEWED AT
 FORMAL ENGINEERING SUBMITTAL.
  
 -ON 4TH ST, LARGE DIAMETER WATER MAIN CROSSES IN CLOSE
 PROXIMITY OVER SANITARY PIPING. IS THAT VERTICAL LOAD
 ALRIGHT?
  
 -L1-121 DOES NOT MATCH LOCATIONS OF UTILITIES ON
 SUBMITTED CIVIL PLANS. PLEASE UPDATE L1-121 AND ENSURE
 NO CONFLICTS BETWEEN TREES AND WATER/SEWER UTILITIES.
  
 -VERIFY THAT WPB PARKS AND RECREATION DEPARTMENT AGREES
 WITH THE PLAN PROPOSAL FOR THEIR METERED WATER SERVICES
 NEAR THE SOUTHEAST AND NORTHWEST AREAS OF PROPERTY.
  
 -WATER METER ORDERING AND RECEIVING COULD TAKE UPWARDS
 OF FIVE MONTHS AFTER UTILITY QUOTES ARE PAID AND
 UTILITY BILLING ACCOUNTS ARE SETUP DUE TO THE SIZING.
  