| 2022-07-27 17:29:27 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | THE INCLUSION OF THE DOCUMENT "RESPONSE TO COMMENTS" IS |
| | NOTED BUT IT DOES NOT APPEAR TO INCLUDE A NARRATIVE OF |
| | THE RESPONSE TO THE BUILDING COMMENTS. |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. |
| | |
| | 2. ACCESSIBLE ROUTE. SITE PLAN, SHEET C-100, SITE PLAN, |
| | STILL DOES NOT SHOW A WHEECHAIR ACCESSIBLE ROUTE FROM |
| | THE SIDEWALK TO BUILDING #1 (SHOWROOM). WHEN SUBMITTED |
| | FOR PERMIT, THE PLANS SHALL SHOW AT LEAST ONE |
| | ACCESSIBLE ROUTE, COMPLYING WITH SECTIONS 206.2 AND |
| | 402.2 OF FLORIDA ACCESSIBILITY CODE, FROM THE PUBLIC |
| | RIGHT-OF-WAY TO ALL ACCESSIBLE BUILDING OR FACILITY |
| | ENTRANCES. |
| | |
| | 3. ACCESSIBLE ROUTE BETWEEN BUILDINGS. SHEET C-100, |
| | SITE PLAN, STILL DOES NOT SHOW A WHEECHAIR ACCESSIBLE |
| | ROUTE FROM THE BUILDING #4 (GENESIS BUILDING) TO |
| | BUILDING #1 (SHOWROOM). WHEN SUBMITTED FOR PERMIT THE |
| | PLANS MUST SHOW AT LEAST ONE ACCESSIBLE ROUTE, |
| | COMPLYING WITH SECTIONS 206.2 AND 402.2 OF FLORIDA |
| | ACCESSIBILITY CODE, CONNECTING ACCESSIBLE BUILDING OR |
| | FACILITY ENTRANCES WITH ALL ACCESSIBLE SPACES AND |
| | ELEMENTS WITHIN THE BUILDING OR FACILITY |
| | |
| | 4. LOCATION OF ACCESSIBLE PARKING SPACES. SITE PLAN, |
| | SHEET C-100, NOW SHOWS THE ACCESSIBLE PARKING SPACES |
| | CLOSER TO THE BUILDING ENTRANCES BUT THE LOCATION OF |
| | THE EAST ACCESSIBLE PARKING SPACE OUTSIDE BUILDING #1 |
| | WOULD REQUIRE THE USER TO PASS BEHIND SOMEONE ELSE'S |
| | PARKED VEHICLE TO GET TO THE BUILDING ENTRANCE. PER |
| | SECTION 208.3 OF FLORIDA ACCESSIBILITY CODE, ACCESSIBLE |
| | PARKING SPACES ARE TO BE LOCATED ON THE SHORTEST |
| | POSSIBLE SAFE ROUTE OF TRAVEL FROM ADJACENT PARKING TO |
| | AN ACCESSIBLE ENTRANCE. THE DESIGN OF ACCESSIBLE |
| | PARKING SPACES SHALL COMPLY WITH SECTION 502 OF FLORIDA |
| | ACCESSIBILITY CODE. |
| | |
| | 5. ELECTRIC VEHICLE CHARGING STATION. INFORMATIONAL |
| | COMMENT. IF ELECTRIC VEHICLE (EV) CHARGING STATIONS ARE |
| | PROVIDED AT LEAST 1 IN 25 MUST COMPLY WITH ACCESSIBLE |
| | PARKING SPACE REQUIREMENTS. |
| | |
| | 6. BUILDING SIZE. INFORMATIONAL COMMENT. WHEN SUBMITTED |
| | FOR BUILDING PERMIT, THE PLANS SHALL SHOW THAT THE TYPE |
| | OF CONSTRUCTION FOR THE BUILDINGS WILL BE IN ACCORDANCE |
| | WITH THE HEIGHT, AREA AND OCCUPANCY LIMITATIONS IN |
| | CHAPTER 5 OF THE FLORIDA BUILDING CODE. |
| | |
| | 7. THE ADDITION TO THE EXISTING BUILDING IS COVERED BY |
| | CHAPTER 11 OF THE FLORIDA EXISTING BUILDING CODE. |
| | INFORMATIONAL COMMENT. THE HEIGHT AND/OR AREA INCREASE |
| | DUE TO THE PROPOSED ADDITION SHALL NOT INCREASE THE |
| | TOTAL BUILDING HEIGHT AND/OR AREA BEYOND THAT ALLOWED |
| | UNDER THE APPLICABLE PROVISIONS OF CHAPTER 5 OF THE |
| | FLORIDA BUILDING CODE FOR THE TYPE OF CONSTRUCTION |
| | USED. |
| | |
| | 8. GREASE/PETROLEUM INTERCEPTOR. INFORMATIONAL COMMENT. |
| | A GREASE/PETROLEUM INTERCEPTOR WILL BE REQUIRED. FOR |
| | INFORMATION ON THE REQUIRED TYPE, SIZE AND LOCATION, |
| | PLEASE CONTACT RYAN BROWN, CHIEF PLUMBING INSPECTOR, |
| | DEVELOPMENT SERVICES DEPARTMENT, AT (561) 805-6692, OR |
| | BY EMAIL: [email protected] |
| | |
| | 9. SEPARATE PERMITS REQUIRED. INFORMATIONAL COMMENT. |
| | ALL APPLICABLE PERMITS AND SUB-PERMITS MUST BE OBTAINED |
| | BEFORE COMMENCING THE WORK. SEPARATE PERMITS, PLANS AND |
| | FEES, ARE REQUIRED FOR SIGNS, GAS SYSTEMS, GENERATORS, |
| | FIRE ALARM SYSTEMS, FIRE SPRINKLER AND OTHER FIRE |
| | SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, SITE |
| | LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | 10. BUILDING ADDRESS. INFORMATIONAL COMMENT. EACH |
| | SEPARATE BUILDING, AND UNIT WITH AN INDEPENDENT |
| | ENTRANCE FROM THE STREET, SHALL HAVE A SEPARATE ADDRESS |
| | ASSIGNED BASED ON THE LOCATION OF THE BUILDING |
| | ENTRANCE. FOR STREET ADDRESSING, CONTACT CAROLINE |
| | PUELL, ADDRESSING COORDINATOR, AT (561) 805 6659, OR BY |
| | EMAIL: [email protected] |
| | |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |