Plan Review Notes
Plan Review Notes For Project Z22040026
Project Number Z22040026
Review Stop PU-CS
Sequence Number 1
Notes
Date Text
2022-07-18 09:37:56PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
  
 -RESPONSE LETTER HAD NO RESPONSE TO NUMBER 33 AND
 NUMBER 34. PLEASE INCLUDE IN NEXT REPONSE LETTER.
  
 -PLEASE ADD VISUAL MEASUREMENT SCALE TO ENLARGEMENTS ON
 SHEET C300.
  
 -MAY NOT BE ABLE TO TEE PROPOSED 1 INCH METER DEPENDING
 ON CHARACTERISTICS OF EXISTING METERED WATER SERVICE.
 WILL DETERMINE IF NEW TAP IS NEEDED AT ENGINEERING
 DEVELOPMENT SUBMITTAL.
  
 -PGD PLAN SHOWS LIGHT POLE AND BOLLARDS ENCROACHING IN
 PROPOSED SIDEWALK NEAR SOUTHWEST AREA OF PROPERTY.
  
 -FIRELINE AND HYDRANT DESIGN NEEDS TO BE REFINED. IF
 FIRE HYDRANT IS INTENDED TO BE PRIVATE, THEN IT NEEDS
 TO BE DOWNSTREAM OF DCDA. IF PROPOSED TO BE CITY
 HYDRANT, THEN NEEDS TO BE ADJACENT PROPERTY LINE WITH
 PIPE DISTANCE REDUCED IN A UTILITY EASEMENT. ALSO MAKE
 SURE FIRE HYDRANT WILL NOT CONFLICT WITH ANY TREES IN
 LANDSCAPING ISLAND. ALTERNATELY COULD TRY TO EXTEND FDC
 CLOSER TO EXISTING HYDRANT.
  
 -PIPING BETWEEN TAP AND DCDA NEEDS TO BE DIP.
  
 -SMALL WATER SERVICES SHOULD BE K COPPER OR POLY.
  
 -PROPOSED 1 INCH METER WOULD REQUIRE RP BACKFLOW
 ASSEMBLY. IT WOULD ALSO REQUIRE UTILITY EASEMENT.
 PLEASE SHOW AND LABEL THEM ON UTILITY PLAN.