Notes
Date Text
2022-04-21 16:42:471. SURVEY
 A. DATED 2018.
 B. UPDATE THE FLOOD ZONE INFOMRATION. REVISED FIRMS
 WERE ISSUED IN 2017.
 C. REVIEW LOT DIMENSIONS (100 FT X 140 FT) AND LOT AREA
 (0.32 ACRES, 14000 S.F.) .
  
 2. NO DRAINAGE PLAN OR GRADING PLAN PROVIDED. DRAINAGE
 SYSTEM TO BE DESIGNED TO MEET SFWMD ERP CRITERIA.
  
 3. NO ENGINEEERING PLANS PROVIDED.
  
 4. THE CITY'S OFFICIAL VERTICAL DATUM IS NGVD1929. THE
 CITY HAS ALLOWED THE USE OF NAVD1988 PROVIDED A
 CONVERSION EQUATION BETWEEN NAVD1988 AND NGVD1929 IS
 SHOWN ON THE PLANS. THE VERTICAL DATUM AND CONVERSION
 EQUATION SHALL BE PROVIDED ON EVERY SHEET WITH
 ELEVATION INFORMATION.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120