Plan Review Notes
Plan Review Notes For Project Z22040021
Project Number Z22040021
Review Stop PU
Sequence Number 1
Notes
Date Text
2022-05-11 15:11:33-SHOW EXISTING 6? CAS WM ON CARVER AVE.
 -PROVIDE LEVEL OF SERVICE CALCS AND FIRE FLOW CALCS.
 -IF AN EXISTING SANITARY LATERAL IS FOUND ON SITE ADD
 NOTE TO EITHER 1) CUT AND CAP UNUSED SERVICE AT THE
 MAIN. 2) TELEVISE EXISTING MAIN AND REPAIR AS NECESSARY
 PRIOR TO USE.
  