Plan Review Notes
Plan Review Notes For Project Z22040017
Project Number Z22040017
Review Stop PU-CS
Sequence Number 1
Notes
Date Text
2023-05-19 13:22:42PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -RESPONSE LETTER WAS NOT PROVIDED FOR THE FOLLOWING
 REVIEW COMMENTS FROM INITIAL SUBMITTAL. PLEASE RESPOND
 TO THOSE NOW:
 *WHAT DAYS AND TIMES ARE THE ACCESS GATES CLOSED?
 *IS THERE A CURRENT AGREEMENT TO USE NEIGHBOR???S SEWER
 INFRASTRUCTURE? IF SO, PLEASE PROVIDE COPY.
 *IS THERE A CURRENT ACCESS AGREEMENT OR EASEMENT TO
 TRAVERSE NEIGHBOR???S PROPERTY TO THE NORTH? IF SO,
 PLEASE PROVIDE DOCUMENTATION AND UPDATE SURVEY AND
 ENGINEERING PLAN.
 *ARE EXISTING WATER AND SEWER INFRACTURE SUFFICIENT FOR
 ANY INCREASED DEMAND?
 *SHOW AND LABEL EXISTING DOMESTIC WATER SERVICE, SEWER
 MAIN, CLEANOUT, WATER MAIN, METER BOX, AND BACKFLOW
 ASSEMBLY ON ENGINEERING PLAN.
 *LP1 CALLS OUT THREE (5) NEW CHRISTMAS PALM TREE.
 *EXISTING DCDA IS 4 INCH SIZE. IF PROPOSED BUILDING
 WILL HAVE FIRE SPRINKLERS, IS DCDA SIZE SUFFICIENT?
 *DOMESTIC BACKFLOW ASSEMBLY IS SHOWING AS OVERDUE FOR
 ANNUAL TESTING. IF IT WILL REMAIN THROUGH THE PROJECT,
 THEN NEEDS TO BE TESTED BY LICENSED PLUMBER.
 RESPECTFULLY,
 MARK HURLEY [email protected]