2023-01-13 14:40:44-SEVERAL REVIEW COMMENTS FROM PRIOR SUBMITTALS HAVE YET
 TO BE ADDRESSED.
 -THE SITE PLAN CAN BE APPROVED ON PUBLIC UTILITIES
 ENGINEERING'S END WITH THE CONDITION OF OUTSTANDING
 COMMENTS BEING ADRESSED AS PART OF THE ENGINEERING
 REVIEW, WHICH INCLUDES BUT IS NOT LIMITED TO THE
 FOLLOWING:
 -ELABORATE ON THE SANITARY IMPROVEMENTS (ADDITION OF
 GRAVITY MAIN, AND SECTIONAL REPLACEMENT OF FORCE MAIN)
 -NORTHERN WATER MAIN CONNECTION MUST BE TO 12 IN MAIN,
 NOT JUNCTION BETWEEN 12" AND 36"
 -PER DETAILS WS-1 AND WS-4, SEPARATE CONNECTIONS MUST
 BE MADE FOR FIRE LINE AND POTABLE WATER
 -PROFILE NEEDED FOR ALL UTILITIES FROM TAP TO POINT OF
 SERVICE (WATER, GRAVITY, AND FORCE MAIN)
 -PROXIMITY BETWEEN PIPES IS TOO CLOSE (PROPOSED STORM,
 FORCE MAIN, AND EXISTING DRY UTILITIES)
 -APPROPRIATELY LABEL ALL EXISTING VALVES AND EXISTING
 UTILITY ASSESTS ON PLANS
 -LABEL ALL PROPOSED FITTINGS FOR BOTH WATER AND FORCE
 MAIN
 -DENOTE THAT THE PROJECT IS WITHIN THE BOUNDARIES OF
 LIFT STATION 41
 -SIZE AND MATERIAL NEEDS TO BE NOTED FOR ALL PROPOSED
 UTILITIES (SEWER)
 -PER PRIOR CONVERSATION, THE PRIVATE LIFT STATION CAN
 NOT BE TIED INTO THE EXISTING FORCE MAIN ON CLEARWATER
 DR.
 -FIRE FLOW TEST DATA FOR EXISTING SYSTEM NEEDED
 -A LEGEND NEEDS TO BE PROVIDED
 -CLEANOUTS NEAR THE PROPERTY LINE NEED TO BE DENOTED AS
 THE CITY'S POINT OF SERVICE
 -SEPARATE TAPS FOR WATER AND FIRE REQUIRED PER WS-1 AND
 WS-4
 -EXISTING SERVICES (WATER AND SEWER) THAT RUN TO THE
 PROPERTY BUT ARE NOT TO BE USED MUST BE CUT AND CAPPED
 AT THE MAIN
 -SERVICES LARGER THAN 2" IN DIAMETER MUST BE REMOVED
 -CLARIFY THE HYDRANT RELOCATIONS (NORTHERN RELOCATION
 NOT FULLY SHOWN ON PLANS, SOUTHERN RELOCATION IS NEAR
 350 PROJECT
 -EXISTING FORCE MAIN ON CLEARWATER DRIVE MUST BE
 REPLACED ENTIRELY (NOT IN SECTIONS)
 -SHOW STATIONING AND HORIZONTAL SEPARATION CLEARANCE
 BETWEEN PROPOSED UTILITIES AND EXISTING UTILITIES
 -SHOW SLOPE PERCENTAGE AND FLOW DIRECTION FOR ALL
 SANITARY LINES, AND CALL OUT MATERIAL FOR BOTH EXISTING
 AND PROPOSED
 -SANITARY SEWER SERVICE LINES 8" OR GREATER MUST BE
 TIED INTO SEWER SYSTEM VIA MANHOLE
  