2022-12-12 09:07:57PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -SHEET L400B SHOWS TREES TOO CLOSE TO FIRE HYDRANT,
 WATER SERVICE LINE, AND BACKFLOW ASSEMBLY.
 -SHEETS C03 AND L400B SHOW PROPOSED BACKFLOW ASSEMBLY
 IN THE RIGHT OF WAY. SHOULD BE LOCATED ON PRIVATE
 PROPERTY.
 -SHEET L400A DOES NOT SHOW UPSTREAM WATER SERVICE LINE
 FOR WATER METER NEAR PARK AS SHOWN ON C03. LOOKS LIKE
 IT WOULD BE TOO CLOSE TO POLE AND TREE. PLEASE SHOW
 WATER SERVICE LINE ON L400A AND ENSURE ANY PROPOSED
 TREES OR POLES ARE DISTANCED FROM EXISTING WATER
 SERVICE.
 -SHOW ALL WATER AND SEWER UTILITIES ON LANDSCAPING
 PLANS INCLUDING THE LARGE DIAMETER WATER MAIN AND 15
 FOOT WATERLINE EASEMENT THAT RUNS ACROSS THE NORTHWEST
 AREA OF PROPERTY. CANNOT CURRENTLY SEE IT ON L400C.
 -WATER SERVICE DESIGN MAY NEED REVISION UPON FURTHER
 REVIEW AT ENGINEERING DEVELOPMENT SUBMITTAL.
 RESPECTFULLY,
 MARK HURLEY [email protected]