2 |
|
| Notes |
| Date |
Text |
| 2022-07-21 11:04:24 | PREVIOUS ANSWERS TO THESE COMMENTS MADE NO SENSE. | | | | | | UNITY OF CONTROL/TITLE WILL BE REQUIRED | | | LANDSCAPE TREES WITHIN THE CITY?S UTILITY EASEMENT WILL | | | NOT BE ALLOWED. | | | NEED TO SEE WHERE RELOCATED FPL POLES ARE IN RELATION | | | TO EXISTING 36" WATER MAIN. | | | 36" WATER MAIN NEEDS TO BE CLEARLY LABELED FOR | | | POTENTIAL CONFLICTS. | | | PROPOSED FPL POLES ALONG WEST R/W OF CLEARWATER MAY | | | CONFLICT WITH EXISTING SANITARY SEWER. CCTV WILL BE | | | REQUIRED FOR ENTIRE LENGTH. | | | WHAT TYPE OF OWNERSHIP IS PROPOSED FOR THE IMPROVEMENTS | | | ABOVE 21' 4" | | | | | | ADDITIONAL COMMENTS 7.21.2022 | | | | | | 1. NEED PROFILE OF 36" WM AND ALL UTILITIES IN NW | | | CORNER OF PROJECT. | | | 2. FPL POLE 1D16 SHOWN ON TOP OF WATER MAIN. REFER TO | | | PREVIOUS COMMENT ABOVE. | | | 3. IS A VERTICAL SUBDIVISION PROPOSED? IF SO, NEED | | | APPROVAL FROM BUILDING DEPT. | | | 4. RELOCATE SEWER VALVE FROM UNDER CURB IN VICINITY OF | | | EXISTING FIRE EMERGENCY ACCESS. |
| |