2022-07-21 11:04:24PREVIOUS ANSWERS TO THESE COMMENTS MADE NO SENSE.
  
 UNITY OF CONTROL/TITLE WILL BE REQUIRED
 LANDSCAPE TREES WITHIN THE CITY?S UTILITY EASEMENT WILL
 NOT BE ALLOWED.
 NEED TO SEE WHERE RELOCATED FPL POLES ARE IN RELATION
 TO EXISTING 36" WATER MAIN.
 36" WATER MAIN NEEDS TO BE CLEARLY LABELED FOR
 POTENTIAL CONFLICTS.
 PROPOSED FPL POLES ALONG WEST R/W OF CLEARWATER MAY
 CONFLICT WITH EXISTING SANITARY SEWER. CCTV WILL BE
 REQUIRED FOR ENTIRE LENGTH.
 WHAT TYPE OF OWNERSHIP IS PROPOSED FOR THE IMPROVEMENTS
 ABOVE 21' 4"
  
 ADDITIONAL COMMENTS 7.21.2022
  
 1. NEED PROFILE OF 36" WM AND ALL UTILITIES IN NW
 CORNER OF PROJECT.
 2. FPL POLE 1D16 SHOWN ON TOP OF WATER MAIN. REFER TO
 PREVIOUS COMMENT ABOVE.
 3. IS A VERTICAL SUBDIVISION PROPOSED? IF SO, NEED
 APPROVAL FROM BUILDING DEPT.
 4. RELOCATE SEWER VALVE FROM UNDER CURB IN VICINITY OF
 EXISTING FIRE EMERGENCY ACCESS.