| 2022-07-01 16:26:07 | Z22040014 - TRANSIT VILLAGE - 150 CLEARWATER ? 6.15.22 |
| | RESUB |
| | |
| | COMMENTS FROM RICK ROSSANO, SR. PROJECT COORDINATOR, |
| | ENGINEERING SERVICES DEPARTMENT AT 561-494-1098 |
| | [email protected] |
| | O PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND |
| | STORMWATER INFRASTRUCTURE ALONG ENTIRE PROJECT |
| | FRONTAGE. |
| | (REPEATED COMMENT ? THIS IS A REQUIREMENT FOR SITE PLAN |
| | APPROVAL.) |
| | COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE |
| | SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, |
| | 561-822-2262 OR [email protected] |
| | -IR510 SPECIFIES FEBCO 825Y RPZ. IF THAT IS A |
| | CONTAINMENT BACKFLOW ASSEMBLY, THEN IT MUST BE LEAD |
| | FREE. LF825Y IS THE LEAD FREE VERSION. PLEASE UPDATE |
| | IR510 AS NEEDED. |
| | |
| | -EXISTING 12 INCH WATER MAIN ON SHEET C08 TRYING TO USE |
| | FOR NEW WATER SERVICES SEEMS TO BE CONNECTED TO 36 INCH |
| | WATER MAIN. IF SO, CONNECTION WOULD NEED BE MAINTAINED |
| | AND WATER SERVICE DESIGN ALTERED. EOR NEED INVESTIGATE |
| | FURTHER AT FORMAL ENGINEERING SUBMITTAL. |
| | |
| | -PROVIDE LANDSCAPING PLAN THAT SHOWS UPDATED UTILITY |
| | AND TREE LOCATIONS ON ONE SHEET, SO CAN VERIFY NO |
| | CONFLICTS BETWEEN THEM. |
| | |
| | -ADDITIONAL UTILITY EASEMENTS ARE NEEDED FOR PROPOSED |
| | WATER SERVICES ON SHEETS C08 AND C09. |
| | |
| | -SEWER LATERAL ON SHEET C09 LABELED AS 8 INCH, BUT SAYS |
| | 6 INCH CONNECTION AT MAIN. PLEASE VERIFY SIZING. |
| | |
| | -SHEET C09 ENLARGED VIEW SAYS THERE IS AN 8 BY 6 TEE ON |
| | THE 8 INCH FIRELINE. PLEASE VERIFY AND CORRECT AS |
| | NEEDED. |
| | |
| | -VERIFY WELLS WILL NOT BE CONNECTED TO PRIVATE FIRE |
| | SYSTEM. |
| | |
| | -EXISTING WATER METER BOX NEAR SOUTHWEST AREA OF |
| | PROPERTY IS CURRENTLY LOCATED IN GRASS. SEE IF CAN |
| | RELOCATE IT TO PARKWAY OUT OF PEDESTRIAN TRAFFIC |
| | HARDSCAPE AND SUFFICIENTLY DISTANCED FROM TREES. |
| | |
| |