Plan Review Notes For Project Z22040014
Project Number Z22040014
Review Stop PU
Sequence Number 1
Notes
Date Text
2022-05-11 15:25:20-NO ISSUES WITH THE CONCEPTUAL UTILITY PLAN. SOME
 STANDARD COMMENTS HAVE BEEN ATTACHED BELOW:
 -REVISE BANYAN ST TO BANYAN BLVD.
 -SHOW ALL EXISTING UNDERGROUND UTILITIES WITHING CITY
 ROW ( BANYAN AND CLEARWATER). CALL OUT SIZE/TYPE.
 -CALL OUT THE EXISTING FM ON CLEARWATER DR AS 6? DIP.
 -CALL OUT THE LOCATION OF THE CAP AND LOCATION OF THE
 PROPOSED TAP ON THE 6? DIP FM. MAINTAIN A MIN. OF 10?
 DISTANCE BETWEEN THE TWO.
 -ADD NOTE FOR ALL EXISTING LATERALS: ?REHAB/REPLACE AS
 REQUIRED?
 -PROFILE OF SERVICE TAPS WILL BE NEEDED FOR ENGINEERING
 SUBMITTAL AS WELL AS LEVEL OF SERVICE CALCS. SEE LIST
 OF STANDARD COMMENTS.
  