Plan Review Notes
Plan Review Notes For Project Z22030046
Project Number Z22030046
Review Stop STORM
Sequence Number 2
Notes
Date Text
2022-07-05 11:21:48THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 6-27-2022 SUBMITTAL. NOTE: WRITTEN RESPONSES TO THE
 LAST SET OF STORM COMMENTS WERE NOT RECEIVED WITH THIS
 SUBMTITAL.
  
  
 1. [NOT SATISFIED] THE CITY'S OFFICIAL VERTICAL DATUM
 IS NGVD1929. THE CITY HAS ALLOWED THE USE OF NAVD1988
 AS LONG AS THE CONVERSION EQUATION TO NGVD1929 AT THE
 PROJECT LOCATION IS PROVIDED. PROVIDE VERTICAL DATUM
 REFERENCE AND CONVERSION TO NGVD1929 ON EVERY SHEET
 WITH ELEVATION INFORMATION.
  
 2. [NOT SATISFIED - DIMENSIONS IN INCHES INSTEAD OF
 FEET] REVISE DIMENSION SYMBOL USED ON THE CROSS SECTION
 VIEW OF THE FRENCH DRAINAGE DETAIL.
  
 3. [SATISFIED] SHOW UTILITIES ON THE LANDSCAPE PLAN.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  