Plan Review Notes
Plan Review Notes For Project Z22030030
Project Number Z22030030
Review Stop STORM
Sequence Number 2
Notes
Date Text
2022-07-08 15:22:07THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 6/8/2022 SUBMITTAL:
  
 1. [PARTIALLY SATISFIED - AN EXTRA PIPE WAS ADDED TO
 THE CATCH BASIN ON THE NORTH SIDE OF 27TH STREET.
 ADVISE WHERE THIS INFORMATION CAME FROM.] REVISE THE
 LAYOUT OF THE EXISTING STORM PIPE CROSSING 27TH STREET
 BY MOVING THE NORTH END OF THE PIPE FROM THE CATCH
 BASIN (WITH RIM ELEVATION 12.28 FT NAVD) TO A MANHOLE
 THAT IS LOCATED IN THE SWALE OF ELECTRONICS WAY EAST OF
 THE CATCH BASIN. THEN ADD AN EXISTING 36 INCH RCP PIPE
 BETWEEN THE MANHOLE AND THE CATCH BASIN TO THE WEST.
  
 2. [SATISFIED] REVIEW THE PROPOSED GRADING OF THE
 INTERIOR SWALE ALONG THE NORTH PERIMETER. NEARLY 12.5
 FEET IS NEEDED BETWEEN THE CORNER OF THE SIDEWALK (AT
 NORTHWEST CORNER OF THE BUILDING) AND THE NORTH
 PROPERTY LINE BUT THERE IS ONLY ABOUT 10.5 FEET.
 APPROXIMATELY 12.5 FEET IS NEEDED BETWEEN THE BIKE RACK
 AND NORTH PROPERTY LINE BUT ONLY 10 FEET IS AVAILABLE
 (SECTION B-B).
  
 3. [SATISFIED] SECTION D-D - INDICATE HOW THE GROUND
 WILL SLOPE BETWEEN THE FENCE AND BACK OF CURB. PROVIDE
 A SWALE BETWEEN THE FENCE AND THE SOUTH PROPERTY LINE
 TO PREVENT DIRECT RUNOFF ONTO THE ADJACENT PROPERTY.
  
 4. [SATISFIED] CONSIDER REDUCING THE PARKING SPACES
 ALONG THE WEST PROPERTY LINE AND PROVIDE 2 FEET OF
 OVERHANG. TYPE D CURB COULD REPLACE THE WHEEL STOPS.
  
 5. [SATISFIED] MOVE THE HIGH POINT OF THE DRIVEWAY
 CLOSER TO THE EAST PROPERTY LINE SO THAT A PORTION OR
 ALL OF THE LOADING PARKING SPACE WILL DRAIN TO THE
 INTERIOR OF THE SITE INSTEAD OF THE RIGHT OF WAY.
  
 6. [SATISFIED] LIST THE TOP OF TRENCH ELEVATION AND
 BOTTOM OF TRENCH ELEVATION ON THE EXFILTRATION TRENCH
 DETAIL CROSS SECTION.
  
 7. [SATISFIED] THE CITY DOES NOT ALLOW THE USE OF
 BLEEDERS WITH EXFILTRATION TRENCH SYSTEMS.
  
 8. [SATISFIED] ON SHEETS 4 AND 5, WHAT DOES THE HEAVY
 SINGLE SHORT DASH - LONG DASH LINE REPRESENT THAT IS
 SHOWN IN THE INTERIOR OF THE WEST PARCEL?
  
 9. [SATISFIED] SITE IS LOCATED WITHIN A SPECIAL FLOOD
 HAZARD AREA. MINIMUM TWO FEET OF FREEBOARD ARE REQUIRED
 ABOVE THE BASE FLOOD ELEVATION.
  
 NEW COMMENTS:
  
 10. CIVIL PLANS DO NOT MATCH THE ARCHITECTURAL PLANS OR
 LANDSCAPE PLANS. THE CIVIL PLANS REMOVED THE SIDEWALK
 ON THE NORTH SIDE OF THE BUILDING. THIS MAY AFFECT THE
 LIFE SAFETY PLAN AND LANDSCAPE PLAN.
  
 11. ADD VERTICAL DATUM REFERENCE AND CONVERSION
 EQUATION TO ENGINEERING SHEET 7.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  
  