Plan Review Notes
Plan Review Notes For Project Z22030025
Project Number Z22030025
Review Stop STORM
Sequence Number 4
Notes
Date Text
2022-10-25 17:20:26THE FOLLOWIONG COMMENTS ARE FROM THE REVIEW OF THE
 10/7/2022 SUBMITTAL:
  
 CONDITIONS FOR SITE PLAN APPROVAL:
  
 1. REVISE ENGINEERING PLANS FOR ENGINEERING PERMIT
 SUBMITTAL TO INCLUDE:CROSS SECTIONS SHOWING GRADE
 BREAKS, SURFACE SLOPES, SURFACE FEATURES, RIGHT OF WAY
 LABELS, DISTANCES FROM PROPERTY LINE TO GRADE BREAKS:
 A. DRIVEAY CONNECTIONS AT THE PROPERTY LINE. FOR THE
 DRIVEAY AT THE CUL-DE-SAC, EXTEND THE SECTION TO THE
 FACE OF THE BUILDING AND TO 5 FEET IN THE CUL-DE-SAC.
 B. FACE OF BUILDING TO THE CHAIN LINK FENCE ON THE
 OUTSIDE OF THE NORTHEAST PROPERTY LINE
 C. EDGE OF PAVEMENT OF PALM BEACH LAKES BLVD TO
 INTERIOR OF VEHICLE STACKING AREA
 D. FACE OF BUILDING TO THE BUILDING TO THE SOUTHWEST OF
 THE SITE.
  
 2. INDICATE 15" RCP PIPE INSTEAD OF 15" HDPE PIPE
 BETWEEN STRUCTURE A1 AND THE EXISTING CATCH BASIN IN
 THE CUL DE SAC. (THERE IS INSUFFICIENT COVER DEPTH NEAR
 THE EXISTING CATCH BASIN FOR THE HDPE PIPE.)
  
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 [email protected]
  