| 2022-08-08 12:11:44 | THE FOLLOWIONG COMMENTS ARE FROM THE REVIEW OF THE |
| | 8/8/2022 SUBMITTAL: |
| | |
| | CONDITIONS FOR SITE PLAN APPROVAL: |
| | |
| | 1. REVISE ENGINEERING PLANS FOR ENGINEERING PERMIT |
| | SUBMITTAL TO INCLUDE:CROSS SECTIONS SHOWING GRADE |
| | BREAKS, SURFACE SLOPES, SURFACE FEATURES, RIGHT OF WAY |
| | LABELS, DISTANCES FROM PROPERTY LINE TO GRADE BREAKS: |
| | A. DRIVEAY CONNECTIONS AT THE PROPERTY LINE. FOR THE |
| | DRIVEAY AT THE CUL-DE-SAC, EXTEND THE SECTION TO THE |
| | FACE OF THE BUILDING AND TO 5 FEET IN THE CUL-DE-SAC. |
| | B. FACE OF BUILDING TO THE CHAIN LINK FENCE ON THE |
| | OUTSIDE OF THE NORTHEAST PROPERTY LINE |
| | C. EDGE OF PAVEMENT OF PALM BEACH LAKES BLVD TO |
| | INTERIOR OF VEHICLE STACKING AREA |
| | D. FACE OF BUILDING TO THE BUILDING TO THE SOUTHWEST OF |
| | THE SITE |
| | |
| | 2. POSITION DUMPSTER ENCLOSURE SO THAT THE GATES DO NOT |
| | OPEN UP INTO THE RIGHT OF WAY. |
| | |
| | 3. ADJUST THE PROPOSED CURB BETWEEN THE DUMPSTER |
| | ENCLOSURE AND THE UTILITY POLE TO BE WITHIN THE RIGHT |
| | OF WAY. CURB CAN TURN TO THE DUMPSTER PAD AS SHOWN FOR |
| | THE NORTH CURB TO THE DUMPSTER PAD. |
| | |
| | 4. IDENTIFY WHERE THE DECORATIVE PAVERS WILL BE |
| | LOCATED. HATCH PATTERN OF HANDICAP CROSS WALK IS NOT |
| | IDENTIFIED IN THE LEGEND. |
| | |
| | TRACY WARD, PE |
| | SENIOR STORMWATER ENGINEER |
| | ENGINEERING SERVICES DEPARTMENT |