Plan Review Notes
Plan Review Notes For Project Z22030025
Project Number Z22030025
Review Stop STORM
Sequence Number 1
Notes
Date Text
2022-04-14 10:05:53THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. THE CITY'S OFFICIAL VERTICAL DATUM IS NGVD1929. THE
 CITY HAS ALLOWED THE USE OF NAVD1988 AS LONG AS THE
 CONVERSION EQUATION TO NGVD1929 AT THE PROJECT LOCATION
 IS PROVIDED. PROVIDE CONVERSION TO NGVD1929 ON THE
 SURVEY AND EVERY SHEET WITH ELEVATION INFORMATION.
  
 2. SHOW AND LABEL STORM PIPE BETWEEN CATCH BASIN IN THE
 CUL-DE-SAC AND THE CANAL.
  
 3. PROVIDE CROSS SECTIONS AT THE DRIVEWAY CONNECTIONS
 AT THE PROPERTY LINES. LABEL PROPERTY LINE AND SHOW
 GENERAL SURFACES ARE SLOPING AND WHERE THE HIGH POINT
 WILL BE WITHIN THE SITE.
  
 4. PROVIDE CROSS SECTION FROM PALM BEACH LAKES BLVD TO
 INTERIOR OF VEHICLE STACKING AREA.
  
 5. PROVIDE CROSS SECTION FROM OUTSIDE NORTHEAST
 PROPERTY LINE TO FACE OF BUILDING. DIMENSION DRIVE
 AISLE, PARKING, LANDSCAPING, ETC.
  
 6. CAR WASH WASTEWATER IS NOT TO ENTER THE DRAINAGE
 SYSTEM.
  
 7. THE CITY DOES NOT ALLOW THE USE OF ORIFICES WITH
 EXFILTRATION TRENCHES.
  
 8. INCLUDE PRBS IN STRUCTURES CONNECTED TO EXFILTRATION
 TRENCHES TO EXTEND THE LIFE OF THE EXFILTRATION
 TRENCHES.
  
 9. AVOID PLANTING TREES OVER UTILITY PIPES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP
 CRITERIA. STORMWATER CALCULATIONS WILL BE REVIEWED WITH
 THE ENGINEERING PERMIT SUBMITTAL.
  
 2. PROVIDE COPY OF SFWMD ERP PERMIT BEFORE START OF
 CONSTRUCTION, IF REQUIRED.
  
 3. PROVIDE AN EROSION CONTROL PLAN WITH DETAILS.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 [email protected]
  
  Print


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved