2022-04-13 14:41:04-PLAN ON CONNECTING TO THE 16" WM IN THE REAR OF THE
 PROPERTY. THE CITY HAS NO RECORD OF THE 3" LINE AND IT
 APPEARS TO BE FOR IRRIGATION.
 -SHOW THE EXISTING 8" CAS FORCE MAIN. CONTACT JANICE
 TARBILL [email protected] FOR AS-BUILT/RECORD
 INFORMATION.
 -ADD NOTE THIS IS WITHIN LS 73 SERVICE BOUNDARY.
 -SHOW ALL EXISITING VALVES ON THE 16" WM.