Plan Review Notes
Plan Review Notes For Project Z22020023
Project Number Z22020023
Review Stop ENG - PPRC
Sequence Number 1
Notes
Date Text
2022-03-04 08:11:19Z22020023 ? 695 S OLIVE HOTEL ? 2-23-22 REVIEW
  
 MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH
 CITY OF WPB PUBLIC UTILITIES, REGARDING PLACEMENT OF
 BACKFLOW DEVICES AND WATER METERS. CONTACT HIM AT
 561-822-2262 OR [email protected]
  
 -WHY IS APPLICANT SEEKING CHANGE OF USE FROM
 RESIDENTIAL MICRO UNITS TO HOTEL?
  
 -CALLOUT ON SHEET A1-01 DOUBLE DETECTION CHECK VALVE
 AND WATER METER UNDER GROUND - SEE CIVIL DWGS NEEDS TO
 BE UPDATED AS DDCV CANNOT BE UNDER GROUND.
  
 -PLANTING PLAN LP 1.01 DOES NOT MATCH FIELD CONDITIONS
 AS OF 25FEB2022 WITH REGARD TO BUSHES AND LANDSCAPING
 AROUND WATER METER VAULT. IS PLAN CORRECT AND CHANGE
 INTENDED?
  
 -UTILITY PLAN DOES NOT SHOW GREASE INTERCEPTOR FOR ONE
 OF THE PROPOSED RESTAURANT/RETAIL SPACES. APPLICANT
 NEEDS TO COMPLY WITH ANY GREASE INTERCEPTOR
 REQUIREMENTS IF RESTAURANT IS ESTABLISHED THERE.
  
 -WOULD HOTEL PORTION HAVE ANY FOOD SERVICE REQUIRING
 INSTALLATION OF GREASE INTERCEPTOR?
  
 -VERIFY PEDESTRIAN AND UTILITY EASEMENTS ARE RECORDED
 AS SHOWN ON UTILITY PLAN.
  
 -VERIFY IF THE WATER AND SEWER UTILITIES SHOWN ON
 UTILITY PLAN HAVE ALREADY BEEN BUILT, AND INDICATE IF
 ANY CHANGES ARE PROPOSED TO UTILITIES FROM MICROUNITS
 PLAN TO HOTEL PLAN.
  
  