Plan Review Notes
Plan Review Notes For Project Z22020019
Project Number Z22020019
Review Stop ENG - PPRC
Sequence Number 2
Notes
Date Text
2022-05-02 19:12:40RICK ROSSANO, SR. PROJECT COORDINATOR, ENGINEERING
 SERVICES DEPARTMENT AT 561-494-1098 [email protected]
 NO COMMENTS.
  
 MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH
 CITY OF WPB PUBLIC UTILITIES, REGARDING PLACEMENT OF
 BACKFLOW DEVICES AND WATER METERS. CONTACT HIM AT
 561-822-2262 OR [email protected]
 -SURVEY NOTE 1 SAYS OFFICE HAS MADE NO SEARCH OF PUBLIC
 RECORDS. WILL A PUBLIC RECORDS SEARCH BE CONDUCTED?
  
 -CIVIL PLAN SHOWS FPL UTILITY EASEMENTS WHERE BUILDING
 STRUCTURE IS PROPOSED. ARE THOSE EASEMENTS EXISTING OR
 PROPOSED. IF EXISTING, HAS FPL GIVEN APPROVAL TO
 BUILDING THE EASEMENTS?
  
 -CIVIL SECTION B-B SAYS SOD, BUT LANDSCAPING PLANS SAYS
 GREEN ISLAND FICUS AND SWISS CHEESE PLANTS. PLEASE SHOW
 METERS AND BACKFLOWS NEAR SOUTH SIDE OF BUILDING ON
 PLANTING PLAN AND PROVIDE MINIMUM 18 INCHES CLEARANCE
 BETWEEN LANDSCAPING PLANTS AND METERS, VALVES, AND
 BACKFLOWS. BECAUSE SIZE OF UTILITIES HAS NOT BEEN
 DETERMINED ON ENGINEERING PLANS, THE FOOTPRINT MAY
 CHANGE AND PLANTING PLAN MAY NEED FUTURE ADJUSTMENT.
  
 -CANNOT ASSESS PROPOSED METERED IRRIGATION WATER
 SERVICE RELOCATION DUE TO LIMITED DETAIL PROVIDED IN
 CONCEPTUAL ENGINEERING PLAN. MUCH MORE DETAIL NEEDS TO
 BE PROVIDED FOR REVIEW AT FORMAL ENGINEERING SUBMITTAL
  
 -WHAT IS THE CLEARANCE DISTANCE BETWEEN PROPOSED
 BUILDING WALL ON WEST SIDE AND THE EXISTING BUILDING
 WALL, LIGHTS, AND CONC. WALL AT EAST SIDE OF 518
 CLEMATIS? ASKING THIS FOR PRACTICAL MAINTENANCE
 PURPOSES AND ALSO BECAUSE ENGINEERING PLAN SHOWS LIGHTS
 FROM 518 CONFLICTING WITH WALL FOR 512.
  
 -ENGINEERING PLAN SHOWS EXISTING BE UNDER PROPOSED
 BUILDING. VERIFY THAT IS ACCEPTABLE. ALSO SEE CBL, OHW,
 AND TEL UTILITIES WHERE BUILDING LOCATION IS PROPOSED.
 IF THOSE UTILITIES ARE EXISTING, PLEASE CONFIRM THAT IS
 ACCEPTABLE.
  
 -WALL MOUNTING OF DCDA WOULD BE NONSTANDARD AND LIKELY
 NOT NEEDED IF FOLLOWING STANDARD DETAILS. CLEARANCE
 DISTANCE BETWEEN BACKFLOW AND WALL SHOULD TYPICALLY BE
 18 INCHES. EOR NEEDS TO PROVIDE MORE DETAIL AT FORMAL
 ENGINEERING SUBMITTAL FOR REVIEW AND ALSO MAKE SURE
 STILL COMPLIES WITH FIRE MARSHAL?S PRIOR 9A REVIEW
 COMMENT.
  
 -SIZING OF WATER SERVICES MAY BE LIMITED DUE TO
 EXISTING WATER MAIN DESIGN. LARGER SIZES MAY REQUIRE
 UPSIZING WATER MAIN FROM QUADRILLE PLAZA DR.
  
 -THE AUTOTURN ANALYSIS DOES NOT SHOW VEHICLES ENTERING
 OR EXISTING BUILDING. PLEASE ADD ADDITIONAL AUTOTURN
 ANALYSIS FOR THOSE WITH AT LEAST A SMALL MOVING TRUCK.
  
 -ENGINEERING PLAN SHOWS EXTERIOR DOORS OPENING OUTWARD
 WHILE ARCHITECTURAL PLANS SHOW RECESSED DOORS. PLEASE
 UPDATE ALL PLAN SETS AND MAKE SURE THEY ALL MATCH
 GENERAL DESIGN LAYOUT.
  
  