Plan Review Notes
Plan Review Notes For Project Z21120021
Project Number Z21120021
Review Stop STORM
Sequence Number 4
Notes
Date Text
2022-12-13 09:20:13CONDITIONS FOR SITE PLAN APPROVAL:
 1. REMOVE CURB OR ADJUST CURB CALLOUT FOR THE DRIVEWAY
 APRON/SIDEWALK.
 2. SHOW CURBS, SIDEWALKS, GUTTERS, ETC. AT THEIR PROPER
 WIDTHS/DEPTHS ON THE PLANS AND CROSS SECTIONS.
 3. PROVIDE REFERENCE ELEVATION TO NGVD1929 (THE
 CITY???S VERTICAL DATUM) ON THE SURVEY.
 4. PROVIDE EXISTING INVERT AND BOTTOM ELEVATION FOR THE
 EXISTING DRAINAGE STRUCTURES TO BE CONNECTED TO.
 5. PROVIDE INVERT INFORMATION FOR THE PROPOSED SANITARY
 LATERAL, INCLUDING THE INVERT ELEVATION OF THE EXISTING
 MAIN AT THE WYE CONNECTION AND THE TOP AND BOP
 ELEVATIONS FOR THE CROSSING OF THE PROPOSED 15???
 STORM.
 6. STORM PIPE CONNECTION TO EXISTING CATCH BASIN ON
 STATE STREET TO BE EXCLUSIVE WITHIN ONLY ONE SIDE OF
 THE STRUCTURE (I.E. DO NOT REMOVE ANY OF THE CORNER OF
 THE STRUCTURE).
 7. SHOW AND LABEL THE LANDSCAPING OVERHANG (DASHED
 LINE) FOR THE PARKING SPACES ON ALL OF THE CIVIL PLAN
 SHEETS.
 9. LABEL (SIZE AND MATERIAL) ALL EXISTING UTILITIES IN
 THE R/W.
 10. PROVIDE A CROSS SECTION FOR THE DRIVEWAY FROM THE
 CENTERLINE OF THE R/W TO 5 FEET PAST THE HIGH POINT OF
 THE DRIVEWAY. CALLOUT SURFACE FEATURES AND PROVIDE
 DIMENSIONS FROM THE R/W TO THE BACK OF CURB, EDGE OF
 PAVEMENT, R/W CENTERLINE, HIGH POINT OF DRIVEWAY AND
 OTHER BREAKPINTS OF DRIVEWAY. SHOW AND LABEL LOCATION
 OF SIDEWALK CROSSING. LABEL STREET NAME OF THE R/W.
  
 THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 11/4/2022 SUBMITTAL. PREVIOUSLY SATISFIED COMMENTS ARE
 NOT LISTED.
  
 5. [PARTIALLY SATISFIED - SEE COMMENTS UNDER NEW
 COMMENTS BELOW] PROVIDE CROSS SECTIONS FROM:
 A. BUILDING TO EACH R/W CENTERLINE
 B. AT PROPOSED DRIVEWAY
 C. FROM GRANT ST CENTERLINE TO PARKING LOT
 D. FROM WEST PROPERTY LINE TO FACE OF BUILDING.
 E. BETWEEN THE TWO BUILDINGS
  
 LABEL STREETS, PROPERTY LINES, SURFACE FEATURES AND
 GENERAL SURFACE SLOPES. PROVIDE DIMENSIONS FOR
 CURBS/CURB AND GUTTER, SIDEWALKS AND DISTANCE FROM
 PROPERTY LINE TO FACE OF BUILDING. INCLUDE PROPOSED
 PARALLEL PARKING AREAS.
  
 6. {SATISFIED] SHOW MILL AND RESURFACING LIMITS WITHIN
 THE STREETS. ADDITIONAL COMMENT - THE EXISTING WATER
 SERVICE ON GRANT STREET MAY NEED TO BE REMOVED AND
 PLUGGED AT THE WATER MAIN.
  
  
 9. [SATISFIED ??? CORNER OF THE STRUCTURE IS NOT TO BE
 REMOVED IN ORDER TO CONNECT THE OUTFALL PIPE.] CONFIRM
 THE OUTFALL PIPE WILL NOT ENTER THE EXISTING STRUCTURE
 AT A CORNER OF THE STRUCTURE. ADDITIONAL COMMENT ? THE
 ANGLE OF THE PIPE TO THE STRUCTURE MAY REQUIRE THE HOLE
 OPENING (42 +/- INCHES) TO BE WIDER THAN THE INSIDE
 WALL DIMENSION.
  
 10. [SATISFIED ??? NOTE 13 ON SHEET C2.1 STATES ALL
 EXISTING SIDEWALKS TO BE REPLACED.] PROVIDE HATCHING
 PATTERNS FOR SIDEWALKS TO REMAIN AND FOR
 NEW/REPLACEMENT SIDEWALKS. ADDITIONAL COMMENT: ADD
 PATTERNS TO LEGEND. ADD DUMPSTER PAD HATCHING TO THE
 LEGEND.
  
  
 13. [NOT SATISFIED] THE CITY???S OFFICIAL VERTICAL
 DATUM IS NGVD1929. THE CITY HAS ALLOWED THE USE OF
 NAVD1988 AS LONG AS THE CONVERSION EQUATION TO NGVD1929
 AT THE PROJECT LOCATION IS PROVIDED. PROVIDE THE
 NAVD1988 TO NGVD1929 CONVERSION EQUATION ON THE SURVEY.
  
 14. [PARTIALLY SATISFIED] LABEL ANY NEW GUTTER OR CURB
 AND GUTTER IN THE RIGHT OF WAY. ADDITIONAL COMMENT -
 SHOW THE LINEWORK FOR THE PROPOSED VALLEY GUTTER ON
 GRANT ST. LABELED THE PROPOSED CURBING CREATED FOR THE
 ON-STREET PARKING. USE DIFFERENT LINE TYPE/WEIGHT
 BETWEEN EXISTING CURBING AND PROPOSED CURBING. DRAW THE
 VALLEY GUTTER WITH THE CORRECT WIDTH AND LOCATION.
  
  
 17. [NO LONGER APPLICABLE - SIDEWALK AREA NOT BEING
 MODIFIED FOR PARKING ON N. TAMARIND AVE] REVIEW
 AS-BUILT DRAWINGS FOR THE ARV TO DETERMINE IF THE
 STRUCTURE CAN BE MODIFIED TO LOWER THE RIM TO PROPOSED
 GRADE.
  
  
 NEW COMMENTS(3/24/22 SUBMITTAL):
  
 19. [NOT SATISFIED - REVISE FOR ENGINEERING PERMIT
 SUBMITTAL] REVISE FDOT INDEX NUMBERS TO CURRENT FDOT
 STANDARD PLAN NUMBERS ON THE SITE PLAN SHEETS AND
 ENGINEERING SHEETS.
  
  
 21. [SATISFIED] REMOVE THE HATCHING FOR THE PROPOSED
 R/W ABANDONMENT AREA ON THE ENGINEERING PLAN SHEETS.
  
 22. [NOT SATISFIED] PROVIDE THE EXISTING INVERT
 ELEVATION OF THE DRAINAGE STRUCTURE THE OUTFALL PIPE
 WILL CONNECT TO.
  
 23.[NOT SATISFIED] LIST THE WEIR ELEVATION WITH THE
 INFORMATION FOR STRUCTURE S-102.
  
 24. [NOT SATISFIED] CONFIRM THERE WILL BE SUFFICIENT
 VERTICAL CLEARANCE BETWEEN THE PROPOSED 15 INCH RCP
 OUTFALL PIPE AND 6 INCH SANITARY SEWER LATERAL.
 ADDITIONAL COMMENTS: SURVEY LISTS THE BOTTOM ELEVATION
 OF THE SANITARY SEWER MANHOLE NO. 2 AS 15.16 FT NAVD.
 THIS BOTTOM (OR MINIMUM INVERT ELEVATION FOR THE
 SANITARY LATERAL) IS LESS THAN 2 INCHES LOWER THAN THE
 TOP OF THE PROPOSED 6 INCH SANITARY LATERAL (AS LISTED
 ON THE WATER AND SEWER PLAN) WHERE THE LATERAL CROSSES
 THE PROPOSED 15 INCH RCP STORM PIPE.
  
  
 26. [NOT SATISFIED] SHOW THE 2-FT LANDSCAPE OVERHANG AT
 THE END OF THE PARKING SPACES. ADDITIONAL COMMENT ?
 OVERHANG WILL BE OVER THE SIDEWALK. SHOW THE DASHED
 LINE ON THE SIDEWALK.
  
  
 28. [NOT SATISFIED] SHOW WATER MAIN ON STATE STREET IN
 THE CORRECT LOCATION. SHOW THE VALVES FROM THE SURVEY.
  
 29. SHEET C2.3 GEOMETRIC, SIGNING AND STRIPING PLAN:
 A. [SATISFIED - EXTEND DOUBLE YELLOW TO 25 LF] PROVIDE
 STRIPING PLAN FOR MILL AND RESURFACE AREAS.
 B. [SATISFIED - SIGNS AND STOP BARS TO BE MINIMUM 4
 FEET FROM CROSS WALK] SHOW EXISTING STOP SIGNS FOR
 STATE STREET AND FOR GRANT STREET.
 E. [SATISFIED] REFERENCE THE CWPB TYPICAL 90 DEGREE
 PARKING STALL DETAIL.
  
 G. [NOT SATISFIED] TYPE D CURB CALLED OUT ACROSS
 SIDEWALK ON EAST SIDE OF PROPOSED DRIVEWAY.
 ADDITIONAL COMMENTS (7/19/22 SUBMITTAL):
 H. [NOT SATISFIED] SHARROWS SHOULD BE LOCATED AFTER THE
 INTERSECTION AND NOT IN THE INTERSECTION.
 I. [SATISFIED] CONSIDER REDUCING THE LENGTH OF THE STOP
 BAR IN THE PARKING LOT TO HALF THE WIDTH OF THE
 DRIVEWAY.
 J. [SATISFIED] CALLOUT FOR TYPE D CURB AT BACK OF
 PARALLEL PARKING SPACES ON GRANT STREET IS LOCATED ON
 TOP OF THE VALLEY GUTTER LINE WORK AND IS
 INDISCERNIBLE.
  
 30. [SATISFIED ? COMMENTS BELOW WERE MODIFIED FOR THE
 LATEST (7/19) SUBMITTAL] SECTION A (SHEET C3.2)
 A. [SATISFIED] VALLEY GUTTER NOT SHOWN OR LABELED FOR
 GRANT STREET.
 B. [SATISFIED] SHOW SLOPE DIRECTION FOR PARKING SPACE.
 C. {SATISFIED] VALLEY GUTTER FOR STATE STREET SHOWN AT
 CENTERLINE OF R/W.
 D. [SATISFIED] IS THICKENED-EDGE SIDEWALK PROPOSED FOR
 GRANT STREET? LABEL AS SUCH AND PROVIDE A DETAIL OF THE
 SIDEWALK.E. DOES THE EXISTING SIDEWALK ON STATE STREET
 HAVE CURBING AND THICKENED-EDGE AS SHOWN ON THE CROSS
 SECTION?
  
 31. [COMMENTS BELOW WERE MODIFIED FOR THE LATEST (7/19)
 SUBMITTAL] SECTION B (SHEET C3.2)
 A. [NOT SATISFIED] WILL NEW SIDEWALK HAVE THICKENED
 EDGE AT BACK OF WALK? LABEL SIDEWALK AS SUCH AND
 PROVIDE DETAIL.
  
  
  
 NEW COMMENTS (7/19/2024)
 38. [NOT SATISFIED] FOR ENGINEERING PERMIT SUBMITTAL,
 SHOW THE CURBING ON THE OTHER SIDE OF STATE STREET AND
 GRANT STREET.
  
 39. [NOT SATISFIED ??? 2015 AS-BUILT DRAWING SHOWS
 8-INCH WATER MAIN CONNECTING TO 6??? WATER MAIN ABOUT
 10 FEET WEST OF THE WEST R/W OF TAMARIND AVE] CONFIRM
 SIZE OF EXISTING WATER MAIN ON STATE STREET IS 8?.
  
 40. [NOT SATISFIED] LABEL SIZE AND MATERIAL OF ALL
 EXISTING UTILITIES ON STATE STREET, TAMARIND AVE AND
 GRANT STREET.
  
 41. [NOT SATISFIED] SHARROW STRIPING DETAIL TO BE
 PROVIDED WITH THE ENGINEERING PERMIT SUBMITTAL. BIKE
 STRIPING TO BE IN ACCORDANCE WITH CWPB STANDARD DETAILS
 AND MUTCD. PROPERLY SHOW WHERE THE MARKINGS AND SIGNAGE
 ARE TO BE PLACED.
  
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 [email protected]
  