Notes
Date Text
2022-08-01 15:32:14Z21120021 SITE G 1002 GRANT ST, 1001 STATE ST.
  
 THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 7/19/2022 SUBMITTAL:
  
 1. [SATISFIED] REMOVE REFERENCES TO VOW (VILLAGE OF
 WELLINGTON?) ON COVER.
  
 2. [SATISFIED ? AS BEST AS THEY CAN DO] PROJECT SITE ON
 PROJECT LOCATION MAP IS SHOWN ON THE EAST SIDE OF
 TAMARIND AVE. THE SITE IS ON THE WEST SIDE OF TAMARIND
 AVE.
  
 3. [SATISFIED] CONCEPTUAL ENGINEERING PLAN IS CONFUSING
 WITH EXISTING FEATURES SHOWN AND NOT SCREENED.
  
 4. [SATISFIED] PROVIDE FLOW ARROWS SHOWING DIRECTION OF
 SURFACE RUNOFF. ADDITIONAL COMMENT - ADD FLOW ARROWS
 FOR THE AREAS AROUND THE BUILDING.
  
 5. [PARTIALLY SATISFIED - SEE COMMENTS UNDER NEW
 COMMENTS BELOW] PROVIDE CROSS SECTIONS FROM:
 A. BUILDING TO EACH R/W CENTERLINE
 B. AT PROPOSED DRIVEWAY
 C. FROM GRANT ST CENTERLINE TO PARKING LOT
 D. FROM WEST PROPERTY LINE TO FACE OF BUILDING.
 E. BETWEEN THE TWO BUILDINGS
  
 LABEL STREETS, PROPERTY LINES, SURFACE FEATURES AND
 GENERAL SURFACE SLOPES. PROVIDE DIMENSIONS FOR
 CURBS/CURB AND GUTTER, SIDEWALKS AND DISTANCE FROM
 PROPERTY LINE TO FACE OF BUILDING. INCLUDE PROPOSED
 PARALLEL PARKING AREAS.
  
 6. {PARTIALLY SATISFIED] SHOW MILL AND RESURFACING
 LIMITS WITHIN THE STREETS. ADDITIONAL COMMENT - THE
 EXISTING WATER SERVICE ON GRANT STREET MAY NEED TO BE
 REMOVED AND PLUGGED AT THE WATER MAIN.
  
 7. [SATISFIED] IDENTIFY ON THE CONCEPTUAL ENGINEERING
 PLAN WHERE THE SPECIAL TYPE 'F' CURB AND GUTTER WILL BE
 CONSTRUCTED. REDRAW THE DETAIL IN ACAD AND PROVIDE
 ENGLISH UNITS. ADDITIONAL COMMENT: IF SPECIAL TYPE F
 CURB AND GUTTER IS NOT BEING CONSTRUCTED THEN DO NOT
 INCLUDE THE DETAIL FOR THE ITEM.
  
 8. [SATISFIED] LABEL WHERE THE DRAINAGE CONTROL
 STRUCTURE WILL BE LOCATED AND PROVIDE A DETAIL OF THE
 STRUCTURE. NOTE THE CITY DOES NOT ALLOW THE USE OF
 BLEEDERS WITH EXFILTRATION TRENCHES.
  
 9. [PARTIALLY SATISFIED] CONFIRM THE OUTFALL PIPE WILL
 NOT ENTER THE EXISTING STRUCTURE AT A CORNER OF THE
 STRUCTURE. ADDITIONAL COMMENT ? THE ANGLE OF THE PIPE
 TO THE STRUCTURE MAY REQUIRE THE HOLE OPENING (42 +/-
 INCHES) TO BE WIDER THAN THE INSIDE WALL DIMENSION.
  
 10. [NOT SATISFIED] PROVIDE HATCHING PATTERNS FOR
 SIDEWALKS TO REMAIN AND FOR NEW/REPLACEMENT SIDEWALKS.
 ADDITIONAL COMMENT: ADD PATTERNS TO LEGEND. ADD
 DUMPSTER PAD HATCHING TO THE LEGEND.
  
 11. [SATISFIED] PER FIGURE XV-2: GENERAL PARKING
 DIMENSIONS IN SECTION 94-485 OF THE CITY'S CODE OF
 ORDINANCES, THE CURB LENGTH OF PARALLEL PARKING SPACES
 IS 22 FEET. THE SITE PLAN SHOWS 25 FEET AND GAPS IN THE
 PARKING SPACES ON TAMARIND AVE.
  
 12. [SATISFIED] CONSIDER ANGLING THE CURBING AT EACH
 END OF PROPOSED PARALLEL PARKING SPACES TO FACILITATE
 ACCESS TO AND FROM THE END SPACES. ADDITIONAL COMMENT -
 INCREASE THE ANGLE OF THE END CURBING FROM 16 DEGREES
 FROM PERPENDICULAR TO 45 DEGREES FROM PERPENDICULAR AT
 BOTH ENDS OF THE PARKING AREA ON GRANT STREET.
  
 13. [NOT SATISFIED] THE CITY?S OFFICIAL VERTICAL DATUM
 IS NGVD1929. THE CITY HAS ALLOWED THE USE OF NAVD1988
 AS LONG AS THE CONVERSION EQUATION TO NGVD1929 AT THE
 PROJECT LOCATION IS PROVIDED. PROVIDE THE NAVD1988 TO
 NGVD1929 CONVERSION EQUATION ON THE SURVEY.
  
 14. [PARTIALLY SATISFIED] LABEL ANY NEW GUTTER OR CURB
 AND GUTTER IN THE RIGHT OF WAY. ADDITIONAL COMMENT -
 SHOW THE LINEWORK FOR THE PROPOSED VALLEY GUTTER ON
 GRANT ST. LABELED THE PROPOSED CURBING CREATED FOR THE
 ON-STREET PARKING. USE DIFFERENT LINE TYPE/WEIGHT
 BETWEEN EXISTING CURBING AND PROPOSED CURBING. DRAW THE
 VALLEY GUTTER WITH THE CORRECT WIDTH AND LOCATION.
  
 15. [SATISFIED] CONSIDER LOW IMPACT DEVELOPMENT
 DRAINAGE SYSTEMS IN LIEU OF EXFILTRATION TRENCHES.
  
 16. [SATISFIED] EASEMENT MAY BE NEEDED FOR THE SIDEWALK
 AND PARKING ON GRANT ST.
  
 17. [NO LONGER APPLICABLE - SIDEWALK AREA NOT BEING
 MODIFIED FOR PARKING ON N. TAMARIND AVE] REVIEW
 AS-BUILT DRAWINGS FOR THE ARV TO DETERMINE IF THE
 STRUCTURE CAN BE MODIFIED TO LOWER THE RIM TO PROPOSED
 GRADE.
  
 18. [SATISFIED] SHOW UTILITIES ON THE LANDSCAPE PLANS.
  
 NEW COMMENTS(3/24/22 SUBMITTAL):
  
 19. [NOT SATISFIED ? REVISE FOR ENGINEERING PERMIT
 SUBMITTAL] REVISE FDOT INDEX NUMBERS TO CURRENT FDOT
 STANDARD PLAN NUMBERS ON THE SITE PLAN SHEETS AND
 ENGINEERING SHEETS.
  
 20. [SATISFIED] SHEET SP-1 CALLS OUT A DETAIL NO. 4 ON
 SHEET SP-3. SHEET SP-3 DOES NOT HAVE A DETAIL NO. 4.
  
 21. [NOT SATISFIED] REMOVE THE HATCHING FOR THE
 PROPOSED R/W ABANDONMENT AREA ON THE ENGINEERING PLAN
 SHEETS.
  
 22. [NOT SATISFIED] PROVIDE THE EXISTING INVERT
 ELEVATION OF THE DRAINAGE STRUCTURE THE OUTFALL PIPE
 WILL CONNECT TO.
  
 23.[NOT SATISFIED] LIST THE WEIR ELEVATION WITH THE
 INFORMATION FOR STRUCTURE S-102.
  
 24. [NOT SATISFIED] CONFIRM THERE WILL BE SUFFICIENT
 VERTICAL CLEARANCE BETWEEN THE PROPOSED 15 INCH RCP
 OUTFALL PIPE AND 6 INCH SANITARY SEWER LATERAL.
 ADDITIONAL COMMENTS: SURVEY LISTS THE BOTTOM ELEVATION
 OF THE SANITARY SEWER MANHOLE NO. 2 AS 15.16 FT NAVD.
 THIS BOTTOM (OR MINIMUM INVERT ELEVATION FOR THE
 SANITARY LATERAL) IS LESS THAN 2? LOWER THAN THE TOP OF
 THE PROPOSED 6? SANITARY LATERAL (AS LISTED ON THE
 WATER AND SEWER PLAN) WHERE THE LATERAL CROSSES THE
 PROPOSED 15? RCP STORM PIPE.
  
 25. [SATISFIED] CAN S-102 AND S-101 SHIFT TO THE NORTH,
 AWAY FROM THE SOUTH PROPERTY LINE. THIS WILL REDUCE THE
 ANGLE OF THE OUTFALL PIPE CONNECTION TO THE EXISTING
 INLET. ADDITIONAL COMMENT ? STRUCTURE S-102 WILL NEED
 TO SHIFT NORTHWARD ABOUT 6 ? 8 MORE FEET SO THAT THE
 PIPE OPENING AT THE EXISTING CURB INLET WILL NOT EXCEED
 THE INSIDE HORIZONTAL DIMENSION OF THE WALL.
  
 26. [NOT SATISFIED] SHOW THE 2-FT LANDSCAPE OVERHANG AT
 THE END OF THE PARKING SPACES. ADDITIONAL COMMENT ?
 OVERHANG WILL BE OVER THE SIDEWALK. SHOW THE DASHED
 LINE ON THE SIDEWALK.
  
 27. [SATISFIED] SHOW CONCRETE FOR THE DRIVEWAY APRON
 AND SIDEWALK WITHIN THE R/W.
  
 28. [NOT SATISFIED] SHOW WATER MAIN ON STATE STREET IN
 THE CORRECT LOCATION. SHOW THE VALVES FROM THE SURVEY.
  
 29. SHEET C2.3 GEOMETRIC, SIGNING AND STRIPING PLAN:
 A. [PARTIAL SATISFIED ? EXTEND DOUBLE YELLOW TO 25 LF]
 PROVIDE STRIPING PLAN FOR MILL AND RESURFACE AREAS.
 B. [PARTIALLY SATISFIED ? SIGNS AND STOP BARS TO BE
 MINIMUM 4 FEET FROM CROSS WALK] SHOW EXISTING STOP
 SIGNS FOR STATE STREET AND FOR GRANT STREET.
 C. [SATISFIED] MOVE STOP BAR AND STOP SIGN FOR PARKING
 LOT TO BEHIND THE SIDEWALK.
 D. [SATISFIED] REMOVE REFERENCE TO CITY OF RIVIERA
 BEACH LAND DEVELOPMENT CODE FROM NOTES.
 E. REFERENCE THE CWPB TYPICAL 90 DEGREE PARKING STALL
 DETAIL.
 F. [SATISFIED] TYPE D CURB CALLED OUT FOR WEST EDGE OF
 PARKING LOT BUT THIS CURB IS NOT SHOWN ON THE PGD PLAN.
 G. [NOT SATISFIED] TYPE D CURB CALLED OUT ACROSS
 SIDEWALK ON EAST SIDE OF PROPOSED DRIVEWAY.
 ADDITIONAL COMMENTS (7/19/22 SUBMITTAL):
 H. SHARROWS SHOULD BE LOCATED AFTER THE INTERSECTION
 AND NOT IN THE INTERSECTION.
 I. CONSIDER REDUCING THE LENGTH OF THE STOP BAR IN THE
 PARKING LOT TO HALF THE WIDTH OF THE DRIVEWAY.
 J. CALLOUT FOR TYPE D CURB AT BACK OF PARALLEL PARKING
 SPACES ON GRANT STREET IS LOCATED ON TOP OF THE VALLEY
 GUTTER LINE WORK AND IS INDISCERNIBLE.
  
 30. [PARTIALLY SATISFIED ? COMMENTS BELOW WERE MODIFIED
 FOR THE LATEST (7/19) SUBMITTAL] SECTION A (SHEET C3.2)
 A. VALLEY GUTTER NOT SHOWN OR LABELED FOR GRANT STREET.
 B. SHOW SLOPE DIRECTION FOR PARKING SPACE.
 C. VALLEY GUTTER FOR STATE STREET SHOWN AT CENTERLINE
 OF R/W.
 D. IS THICKENED-EDGE SIDEWALK PROPOSED FOR GRANT
 STREET? LABEL AS SUCH AND PROVIDE A DETAIL OF THE
 SIDEWALK.E. DOES THE EXISTING SIDEWALK ON STATE STREET
 HAVE CURBING AND THICKENED-EDGE AS SHOWN ON THE CROSS
 SECTION?
  
 31. [PARTIALLY SATISFIED ? COMMENTS BELOW WERE MODIFIED
 FOR THE LATEST (7/19) SUBMITTAL] SECTION B (SHEET C3.2)
 A. WILL NEW SIDEWALK HAVE THICKENED EDGE AT BACK OF
 WALK? LABEL SIDEWALK AS SUCH AND PROVIDE DETAIL.
  
  
 36. [SATISFIED] SIZE OF OUTFALL PIPE SHOWN ON THE
 CONTROL STRUCTURE DETAIL DOES NOT MATCH WHAT IS CALLED
 OUT ON THE PGD PLAN. JUSTIFY ANY OUTFALL PIPE DIAMETER
 LARGER THAN 15 INCH.
  
 37. [SATISFIED]SHEET C4.1 EROSION CONTROL PLAN (CAN BE
 ADDRESSED WITH ENGINEERING PERMIT SUBMITTAL):
 A. PROVIDE ALTERNATIVE TO HAY BALES FOR INLET
 PROTECTION.
 B. IDENTIFY WHICH INLETS ARE TO BE PROTECTED (ONSITE
 AND WITHIN R/W)
 C. MOVE HATCHING FOR CONSTRUCTION ACCESS OUT OF THE
 R/W.
  
 NEW COMMENTS (7/19/2024)
 38. FOR ENGINEERING PERMIT SUBMITTAL, SHOW THE CURBING
 ON THE OTHER SIDE OF STATE STREET AND GRANT STREET.
  
 39. CONFIRM SIZE OF EXISTING WATER MAIN ON STATE STREET
 IS 8?.
  
 40. LABEL SIZE AND MATERIAL OF ALL EXISTING UTILITIES
 ON STATE STREET, TAMARIND AVE AND GRANT STREET.
  
 41. SHARROW STRIPING DETAIL TO BE PROVIDED WITH THE
 ENGINEERING PERMIT SUBMITTAL. BIKE STRIPING TO BE IN
 ACCORDANCE WITH CWPB STANDARD DETAILS AND MUTCD.
 PROPERLY SHOW WHERE THE MARKINGS AND SIGNAGE ARE TO BE
 PLACED.
  
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT