2022-01-13 12:54:09THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. REMOVE REFERENCES TO VOW (VILLAGE OF WELLINGTON?) ON
 COVER.
 2. PROJECT SITE ON PROJECT LOCATION MAP IS SHOWN ON THE
 EAST SIDE OF TAMARIND AVE. THE SITE IS ON THE WEST SIDE
 OF TAMARIND AVE.
 3. CONCEPTUAL ENGINEERING PLAN IS CONFUSING WITH
 EXISTING FEATURES SHOWN AND NOT SCREENED.
 4. PROVIDE FLOW ARROWS SHOWING DIRECTION OF SURFACE
 RUNOFF.
 5. PROVIDE CROSS SECTIONS FROM:
 A. BUILDING TO EACH R/W CENTERLINE
 B. AT PROPOSED DRIVEWAY
 C. FROM GRANT ST CENTERLINE TO PARKING LOT
 D. FROM WEST PROPERTY LINE TO FACE OF BUILDING.
 E. BETWEEN THE TWO BUILDINGS
  
 LABEL STREETS, PROPERTY LINES, SURFACE FEATURES AND
 GENERAL SURFACE SLOPES. PROVIDE DIMENSIONS FOR
 CURBS/CURB AND GUTTER, SIDEWALKS AND DISTANCE FROM
 PROPERTY LINE TO FACE OF BUILDING. INCLUDE PROPOSED
 PARALLEL PARKING AREAS.
 6. SHOW MILL AND RESURFACING LIMITS WITHIN THE STREETS.
 7. IDENTIFY ON THE CONCEPTUAL ENGINEERING PLAN WHERE
 THE SPECIAL TYPE ?F? CURB AND GUTTER WILL BE
 CONSTRUCTED. REDRAW THE DETAIL IN ACAD AND PROVIDE
 ENGLISH UNITS.
 8. LABEL WHERE THE DRAINAGE CONTROL STRUCTURE WILL BE
 LOCATED AND PROVIDE A DETAIL OF THE STRUCTURE. NOTE THE
 CITY DOES NOT ALLOW THE USE OF BLEEDERS WITH
 EXFILTRATION TRENCHES.
 9. CONFIRM THE OUTFALL PIPE WILL NOT ENTER THE EXISTING
 STRUCTURE AT A CORNER OF THE STRUCTURE.
 10. PROVIDE HATCHING PATTERNS FOR SIDEWALKS TO REMAIN
 AND FOR NEW/REPLACEMENT SIDEWALKS.
 11. PER FIGURE XV-2: GENERAL PARKING DIMENSIONS IN
 SECTION 94-485 OF THE CITY?S CODE OF ORDINANCES, THE
 CURB LENGTH OF PARALLEL PARKING SPACES IS 22 FEET. THE
 SITE PLAN SHOWS 25 FEET AND GAPS IN THE PARKING SPACES
 ON TAMARIND AVE.
 12. CONSIDER ANGLING THE CURBING AT EACH END OF
 PROPOSED PARALLEL PARKING SPACES TO FACILITATE ACCESS
 TO AND FROM THE END SPACES.
 13. THE CITY?S OFFICIAL VERTICAL DATUM IS NGVD1929. THE
 CITY HAS ALLOWED THE USE OF NAVD1988 AS LONG AS THE
 CONVERSION EQUATION TO NGVD1929 AT THE PROJECT LOCATION
 IS PROVIDED. PROVIDE THE NAVD1988 TO NGVD1929
 CONVERSION EQUATION ON THE SURVEY.
 14. LABEL ANY NEW GUTTER OR CURB AND GUTTER IN THE
 RIGHT OF WAY.
 15. CONSIDER LOW IMPACT DEVELOPMENT DRAINAGE SYSTEMS IN
 LIEU OF EXFILTRATION TRENCHES.
 16. EASEMENT MAY BE NEEDED FOR THE SIDEWALK AND PARKING
 ON GRANT ST.
 17. REVIEW AS-BUILT DRAWINGS FOR THE ARV TO DETERMINE
 IF THE STRUCTURE CAN BE MODIFIED TO LOWER THE RIM TO
 PROPOSED GRADE.
 18. SHOW UTILITIES ON THE LANDSCAPE PLANS.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP
 CRITERIA. STORMWATER CALCULATIONS WILL BE REVIEWED WITH
 THE ENGINEERING PERMIT SUBMITTAL.
  
 2. PROVIDE COPY OF SFWMD ERP PERMIT BEFORE START OF
 CONSTRUCTION, IF REQUIRED.
  
 3. PROVIDE AN EROSION CONTROL PLAN WITH DETAILS.
  