Plan Review Notes
Plan Review Notes For Project Z21120021
Project Number Z21120021
Review Stop PU
Sequence Number 1
Notes
Date Text
2022-01-05 17:01:18CUT/CAP UNUSED SERVICES AT THE MAIN.
 -PROFILE OF THE TAP TO POINT OF SERVICE.
 -THE CITY DOES NOT ALLOW 3? SERVICES. PLEASE UPSIZE TO
 4?
 -SHOW/LABEL EASEMENT.
 -THE PLAN VIEW IS TOUGH TO READ. COULD YOU PLEASE MAKE
 IT MORE LEGIBLE?
 -PROVIDE POST CCTV OF THE LATERALS.
 -FOR THE STORMWATER SYSTEM, PLEASE SHOW THE TRUNK LINE
 ON THE PLANS.
 - FOR STORMWATER STRUCTURES CALL OUT STATIONING AND
 HORIZONTAL SEPARATION BETWEEN UTILITIES
  
 CONTACT MIKE TECHNOW 561-494-1047 OR [email protected]
 WITH ANY QUESTIONS.