Plan Review Notes
Plan Review Notes For Project Z21120020
Project Number Z21120020
Review Stop STORM
Sequence Number 4
Notes
Date Text
2022-12-13 09:37:27CONDITIONS FOR SITE PLAN APPROVAL:
 1. PROVIDE A REFERENCE ELEVATION TO NGVD1929 ON THE
 SURVEY.
 2. CONFIRM RUNOFF FROM THE SIDEWALK ALONG THE WEST SIDE
 OF THE BUILDING WILL FLOW TO AN ONSITE DRAINAGE
 STRUCTURE.
 3. IN ORDER TO PROPERLY MAINTAIN THE SWALE ALONG THE
 SOUTH PROPERTY LINE, THE SIDES SHOULD BE SLOPED 4:1 OR
 FLATTER.
 4. IDENTIFY THE MATERIAL TO BE USED TO CONSTRUCT THE
 PATH FROM THE BUILDING TO THE TOT LOT.
 5. DRIVEWAY APRON WITHIN THE R/W TO BE COMPOSED OF
 CONCRETE.
 6. REMOVE THE CALLOUT OR DEFINE THE LIMITS OF THE
 COLORED STAMPED ASPHALT AS CALLED OUT ON SHEET C2.1.
  
 THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 11/4/2022 SUBMITTAL. PREVIOUSLY SATISFIED COMMENTS ARE
 NOT LISTED.
  
 7. [PARTIALLY SATISFIED - SEE MORE COMMENTS UNDER NEW
 COMMENTS BELOW.] PROVIDE CROSS SECTIONS FROM:
 A. FACE OF BUILDING TO TAMARIND AVE CENTERLINE
 B. FACE OF BUILDING TO GRANT ST CENTERLINE
 C. AT PROPOSED DRIVEWAY
 D. FROM WEST PROPERTY LINE TO FACE OF BUILDING
 E. FROM SOUTH PROPERTY LINE TO PARKING LOT
 F. FROM SOUTH PROPERTY LINE TO FACE OF BUILDING
 LABEL STREETS, PROPERTY LINES, SURFACE FEATURES AND
 GENERAL SURFACE SLOPES. PROVIDE DIMENSIONS FOR
 CURBS/CURB AND GUTTER, SIDEWALKS AND DISTANCE FROM
 PROPERTY LINE TO FACE OF BUILDING. INCLUDE PROPOSED
 PARALLEL PARKING AREAS.
  
 10. [SATISFIED ??? NOTE 13 ON SHEET C2.1 STATES ALL
 SIDEWALKS ADJACENT TO THE PROPERTY ARE TO BE REPLACED.]
 PROVIDE HATCHING PATTERNS FOR SIDEWALKS TO REMAIN AND
 FOR NEW/REPLACEMENT SIDEWALKS. ADDITIONAL COMMENT -
 SHOW CONCRETE FOR THE PROPOSED DRIVEWAY APRON WITHIN
 THE R/W. SIDEWALKS AT EXISTING DRIVEWAY APRONS TO BE
 REPLACED IF CROSS SLOPE EXCEEDS 2%.
  
 15. [NOT SATISFIED] THE CITY'S OFFICIAL VERTICAL DATUM
 IS NGVD1929. THE CITY HAS ALLOWED THE USE OF NAVD1988
 AS LONG AS THE CONVERSION EQUATION TO NGVD1929 AT THE
 PROJECT LOCATION IS PROVIDED. PROVIDE THE NAVD1988 TO
 NGVD1929 CONVERSION EQUATION ON THE SURVEY.
  
  
 NEW COMMENTS (3/19/22 SUBMITTAL):
  
 19. [NOT SATISFIED - PROVIDE ON ENGINEERING PERMIT
 SUBMITTAL.] REVISE FDOT INDEX NUMBERS TO CURRENT FDOT
 STANDARD PLAN NUMBERS ON THE SITE PLAN SHEETS AND
 ENGINEERING SHEETS.
  
  
 25. SHEET C2.3 GEOMETRIC, SIGNING AND STRIPING PLAN:
 A. [SATISFIED - STRIPING NEEDED AROUND THE MEDIAN
 ISLAND] PROVIDE STRIPING PLAN FOR MILL AND RESURFACE
 AREAS.
  
 26. [PARTIALLY SATISFIED ? COMMENTS BELOW ARE FOR THE
 REVISED SECTION A ON SHEET C3.2 IN 7/19 SUBMITTAL]
 SECTION A (SHEET C3.2)
 A. [SATISFIED] SIDEWALK ALONG TAMARIND AVE APPEARS TO
 SHOW THICKENED EDGE AT BACK OF SIDEWALK.
 B. [SATISFIED] ADJUST HATCH PATTERN TO THE SPOT GRADE
 FOR THE EXISTING PROPERTY WEST OF THE WEST PROPERTY
 LINE.
 C. [SATISFIED] SPOT GRADE OF PARKING LOT DRIVE
 CENTERLINE LOWER THAN THE GRATE ELEVATIONS OF THE CATCH
 BASIN INLETS.
 D. [NOT SATISFIED] TOP OF CURB ELEVATION ALONG EAST
 SIDE OF THE PARKING LOT IS HIGHER THAN THE SIDEWALK
 ELEVATION ALONG THE WEST SIDE OF THE BUILDING.
  
  
 27. {PARTIALLY SATISFIED ? COMMENTS BELOW ARE FOR THE
 REVISED SECTION B ON SHEET C3.2 IN 7/19/SUBMITTAL}
 SECTION B (SHEET C3.2)
 A. [PARTIALLY SATISFIED ??? GRADING PLAN SHOWS NORTH
 SWALE BANK DESIGNED TO HAVE 2:1 (STEEP) SLOPE] PROVIDE
 SWALE ALONG THE SOUTH PROPERTY LINE TO KEEP RUNOFF FROM
 FLOWING ONTO ADJACENT PROPERTY.
 B. [SATISFIED] SIDEWALK ON 19TH STREET APPEARS TO HAVE
 CURB ALONG THE FRONT OF THE SIDEWALK AND THICKENED EDGE
 ALONG THE BACK OF SIDEWALK. CALL THESE OUT ON THE
 SECTION AND PROVIDE DETAIL FOR THICKENED EDGE SIDEWALK.
  
 31. SHEET C4.1 EROSION CONTROL PLAN (CAN BE ADDRESSED
 WITH ENGINEERING PERMIT SUBMITTAL):
 C. [SATISFIED] MOVE HATCHING FOR CONSTRUCTION ACCESS
 OUT OF THE R/W.
  
 NEW COMMENTS ON 7-19-2022 SUBMITTAL:
 32. [SATISFIED] SHEET C2.1 SHOWS FLOW ARROW TOWARD
 ADJACENT PROPERTY. SURFACE RUNOFF MAY NOT FLOW ONTO
 ADJACENT PROPERTY.
  
 33. [NOT SATISFIED] SHOW CONCRETE FOR DRIVEWAY WITHIN
 THE RIGHT OF WAY.
  
 34. [SATISFIED] RIM ELEVATION FOR STRUCTURE S-102
 SHOULD BE LOWER THAN THE BACK OF SIDEWALK ELEVATION OF
 19TH STREET. RIM ELEVATION CALLED OUT AS 21.4 FT NAVD
 BUT PROPOSED SPOT GRADE IS 19.5 FT NAVD AT STRUCTURE.
  
 35. [SATISFIED] PROVIDE SPOT GRADES FOR BBQ AND TOT LOT
 AREAS. THE EXISTING GRADES ALONG THE PROPERTY LINE ARE
 3 FEET +/- LOWER THAN THE PROPOSED TOP OF CURB
 ELEVATION FOR THE PARKING LOT.
  
 36. [SATISFIED] CHECK THE SLOPE OF THE SIDEWALK FROM
 THE HANDICAP ACCESS AISLE TO THE COVER WALKWAY ALONG
 THE WEST SIDE OF THE BUILDING. THE SLOPE APPEARS TO
 EXCEED 5%.
  
 37. [NOT SATISFIED] LABEL (INCLUDING SURFACE TREATMENT)
 THE PATH FROM THE COVERED WALKWAY TO THE TOT LOT.
  
 38. [ NOT APPLICABLE ??? MIDBLOCK CROSS WALK REMOVED
 FROM THE PLANS] CALLOUT THE FDOT CURB RAMP NUMBER FOR
 THE MIDBLOCK CROSSWALK.
  
 39. [NOT SATISFIED] BICYCLE STRIPING TO BE PER CWPB
 STANDARD DETAILS AND THE MUTCD. SHOW THE APPROPRIATE
 LOCATIONS OF THESE MARKINGS ON SHEET C2.3.
  
 40. [NOT APPLICABLE ??? CROSS WALK REMOVED FROM THE
 PLANS.]SHOW STRIPING AND SIGNAGE FOR MIDBLOCK
 CROSSWALK.
 NEW COMMENT (11-4-2022)
 41. SHEET C2.1 CALLS OUT COLORED STAMPED ASPHALT FOR
 THE ON-STREET PARKING ON TAMARIND AVE. SHOW THE EXTENT
 OF THE STAMPED ASPHALT. DEVELOPER MAY BE RESPONSIBLE TO
 MAINTAIN THE STAMPED ASPHALT.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 [email protected]
  