Plan Review Notes
Plan Review Notes For Project Z21120020
Project Number Z21120020
Review Stop PU
Sequence Number 1
Notes
Date Text
2022-01-05 16:56:55-PROVIDE LEVEL OF SERVICE CALCULATIONS.
 - SHOW EXISTING UTILITIES ON TAMARIND.
 - REPLACE/LINE EXISTING LATERALS AS REQUIRED. PROVIDE
 POST CCTV FOOTAGE.
 -ADD NOTE TO CUT AND CAP EXISTING DOUBLE WATER METER AT
 MAIN.
 -CONFIRM THAT THE EXISTING 6? LATERAL IS SUFFICIENT FOR
 PROPOSED FLOW. REFERENCE DOUBLE SERVICE DETAIL.
 -TELEVISE AND CONFIRM CONDITION OF EXISTING LATERALS
 AND VERIFY THAT IT IS ADEQUATE.
 -SHOW PROFILE OF 4? CONNECTION FROM TAP TO POINT OF
 SERVICE.
 -SHOW EXISTING VALVES.
 -CUSTOMER SERVICE TO COMMENT ON MASTER METER VS
 INDIVIDUAL METER.
 -TELEVISE EXISTING UTILITY FRONTING PROPERTY FROM
 MANHOLE TO MANHOLE.
 -SHOW PROPERTY LINE ON 19TH ST.
 -PLEASE UPSIZE THE 6? WM TO 8? WITHIN PROJECT LIMITS.
 -MISSING LEVEL OF SERVICE CALC SHEET.
 - FOR STORMWATER STRUCTURES CALL OUT STATIONING AND
 HORIZONTAL SEPARATION BETWEEN UTILITIES
  
 CONTACT MIKE TECHNOW 561-494-1047 WITH ANY QUESTIONS.