Plan Review Notes
Plan Review Notes For Project Z21120019
Project Number Z21120019
Review Stop STORM
Sequence Number 3
Notes
Date Text
2022-08-01 15:12:55Z21120019 SITE A 2212 N. TAMARIND AVE
  
 THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 7/19/2022 SUBMITTAL.
 1. [SATISFIED] CONFIRM PROJECT ADDRESS (2122 VS. 2212
 N. TAMARIND AVE)
  
 2. [SATISFIED] REMOVE REFERENCES TO VOW (VILLAGE OF
 WELLINGTON?) ON COVER.
  
 3. [SATISFIED] CONCEPTUAL ENGINEERING PLAN IS CONFUSING
 WITH EXISTING FEATURES SHOWN AND NOT SCREENED.
  
 4. [SATISFIED] RELOCATE DRAINAGE SYSTEM FROM UNDER
 STAIRS.
  
 5. [SATISFIED] PROVIDE FLOW ARROWS SHOWING DIRECTION OF
 SURFACE RUNOFF. ADDITIONAL COMMENT: PROVIDE FLOW ARROWS
 AROUND ALL SIDES OF THE BUILDINGS AND BETWEEN THE
 BUILDINGS.
  
 6. [PARTIALLY SATISFIED - SEE ADDITIONAL COMMENTS UNDER
 NEW COMMENTS BELOW.] PROVIDE AT LEAST TWO CROSS
 SECTIONS FROM EACH R/W CENTERLINE TO THE FACE OF
 BUILDING(S) AND/OR TO PARKING LOT; AND CROSS SECTIONS
 FROM EAST PROPERTY LINE TO FACE OF BUILDINGS. LABEL
 STREETS, PROPERTY LINES, SURFACE FEATURES AND GENERAL
 SURFACE SLOPES. PROVIDE DIMENSIONS FOR CURBS/CURB AND
 GUTTER, SIDEWALKS AND DISTANCE FROM PROPERTY LINE TO
 FACE OF BUILDING. INCLUDE PROPOSED PARALLEL PARKING
 AREAS.
  
 7. [SATISFIED] PROVIDE ADA TRUNCATED MAT ON THE EAST
 SIDE OF THE DRIVEWAY.
  
 8. [SATISFIED] SHOW MILL AND RESURFACING LIMITS WITHIN
 THE STREETS. ADDITIONAL COMMENT: EXTEND MILL AND
 RESURFACING LIMITS FOR THE EXISTING SEWER LATERALS THAT
 WILL BE REMOVED AND CAPPED AT THE MAIN.
  
 9. [SATISFIED] IDENTIFY ON THE CONCEPTUAL ENGINEERING
 PLAN WHERE THE SPECIAL TYPE F CURB AND GUTTER WILL BE
 CONSTRUCTED. REDRAW THE DETAIL IN ACAD AND PROVIDE
 ENGLISH UNITS. ADDITIONAL COMMENT: SHOW IN THE PGD PLAN
 WHERE THIS CURB WILL BE CONSTRUCTED.
  
 10. [SATISFIED] LABEL WHERE THE DRAINAGE CONTROL
 STRUCTURE WILL BE LOCATED AND PROVIDE A DETAIL OF THE
 STRUCTURE. NOTE THE CITY DOES NOT ALLOW THE USE OF
 BLEEDERS WITH EXFILTRATION TRENCHES.
  
 11. [NOT SATISFIED] PROVIDE HATCHING PATTERNS FOR
 SIDEWALKS TO REMAIN AND FOR NEW/REPLACEMENT SIDEWALKS.
 ADDITIONAL COMMENT: SIDEWALK WILL BE REPLACED AT
 PROPOSED DRIVEWAY LOCATION AND FOR MIDBLOCK CROSSWALK.
  
 12. [NOT SATISFIED] EXPLAIN HOW ACCESS FROM THE
 BUILDINGS TO THE PARKING LOT WILL BE PROVIDED FOR THE 3
 FT+/- GRADE DIFFERENTIAL. ADDITIONAL COMMENT: PROVIDE
 ADDITIONAL PROPOSED GRADES FOR SIDEWALKS ON THE EAST
 SIDES OF THE BUILDING. THE PROPOSED ELEVATION OF THE
 WEST END OF THE HANDICAP PARKING ACCESS AISLE IS 30.5
 FEET NAVD. THE FFE ELEVATION OF THE BUILDINGS IS
 PROPOSED TO BE 29.5 FT NAVD. NOTE SHEET C3.2 WAS NOT
 INCLUDED ON THE 7/19/22 SUBMITTAL.
  
 13. [SATISFIED] PER FIGURE XV-2: GENERAL PARKING
 DIMENSIONS IN SECTION 94-485 OF THE CITY'S CODE OF
 ORDINANCES, THE CURB LENGTH OF PARALLEL PARKING SPACES
 IS 22 FEET. THE SITE PLAN SHOWS 25 FEET AND GAPS IN THE
 PARKING SPACES ON TAMARIND AVE.
  
 14. [SATISFIUED] CONSIDER ANGLING THE CURBING AT EACH
 END OF PROPOSED PARALLEL PARKING SPACES TO FACILITATE
 ACCESS TO AND FROM THE END SPACES.
  
 15. [SATISFIED] THE CITY'S OFFICIAL VERTICAL DATUM IS
 NGVD1929. THE CITY HAS ALLOWED THE USE OF NAVD1988 AS
 LONG AS THE CONVERSION EQUATION TO NGVD1929 AT THE
 PROJECT LOCATION IS PROVIDED. PROVIDE THE NAVD1988 TO
 NGVD1929 CONVERSION EQUATION ON THE SURVEY.
  
 16. [SATISFIED - RESPONSE INDICATED NO NEW GUTTERS.]
 LABEL ANY NEW GUTTER ON 21ST ST.
  
 17. [SATISFIED] SIDEWALK EASEMENT WILL BE NEEDED FOR
 22ND ST. SIDEWALK.
  
 18. [SATISFIED] CONSIDER LOW IMPACT DEVELOPMENT
 DRAINAGE SYSTEMS IN LIEU OF EXFILTRATION TRENCHES.
  
 19. [SATISFIED] SHOW UTILITIES ON THE LANDSCAPE PLANS.
  
  
 NEW COMMENTS (3/4/22 SUBMITTAL):
  
 20. [NOT SATISFIED] SOME OF THE FFE LEADERS ARE
 INCOMPLETE (STOPPING IN MIDAIR) ON THE ARCHITECTURAL
 PLANS A-2.2A AND A-2.2B (SOUTH ELEVATIONS).
  
 21. [NOT SATISFIED] UPDATE FDOT STANDARD INDEX NUMBERS
 ON THE SITE PLAN SHEETS AND ENGINEERING SHEETS TO
 CURRENT FDOT STANDARD PLAN NUMBERS.
  
 22. [NOT SATISFIED] SLOPE OF HANDICAP PARKING SPACE IS
 LIMITED TO 2% MAX IN ALL DIRECTIONS.
  
 23. [SATISFIED] JUSTIFY SIZE OF 18-INCH DIAMETER
 OUTFALL PIPE.
  
 24. [SATISFIED] PROVIDE SOURCE FOR THE SIZE AND
 MATERIAL OF THE 16? DIP STORM PIPE AT EXISTING CURB
 INLET BEING CORED FOR OUTFALL PIPE.
  
 25. [PATIALLY SATISFIED ? SPOT GRADE ON THE TOP OF CURB
 AT SOUTH END OF THE PARKING LOT AND AT WEST END OF THE
 HANDICAP ACCESS AISLE] CLARIFY LOCATION OF PROPOSED
 SPOT GRADES. SOME APPEAR TO BE FOR TOP OF CURB.
  
 26. [NOT SATISFIED] SHOW THE RAISED CURBING LANDSCAPE
 ISLANDS ON THE WEST SIDE OF TAMARIND AVE.
  
 27. SHEET C2.3 GEOMETRIC, SIGNING AND STRIPING PLAN:
 A. [NOT SATISFIED] TYPE D CURB CALLED OUT AT NORTH END
 AND AT EAST SIDE OF PARKING LOT. THIS CURBING IS NOT
 SHOWN ON THE SITE PLAN OR PGD PLAN. ADDITIONAL COMMENT:
 SITE PLAN FOR SITE A NOT INCLUDED WITH THE 7-19-2022
 SUBMITTAL (SITE PLAN FOR SITE F WAS PROVIDED).
 B. [SATISFIED] SHOULD STOP BAR AT PARKING LOT EXIST BE
 MOVED BACK FROM BACK OF SIDEWALK?
 C. [SATISFIED] REMOVE OUTLINED STOP BAR, LANE DIVIDER
 STRIPE AND DIRECTIONAL ARROWS FROM PARKING LOT IF NOT
 APPLICABLE. OTHERWISE PROVIDE CALLOUTS FOR THESE ITEMS.
 D. [PARTIALLY SATISFIED ? SEE NEW COMMENTS BELOW]
 PROVIDE STRIPING PLAN (INCLUDING BLUE RPM FOR FIRE
 HYDRANT) FOR MILLED AND RESURFACING AREAS.
 E. [SATISFIED] SHOW EXISTING STOP SIGN FOR 21ST ST.
 F. [SATISFIED] REMOVE REFERENCE TO CITY OF RIVIERA
 BEACH LAND DEVELOPMENT CODE IN NOTES.
 G. [SATISFIED] PROVIDE REFERENCE TO THE CWPB TYPICAL 90
 DEGREE PARKING STALL DETAIL ON SHEET C3.1.
 H. [PARTIALLY SATISFIED] PROVIDE SIGN AND STRIPING FOR
 TURNAROUND SPACE. ADDITIONAL COMMENT ? IS A NO PARKING
 SIGN NEEDED?
  
 28. [NOT SATISFIED ? SHEET C3.2 WAS NOT INCLUDED IN THE
 7-19-2022 SUBMITTAL] SECTION A (SHEET C3.2):
 A. VALLEY GUTTER SHOWN.
 B. PROVIDE DIMENSION FROM PROPERTY LINE TO FACE OF
 BUILDING.
 C. SHOW PATIOS. PROVIDE TOP OF SLAB ELEVATION AND
 DIMENSION.
 D. ALTHOUGH SECTION IS NTS, THE FFE ELEVATION IS SHOWN
 BETWEEN ELEVATION GRID LINES 30 AND 32 FT NAVD.
 E. ADD THE STREET NAME FOR THE PUBLIC R/W.
  
 29. [NOT SATISFIED ? SHEET C3.2 WAS NOT INCLUDED IN THE
 7-19-2022 SUBMITTAL] SECTION B (SHEET C3.2)
 A. VALLEY GUTTER SHOWN
 B. SHOW LOCATION OF BUILDING AND PROPOSED FINISHED
 FLOOR ELEVATION. PROVIDE DISTANCE FROM PROPERTY LINE TO
 FACE OF BUILDING.
 C. ADD THE STREET NAME FOR THE PUBLIC R/W.
  
 30. [NOT SATISFIED ? SHEET C3.2 WAS NOT INCLUDED IN THE
 7-19-2022 SUBMITTAL] SECTION C (SHEET C3.2)
 A. LABEL PROPERTY LINE.
 B. TYPE 'D' CURB SHOWN ON SECTION BUT NOT ON PGD PLAN.
 C. EXTEND SECTION TO FACE OF BUILDING. SHOW GRADE
 BREAKS AND DISTANCES TO GRADE BREAKS.
 D. SHOW PROPSOED FENCE.
  
 31. [NOT SATISFIED ? SHEET C3.2 WAS NOT INCLUDED IN THE
 7-19-2022 SUBMITTAL] SECTION D (SHEET C3.2)
 A. VALLEY GUTTER SHOWN.
 B. MOVE SECTION TO PROPOSED DRIVEWAY LOCATION. CALLOUT
 NEW SIDEWALK AND CURBING.
 C. ADD THE STREET NAME FOR THE PUBLIC R/W.
  
 32. [NOT SATISFIED ? SHEET C3.2 WAS NOT INCLUDED IN THE
 7-19-2022 SUBMITTAL] PROVIDE A SECTION FROM CENTERLINE
 OF 21ST STREET TO SOUTH FACE OF BUILDING A. LABEL R/W;
 SHOW GRADE BREAKS, DIMENSIONS FROM THE PROPERTY LINE,
 ETC.
  
 33. [NOT SATISFIED ? SHEET C3.2 WAS NOT INCLUDED IN THE
 7-19-2022 SUBMITTAL] PROVIDE TYPICAL SECTION FROM NORTH
 FACE OF BUILDING A TO SOUTH FACE OF BUILDING B.
  
 34. [SATISFIED] WHAT IS THE LINE SHOWN ON THE
 ENGINEERING PLANS APPROXIMATELY 20 FEET SOUTH OF THE
 PROPOSED SANITARY MH#2? IS IT A SEWER LATERAL?
  
 35. [PARTIALLY SATISFIED] SHEET C4.1 EROSION CONTROL
 PLAN (THESE CAN BE ADDRESSED WITH THE ENGINEERING
 PERMIT SUBMITTAL):
 A. MOVE CONSTRUCTION ACCESS HATCHING OUTSIDE OF THE
 R/W.
 B. PROVIDE ALTERNATIVE TO HAY BALES FOR INLET
 PROTECTION.
 C. CALLOUT WHICH INLETS ARE TO BE PROTECTED.
  
 36. [SATISFIED] SITE PLAN SHEET SP-1 CALLS OUT DETAIL 4
 ON SHEET SP-3 BUT THERE IS NOT A DETAIL 4 ON SHEET
 SP-3.
  
 NEW COMMENTS(7/19/22 SUBMITTAL):
  
 37. PROVIDE 20 LF OF DOUBLE YELLOW STRIPING ON 21ST ST.
  
 38. BIKE LANE STRIPING TO BE PER THE CITY STANDARD
 DETAILS AND THE MUTCD. PROPERLY SHOW THE LOCATIONS FOR
 THESE MARKINGS.
  
 39. SHARE THE ROAD SIGNS APPEAR TO BE LOCATED IN THE
 ROAD.
  
 40. LABEL BUILDING A AND BUILDING B ON THE CIVIL PLANS.
  
 41. VERIFY SPOT GRADE OF 29.4 AT END OF THE ADA ACCESS
 AISLE IN THE PARKING LOT.
  
 42, SLOPE OF DRIVEWAY FROM BACK OF SIDEWALK TO
 STRUCTURE S-102 APPEARS TO BE OVER 16%. CHECK WITH THE
 SANITATION DEPARTMENT ON THE ALLOWABLE SLOPES FOR THE
 TRASH TRUCKS TO DRIVE ON.
  
 43. CALLOUT THE FDOT CURB RAMP NUMBER FOR THE MIDBLOCK
 CROSS WALK (BOTH SIDES OF TAMARIND).
  
 44. PROVIDE A YARD DRAIN TO COLLECT RUNOFF BETWEEN THE
 BUILDINGS BEFORE IT FLOWS OVER THE SIDEWALK.
  
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER