2022-04-26 16:19:36THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 3/24/2022 SUBMITTAL:
  
 1. [SATISFIED] CONFIRM PROJECT ADDRESS (2122 VS. 2212
 N. TAMARIND AVE)
  
 2. [SATISFIED] REMOVE REFERENCES TO VOW (VILLAGE OF
 WELLINGTON?) ON COVER.
  
 3. [SATISFIED] CONCEPTUAL ENGINEERING PLAN IS CONFUSING
 WITH EXISTING FEATURES SHOWN AND NOT SCREENED.
  
 4. [SATISFIED] RELOCATE DRAINAGE SYSTEM FROM UNDER
 STAIRS.
  
 5. [PARTIALLY SATISFIED] PROVIDE FLOW ARROWS SHOWING
 DIRECTION OF SURFACE RUNOFF. ADDITIONAL COMMENT:
 PROVIDE FLOW ARROWS AROUND ALL SIDES OF THE BUILDINGS
 AND BETWEEN THE BUILDINGS.
  
 6. [PARTIALLY SATISFIED ? SEE ADDITIONAL COMMENTS UNDER
 NEW COMMENTS BELOW.] PROVIDE AT LEAST TWO CROSS
 SECTIONS FROM EACH R/W CENTERLINE TO THE FACE OF
 BUILDING(S) AND/OR TO PARKING LOT; AND CROSS SECTIONS
 FROM EAST PROPERTY LINE TO FACE OF BUILDINGS. LABEL
 STREETS, PROPERTY LINES, SURFACE FEATURES AND GENERAL
 SURFACE SLOPES. PROVIDE DIMENSIONS FOR CURBS/CURB AND
 GUTTER, SIDEWALKS AND DISTANCE FROM PROPERTY LINE TO
 FACE OF BUILDING. INCLUDE PROPOSED PARALLEL PARKING
 AREAS.
  
 7. [SATISFIED] PROVIDE ADA TRUNCATED MAT ON THE EAST
 SIDE OF THE DRIVEWAY.
  
 8. [PARTIALLY SATISFIED] SHOW MILL AND RESURFACING
 LIMITS WITHIN THE STREETS. ADDITIONAL COMMENT: EXTEND
 MILL AND RESURFACING LIMITS FOR THE EXISTING SEWER
 LATERALS THAT WILL BE REMOVED AND CAPPED AT THE MAIN.
  
 9. [PARTIALLY SATISFIED] IDENTIFY ON THE CONCEPTUAL
 ENGINEERING PLAN WHERE THE SPECIAL TYPE ?F? CURB AND
 GUTTER WILL BE CONSTRUCTED. REDRAW THE DETAIL IN ACAD
 AND PROVIDE ENGLISH UNITS. ADDITIONAL COMMENT: SHOW IN
 THE PGD PLAN WHERE THIS CURB WILL BE CONSTRUCTED.
  
 10. [SATISFIED] LABEL WHERE THE DRAINAGE CONTROL
 STRUCTURE WILL BE LOCATED AND PROVIDE A DETAIL OF THE
 STRUCTURE. NOTE THE CITY DOES NOT ALLOW THE USE OF
 BLEEDERS WITH EXFILTRATION TRENCHES.
  
 11. [NOT SATISFIED] PROVIDE HATCHING PATTERNS FOR
 SIDEWALKS TO REMAIN AND FOR NEW/REPLACEMENT SIDEWALKS.
 ADDITIONAL COMMENT: SIDEWALK WILL BE REPLACED AT
 PROPOSED DRIVEWAY LOCATION AND FOR MIDBLOCK CROSSWALK.
  
 12. [NOT SATISFIED] EXPLAIN HOW ACCESS FROM THE
 BUILDINGS TO THE PARKING LOT WILL BE PROVIDED FOR THE 3
 FT+/- GRADE DIFFERENTIAL. ADDITIONAL COMMENT: PROVIDE
 ADDITIONAL PROPOSED GRADES FOR SIDEWALKS ON THE EAST
 SIDES OF THE BUILDING. THE PROPOSED ELEVATION OF THE
 WEST END OF THE HANDICAP PARKING ACCESS AISLE IS 30.5
 FEET NAVD. THE FFE ELEVATION OF THE BUILDINGS IS
 PROPOSED TO BE 29.5 FT NAVD.
  
 13. [SATISFIED] PER FIGURE XV-2: GENERAL PARKING
 DIMENSIONS IN SECTION 94-485 OF THE CITY?S CODE OF
 ORDINANCES, THE CURB LENGTH OF PARALLEL PARKING SPACES
 IS 22 FEET. THE SITE PLAN SHOWS 25 FEET AND GAPS IN THE
 PARKING SPACES ON TAMARIND AVE.
  
 14. [SATISFIUED] CONSIDER ANGLING THE CURBING AT EACH
 END OF PROPOSED PARALLEL PARKING SPACES TO FACILITATE
 ACCESS TO AND FROM THE END SPACES.
  
 15. [NOT SATISFIED] THE CITY?S OFFICIAL VERTICAL DATUM
 IS NGVD1929. THE CITY HAS ALLOWED THE USE OF NAVD1988
 AS LONG AS THE CONVERSION EQUATION TO NGVD1929 AT THE
 PROJECT LOCATION IS PROVIDED. PROVIDE THE NAVD1988 TO
 NGVD1929 CONVERSION EQUATION ON THE SURVEY.
  
 16. [SATISFIED - RESPONSE INDICATED NO NEW GUTTERS.]
 LABEL ANY NEW GUTTER ON 21ST ST.
  
 17. [NOT SATISFIED] SIDEWALK EASEMENT WILL BE NEEDED
 FOR 22ND ST. SIDEWALK.
  
 18. [SATISFIED] CONSIDER LOW IMPACT DEVELOPMENT
 DRAINAGE SYSTEMS IN LIEU OF EXFILTRATION TRENCHES.
  
 19. [NOT SATISFIED] SHOW UTILITIES ON THE LANDSCAPE
 PLANS.
  
  
 NEW COMMENTS:
  
 20. SOME OF THE FFE LEADERS ARE INCOMPLETE (STOPPING IN
 MIDAIR) ON THE ARCHITECTURAL PLANS A-2.1 AND A-2.2.
  
 21. UPDATE FDOT STANDARD INDEX NUMBERS ON THE SITE PLAN
 SHEETS AND ENGINEERING SHEETS TO CURRENT FDOT STANDARD
 PLAN NUMBERS.
  
 22. SLOPE OF HANDICAP PARKING SPACE IS LIMITED TO 2%
 MAX IN ALL DIRECTIONS.
  
 23. JUSTIFY SIZE OF 18? DIAMETER OUTFALL PIPE.
  
 24. PROVIDE SOURCE FOR THE SIZE AND MATERIAL OF THE 16?
 DIP STORM PIPE AT EXISTING CURB INLET BEING CORED FOR
 OUTFALL PIPE.
  
 25. CLARIFY LOCATION OF PROPOSED SPOT GRADES. SOME
 APPEAR TO BE FOR TOP OF CURB.
  
 26. SHOW THE RAISED CURBING LANDSCAPE ISLANDS ON THE
 WEST SIDE OF TAMARIND AVE.
  
 27. SHEET C2.3 GEOMETRIC, SIGNING AND STRIPING PLAN:
 A. TYPE ?D? CURB CALLED OUT AT NORTH END AND AT EAST
 SIDE OF PARKING LOT. THIS CURBING IS NOT SHOWN ON THE
 SITE PLAN OR PGD PLAN.
 B. SHOULD STOP BAR AT PARKING LOT EXIST BE MOVED BACK
 FROM BACK OF SIDEWALK?
 C. REMOVE OUTLINED STOP BAR, LANE DIVIDER STRIPE AND
 DIRECTIONAL ARROWS FROM PARKING LOT IF NOT APPLICABLE.
 OTHERWISE PROVIDE CALLOUTS FOR THESE ITEMS.
 D. PROVIDE STRIPING PLAN (INCLUDING BLUE RPM FOR FIRE
 HYDRANT) FOR MILLED AND RESURFACING AREAS.
 E. SHOW EXISTING STOP SIGN FOR 21ST ST.
 F. REMOVE REFERENCE TO CITY OF RIVIERA BEACH LAND
 DEVELOPMENT CODE IN NOTES.
 G. PROVIDE REFERENCE TO THE CWPB TYPICAL 90 DEGREE
 PARKING STALL DETAIL ON SHEET C3.1.
 H. PROVIDE SIGN AND STRIPING FOR TURNAROUND SPACE
  
 28. SECTION A (SHEET C3.2):
 A. VALLEY GUTTER SHOWN.
 B. PROVIDE DIMENSION FROM PROPERTY LINE TO FACE OF
 BUILDING.
 C. SHOW PATIOS. PROVIDE TOP OF SLAB ELEVATION AND
 DIMENSION.
 D. ALTHOUGH SECTION IS NTS, THE FFE ELEVATION IS SHOWN
 BETWEEN ELEVATION GRID LINES 30 AND 32 FT NAVD.
 E. ADD THE STREET NAME FOR THE PUBLIC R/W.
  
 29. SECTION B (SHEET C3.2)
 A. VALLEY GUTTER SHOWN
 B. SHOW LOCATION OF BUILDING AND PROPOSED FINISHED
 FLOOR ELEVATION. PROVIDE DISTANCE FROM PROPERTY LINE TO
 FACE OF BUILDING.
 C. ADD THE STREET NAME FOR THE PUBLIC R/W.
  
 30. SECTION C (SHEET C3.2)
 A. LABEL PROPERTY LINE.
 B. TYPE 'D' CURB SHOWN ON SECTION BUT NOT ON PGD PLAN.
 C. EXTEND SECTION TO FACE OF BUILDING. SHOW GRADE
 BREAKS AND DISTANCES TO GRADE BREAKS.
 D. SHOW PROPSOED FENCE.
  
 31. SECTION D (SHEET C3.2)
 A. VALLEY GUTTER SHOWN.
 B. MOVE SECTION TO PROPOSED DRIVEWAY LOCATION. CALLOUT
 NEW SIDEWALK AND CURBING.
 C. ADD THE STREET NAME FOR THE PUBLIC R/W.
  
 32. PROVIDE A SECTION FROM CENTERLINE OF 21ST STREET TO
 SOUTH FACE OF BUILDING ?A?. LABEL R/W; SHOW GRADE
 BREAKS, DIMENSIONS FROM THE PROPERTY LINE, ETC.
  
 33. PROVIDE TYPICAL SECTION FROM NORTH FACE OF BUILDING
 A TO SOUTH FACE OF BUILDING B.
  
 34. WHAT IS THE LINE SHOWN ON THE ENGINEERING PLANS
 APPROXIMATELY 20 FEET SOUTH OF THE PROPOSED SANITARY
 MH#2? IS IT A SEWER LATERAL?
  
 35. SHEET C4.1 EROSION CONTROL PLAN (THESE CAN BE
 ADDRESSED WITH THE ENGINEERING PERMIT SUBMITTAL):
 A. MOVE CONSTRUCTION ACCESS HATCHING OUTSIDE OF THE
 R/W.
 B. PROVIDE ALTERNATIVE TO HAY BALES FOR INLET
 PROTECTION.
 C. CALLOUT WHICH INLETS ARE TO BE PROTECTED.
  
 36. SITE PLAN SHEET SP-1 CALLS OUT DETAIL 4 ON SHEET
 SP-3 BUT THERE IS NOT A DETAIL 4 ON SHEET SP-3.
  
 TRACY WARD, PE