Plan Review Notes
Plan Review Notes For Project Z21120019
Project Number Z21120019
Review Stop PU
Sequence Number 1
Notes
Date Text
2022-01-05 16:52:58-SHOW EXISTING UTILITIES ON TAMARIND.
 -SHOW EXISTING WATER SERVICES OFF OF 22ND ST, ADD NOTE
 TO CUT AND CAP UNUSED SERVICES AT THE MAIN.
 -SHOW PROFILE OF 4? CONNECTION FROM TAP TO POINT OF
 SERVICE.
 -PROVIDE LEVEL OF SERVICE CALCULATIONS.
 -REPLACE/LINE EXISTING LATERALS AS REQUIRED. PROVIDE
 POST CCTV FOOTAGE.
 -ADD NOTE THAT THIS IS WITHIN LIFT STATION 21 SERVICE
 BOUNDARY.
 -LABEL EASEMENT/S.
 -WE NEED TO SEE LEVEL OF SERVICE CALCS TO DETERMINE THE
 IMPACT TO THE EXISTING COLLECTION SYSTEM AND LIFT
 STATION.
 -FOR STORMWATER STRUCTURES CALL OUT STATIONING AND
 HORIZONTAL SEPARATION BETWEEN UTILITIES.
  
 CONTACT MIKE TECHNOW 561-494-1047 OR [email protected]
 WITH ANY QUESTIONS.
  