Plan Review Notes
Plan Review Notes For Project Z21120018
Project Number Z21120018
Review Stop STORM
Sequence Number 4
Notes
Date Text
2022-12-13 10:46:28CONDITIONS FOR SITE PLAN APPROVAL:
  
 1. SHOW OUTLINE OF EXFILTRATION TRENCHES ON THE
 LANDSCAPE PLANS. CONFIRM THE PROPOSED LANDSCAPING WILL
 NOT INTERFERE WITH THE EXFILTRATION TRENCHES.
 2. CONFIRM THE CONSTRUCTABILITY OF THE 6 FEET WIDE
 EXFILTRATION TRENCH EAST OF BUILDING A BETWEEN THE
 EXISTING RETAINING WALL AND THE FOOTER FOR THE
 BUILDING. FUTURE MAINTENANCE (I.E. REPLACEMENT) OF THE
 EXFILTRATION TRENCH NEEDS TO BE CONSIDERED IF THE
 TRENCH WILL BE LOCATED UNDER ANY BUILDING OVERHANGS.
 3. SHOW AND LABEL (SIZE AND MATERIAL) ALL EXISTING
 UTILITIES IN THE R/W.
 4. CONFIRM THE EXISTING DRAINAGE STRUCTURE TO BE
 CONNECTED TO IS NOT A BUBBLE-UP STRUCTURE. SHOW
 EXISTING DRAINAGE PIPE CONNECTIONS. PROVIDE PROPOSED
 INVERT ELEVATION FOR PIPE CONNECTION TO EXISTING INLET.
 PROVIDE THE BOTTOM ELEVATION INVERT ELEVATION FOR THE
 EXISTING PIPE(S) CONNECTED TO THE INLET.
 5. CALLOUT THE FDOT CURB RAMP STYLE FOR THE MIDBLOCK
 CROSS WALK ON BOTH SIDES OF TAMARIND AVE.
 6. COORDINATE CURBING CALLOUTS ON SHEET C2.3 WITH THE
 CROSS SECTIONS AND THE GRADES ON SHEET C2.1.
 7. COORDINATE THE EAST-WEST LOCATION OF THE DRAINAGE
 STRUCTURES IN THE PARKING LOT WITH THE SECTION A.
 8. PROVIDE SIGNING AND STRIPING FOR THE MIDBLOCK CROSS
 WALK. LABEL THE FDOT CURB RAMP STYLE.
 9. COORDINATE DETAILS FOR THE CONTROL STRUCTURES WITH
 THE DRAINAGE PLAN.
 10. PROVIDE A CROSS SECTION AT THE PROPOSED DRIVEWAY
 FROM THE CNETERLINE OF THE R/W TO 5 FEET PAST THE HIGH
 POINT OF THE DRIVEWAY. SHOW BREAK POINTS, SURFACE
 FEATURES, R/W LINE. PROVIDE DIMENSIONS FROM THE R/W TO
 THE DRIVEWAY HIGH POINT AND OTHER BREAK POINTS, TO THE
 BACK OF CURB/EDGE OF PAVEMENT, TO THE R/W CENTERLINE.
 SHOW AND DIMENSION WHERE THE SIDEWALK WILL CROSS THE
 DRIVEWAY.
  
  
 THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 11/4/2022 SUBMITTAL. PREVIOUSLY SATISFIED COMMENTS ARE
 NOT INCLUDED.
  
 5. [SATISFIED - SEE COMMENTS UNDER NEW COMMENTS BELOW]
 PROVIDE CROSS SECTIONS FROM:
 A. FACE OF BUILDING TO TAMARIND AVE CENTERLINE
 B. FACE OF BUILDING TO GRANT ST CENTERLINE
 C. FACE OF BUILDING TO 19TH ST CENTERLINE
 D. AT PROPOSED DRIVEWAY
 E. FROM EAST PROPERTY LINE TO FACE OF BUILDING ?A?
 F. FROM EAST PROPERTY LINE TO FACE OF BUILDING ?B?
  
 LABEL STREETS, PROPERTY LINES, SURFACE FEATURES AND
 GENERAL SURFACE SLOPES. PROVIDE DIMENSIONS FOR
 CURBS/CURB AND GUTTER, SIDEWALKS AND DISTANCE FROM
 PROPERTY LINE TO FACE OF BUILDING. INCLUDE PROPOSED
 PARALLEL PARKING AREAS.
  
  
  
  
 9. [SATISFIED - NO NEW SIDEWALKS PER PREVIOUS RESPONSE]
 PROVIDE HATCHING PATTERNS FOR SIDEWALKS TO REMAIN AND
 FOR NEW/REPLACEMENT SIDEWALKS. ADDITIONAL COMMENT:
 SECTION A ON SHEET C3.2 CALLS OUT NEW SIDEWALK ALONG
 19TH ST AND ALONG GRANT AVE. REVISE SECTION OR ADD
 PROPOSED SIDEWALK HATCH PATTERN ON SHEETS C2.1 AND C2.3
 AND HATCH THE PROPOSED SIDEWALKS.
  
 10. [SATISFIED] EXPLAIN HOW ACCESS FROM THE BUILDINGS
 TO THE PARKING LOT WILL BE PROVIDED FOR THE 4 FT+/-
 GRADE DIFFERENTIAL. ADDITIONAL COMMENT (REVISED FOR
 7/19 SUBMITTAL): PARKING LOT ELEVATION AT EAST END OF
 HANDICAP ACCESS AISLE IS APPROX.. 27.7 FT NAVD. THE
 LANDING AT THE BOTTOM OF 19.0 FT LONG RAMP IS AT
 ELEVATION 26.0 FT NAVD. RAMP SLOPE CALCULATES TO 8.9%,
 WHICH IS STEEPER THAN THE 1:12 ALLOWED FOR NEW
 CONSTRUCTION. THE SOUTH END OF THE 10 FT LONG RAMP IS
 47.5 FEET FROM THE NORTH CORNER OF THE BUILDING B. THE
 SOUTH SIDE OF THE DOOR FRAME OF THE APARTMENT ADJACENT
 TO THE RETAIL SPACE IS 47.08 FEET FROM THE NORTH CORNER
 OF BUILDING B SO THAT THE RAMP WILL BE IN FRONT OF THE
 DOOR.
  
  
 20. [PARTIALLY SATISFIED ??? SHOW OUTLINE OF
 EXFILTRATION TRENCHES.] SHOW UTILITIES ON THE LANDSCAPE
 PLANS.
  
  
  
 NEW COMMENTS:
  
 26. [NOT SATISFIED ??? ONSITE DRAINAGE SYSTEM MAY NOT
 CONNECT TO THE STRUCTURE IF THE DRAINAGE STRUCTURE IS
 NOT CONNECTED TO A POSITIVE DRAINAGE SYSTEM.] SHOW ALL
 EXISTING PIPE CONNECTIONS (WITH PIPE SIZES) TO THE
 EXISTING CURB INLET AND THE STRUCTURES THESE PIPES ARE
 CONNECTED TO.
  
 30. - 33 [NOT SATISFIED ? NOTE PREVIOUS SECTIONS WERE
 REPLACED WITH NEW SECTIONS ON THE 7/19 SUBMITTAL. THE
 COMMENTS BELOW ARE FOR THE NEW SECTIONS.
  
 30. SECTION A (SHEET C3.2):
 A. SECTION APPEARS TO CORRESPOND TO SECTION B SYMBOL ON
 SHEET C2.1.
 B. CHANGE LABEL OF GRANT AVE TO GRANT ST.
 C. SIDEWALKS ON GRANT ST AND 19TH ST APPEAR TO HAVE
 THICKENED EDGE AT BACK OF SIDEWALK. PROVIDE A DETAIL
 FOR THE SIDEWALK.
 D. DOOR AND WINDOW LAYOUT FOR BUILDINGS A AND B DO NOT
 MATCH THE ARCHITECTURAL ELEVATION DRAWINGS.
 E. CONFIRM THE GRADES PROVIDED FOR GRANT ST. THE EP IS
 SHOWN HIGHER THAN THE CENTERLINE.
  
 31. SECTION B (SHEET C3.2):
 A. [SATISFIED] SECTION APPEARS TO CORRESPOND TO SECTION
 A SYMBOL ON SHEET C2.1.
 B. [SATISFIED] VERIFY ELEVATION FOR EAST SIDE OF DRIVE
 AISLE (29.7).
 C. [SATISFIED] SIDEWALK ALONG TAMARIND AVE APPEARS TO
 HAVE A THICKENED EDGE.
 D. [NOT SATISFIED] CENTER OF DRIVE AISLE APPEARS TO BE
 LOW SPOT (INVERTED CROWN) BUT THE DRAINAGE STRUCTURES
 ON SHEET C2.1 ARE 14+ FEET FROM THE EAST EDGE OF THE
 PARKING LOT.
  
 32.[SATISFIED] SECTION C (SHEET C3.2):
 A. THIS SECTION DOESN???T APPEAR TO BE FOR THIS
 DEVELOPMENT. BUILDING A WIDTH IS CALLED OUT AS 132 FEET
 WHEREAS IN SECTION A THE BUILDING A WIDTH IS 88 FEET.
 B. PROVIDE A SECTION CORRESPONDING TO THE SECTION C
 SYMBOL ON SHEET C2.1.
  
 36. [NOT SATISFIED] ARCHITECTURAL NORTH AND SOUTH
 ELEVATIONS APPEAR TO BE MISLABELED ON SHEETS
 A-2.1/A2.2B AND SHEETS A-2.1A/A-2.2A.
  
 NEW COMMENTS ON 7/19/22 SUBMITTAL:
  
 37. [SATISFIED] PROVIDE A CROSS SECTION FROM THE CENTER
 OF THE PARKING LOT TO THE EAST FACE OF BUILDING,
 CENTERED ON THE RAMP FROM THE PARKING LOT TO THE FIRST
 FLOOR SIDEWALK. PROVIDE HORIZONTAL DIMENSIONS AND
 ELEVATIONS AT EACH GRADE BREAK.
  
 38.[SATISFIED[ LABEL BUILDING A AND BUILDING B ON THE
 CIVIL DRAWINGS.
  
 39. [NOT SATISFIED] LABEL THE EXISTING UTILITIES (PIPE
 SIZE AND MATERIAL) IN THE RIGHTS OF WAYS.
  
 40. [SATISFIED] HOW DOES ONE ACCESS BUILDING A FROM THE
 PARKING LOT? THERE DOESN?T APPEAR TO BE A SIDEWALK
 CONNECTION BETWEEN THE TWO BUILDINGS ON THE EAST SIDE
 OF THE BUILDINGS.
  
 41. [NOT SATISFIED] CALLOUT THE FDOT CURB RAMP STYLE
 FOR THE MIDBLOCK CROSS WALK ON BOTH SIDES OF TAMARIND
 AVE.
  
 42. [NOT SATISFIED] PROVIDE PROPOSED INVERT ELEVATION
 FOR PIPE CONNECTION TO EXISTING INLET. PROVIDE THE
 BOTTOM ELEVATION INVERT ELEVATION FOR THE EXISTING
 PIPE(S) CONNECTED TO THE INLET.
  
 43. [SATISFIED] SOUTH STAIRWELL OF BUILDING B APPEARS
 TO CONFLICT WITH THE WEST RETAINING WALL OF THE PARKING
 LOT.
  
 44. [SATISFIED] PROVIDE A YARD DRAIN AT WEST END OF THE
 AREA BETWEEN THE TWO BUILDINGS TO COLLECT RUNOFF BEFORE
 IT FLOWS OVER THE SIDEWALK.
  
 45. [SATISFIED ??? SUGGEST MOVING STRUCTURES S-101 AND
 S-102 SOUTHWARD] SLOPE OF PARKING LOT BETWEEN S-101 AND
 BACK OF SIDEWALK APPEARS TO BE CLOSE TO 9%.
  
 46. [PARTIALLY SATISFIED ??? DOUBLE PROPOSED SPOT
 GRADES PROVIDED FOR EAST EDGE OF PARKING LOT.] SHOW
 CURBING ALONG SOUTH AND EAST SIDES OF PARKING LOT ON
 THE CIVIL DRAWINGS. SHEET C2.3 CALLS OUT TYPE D CURB.
  
 46. [NOT SATISFIED] BIKE LANE STRIPING SHALL FOLLOW THE
 CITY STANDARD DETAILS AND THE MUTCD.
  
 47. [NOT SATISFIED] SIGNAGE AND STRIPING NEEDED FOR THE
 MID-BLOCK CROSS WALK.
  
 48. [NOT SATISFIED] REVIEW PIPE SIZES AND INVERT
 ELEVATIONS LISTED ON THE CONTROL STRUCTURE S-104
 DETAILS.
  
 49. [NOT SATISFIED] REVIEW PIPE MATERIAL LISTED ON THE
 CONTROL STRUCTURE S-102 DETAILS.
  
 50. [SATISFIED] MOVE CONSTRUCTION ACCESS AREA OUTSIDE
 OF THE ROAD RIGHT OF WAY.
  
 NEW COMMENT (11/4/2022 SUBMITTAL)
 51. CONFIRM THERE IS SUFFICIENT SPACE FOR THE 6-FOOT
 WIDE EXFILTRATION TRENCH BETWEEN THE EXISTING RETAINING
 WALL AND THE BUILDING A FOOTER AS WELL AS INSTALL THE
 PERIMETER LANDSCAPING.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  
  
  