Plan Review Notes
Plan Review Notes For Project Z21110014
Project Number Z21110014
Review Stop STORM
Sequence Number 1
Notes
Date Text
2022-01-03 08:06:151. WILL THE PROPOSED SIDEWALK BETWEEN THE PARKING LOT
 AND THE GENERATOR PAD AFFECT THE STORMWATER RUNOFF TO
 THE RETENTION AREA? WILL THE OVERLAND FLOW BE BLOCKED
 BY THE SIDEWALK?
  
 2. PROVIDE CROSS SECTIONS FOR THE GENERATOR PAD AND
 SIDEWALK TO SHOW THEIR RELATIONSHIP TO EXISTING GRADES.
  
 3. PROVIDE MINIMUM PAD ELEVATION FOR THE GENERATOR PAD.
 THE SITE IS LESS THAN 100 FEET FROM A SPECIAL FLOOD
 HAZARD AREA WITH BASE FLOOD ELEVATION OF 15 FT NAVD.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120