| 2022-02-25 09:25:20 | COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR, |
| | ENGINEERING SERVICES DEPT., 561-494-1098 |
| | [email protected] : |
| | |
| | PLEASE PROVIDE RESPONSES TO PREVIOUS REVIEW. |
| | |
| | COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE |
| | SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR |
| | [email protected]: |
| | |
| | -BACKFLOW ASSEMBLY LISTED ON IRRIGATION PLAN SAYS |
| | INDOOR INSTALLATION. INDOOR INSTALLATION IS NOT |
| | APPROVED IF IT IS A CONTAINMENT ASSEMBLY. |
| | |
| | -IF THE IRRIGATION BACKFLOW ASSEMBLY IS A CONTAINMENT |
| | DEVICE, THEN IT MUST BE RP TYPE INSTEAD OF PVB AND THE |
| | UPSTREAM PIPING MUST BE COMPLIANT TYPE INSTEAD OF PVC. |
| | |
| | -SURVEY SAYS THE BUILDING IS ENCROACHING IN 30 FOOT |
| | UTILITY EASEMENT. IF THE PROPOSED BUILDING CONSTRUCTION |
| | AREA WOULD ALSO ENCROACH IN THE EASEMENT, THEN |
| | IDENTIFY: UTILITIES IN EASEMENT, PURPOSE OF EASEMENT, |
| | AND APPROVAL OBTAINED TO BUILD IN EASEMENT. |
| | |
| | -VERIFY THAT TREE LOCATIONS ARE DISTANCED SUFFICIENTLY |
| | SO ROOTS WILL NOT DAMAGE METERED WATER SERVICES. CAN |
| | ALSO ADD ROOT BARRIERS AS NECESSARY. |
| | |
| | -WPB GIS INDICATES WATER MAIN IN ROAD IS NOT 2 INCH |
| | PVC. PLEASE UPDATE PLANS. |
| | |
| | -DID NOT RECEIVE WRITTEN RESPONSES FOR PRIOR REVIEW |
| | COMMENTS. ALSO SUBMIT WRITTEN RESPONSES FOR THE |
| | FOLLOWING: |
| | |
| | SUBMITTAL PACKAGE IS MISSING PROJECT NARRATIVE, |
| | JUSTIFICATION, AND SURVEY. |
| | |
| | PLANS DO NOT SHOW BLACK METAL FENCE AND GATES THAT ARE |
| | INSTALLED ALONG EASTERN SIDES OF PROPERTY. PLEASE |
| | UPDATE PLANS. |
| | |
| | METERED WATER SERVICE FOR PROPERTY DOES NOT HAVE AN |
| | ACTIVE USAGE ACCOUNT SETUP WITH CITY WPB UTILITY |
| | BILLING. APPLICANT WOULD NEED TO SET ONE UP AND PAY ALL |
| | APPLICABLE CHARGES, FEES, AND DEPOSITS BEFORE USING |
| | WATER SERVICE. |
| | |
| | BACKFLOW ASSEMBLY DOES NOT APPEAR TO BE INSTALLED FOR |
| | WATER SERVICE. APPLICANT WOULD NEED TO HAVE LICENSED |
| | PLUMBER INSTALL BEFORE WATER CAN BE USED. SHOW PROPOSED |
| | LOCATION ON PLANS. |
| | |
| | VERIFY EXISTING WATER AND SEWER INFRASTRUCTURE IS |
| | SUFFICIENT FOR PROPOSED IMPROVEMENTS. IF SERVICE |
| | UPGRADES ARE NEEDED, SUBMIT ENGINEERING PLAN SHOWING |
| | PROPOSED CHANGES. |
| | |
| | SOME OF THE LANDSCAPING TREES APPEAR TO BE PROPOSED IN |
| | LOCATIONS THAT ARE CURRENTLY HARDSCAPE. |
| | |
| | THERE ARE A FEW UTILITY POLES AT EAST PROPERTY LINE NOT |
| | SHOWN ON SITE PLAN. THE ONES AT TOWARD THE SOUTHEAST |
| | CORNER OF PROPERTY MAY CONFLICT WITH LANDSCAPING. |
| | PLEASE SHOW ON PLANS. |
| | |
| | ARE THERE ANY EXISTING OR PROPOSED FIRE SPRINKLERS FOR |
| | THE BUILDINGS? |
| | |
| |