2022-11-28 11:38:56THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 4-12-2022 SUBMITTAL:
  
 1. [SATISFIED] THE CITY'S OFFICIAL VERTICAL DATUM PER
 CITY CODE IS NGVD1929. THE CITY IS ALLOWING SURVEYS AND
 PLANS TO USE NAVD1988 PROVIDED THE CONVERSION EQUATION
 BETWEEN NAVD1988 AND NGVD1929 IS ALSO PROVIDED. LIST
 THE CONVERSION EQUATION TO NGVD1929 ON THE SURVEY AND
 ON THE ENGINEERING PLAN.
  
 2. [SATISFIED] CONSIDER RELOCATING THE PROPOSED STORM
 CHAMBERS OUTSIDE OF THE UTILITY EASEMENT.
  
 3. [SATISFIED] ARE THE OVERHEAD LINES WITHIN AN
 EASEMENT?
  
 4. [SATISFIED] OKEECHOBEE BLVD IS MAINTAINED BY FDOT.
 PROVIDE PERMIT FROM FDOT PRIOR TO ENGINEERING PERMIT
 ISSUANCE FOR WORK WITHIN THE R/W.
  
 5. [SATISFIED] AUSTRALIAN AVE IS MAINTAINED BY PALM
 BEACH COUNTY. PROVIDE PERMIT FROM THE COUNTY PRIOR TO
 ENGINEERING PERMIT ISSUANCE FOR WORK WITHIN THE R/W.
  
 6. [SATISFIED - FLOW ARROWS WERE REMOVED FROM THE
 CONCEPTUAL P&D PLAN. THE AMOUNT OF RUNOIFF FLOWING TO
 OKEECHOBEE BLVD SHALL BE MINIMIZED.] ARE FLOW ARROWS
 SHOWN CORRECTLY FOR DRIVE LANES GOING TOWARD OKEECHOBEE
 BLVD?
  
 7. INDICATE IF ALL OF THE STORAGE CHAMBERS WILL BE
 INTERCONNECTED TO BALANCE OUT THE RUNOFF TO THE SYSTEM
 AND, IF NOT ALL INTERCONNECTED, THE INDIVIDUAL STORAGE
 CHAMBER AREAS ARE APPROPRIATELY SIZED FOR THE RUNOFF
 EXPECTED TO DRAIN TO THEM.
  
 8. [SATISFIED] CONDITION ASSESSMENT PERFORMED ON THE
 EXISTING CMP STORM PIPE TO REMAIN TO DETERMINE IF THE
 STORM PIPES SHOULD BE REPLACED OR LINED.
  
  