| 2023-05-15 10:38:53 | PLEASE PROVIDE WRITTEN RESPONSE TO THE FOLLOWING: |
| | -SHEET C6.04: ADD ADDRESSES TO THE PROPERTIES ON THE |
| | WEST SIDE OF FLAGLER AS IT IS DIFFICULT TO DETERMINE |
| | THE LOCATION. ALSO ADD THE CURRENT STREET NAMES. |
| | -SHEET C6.04: THERE APPEARS TO BE A BACKFLOW ASSEMBLY |
| | PROPOSED IN THE MIDDLE OF A SIDEWALK. ENSURE BACKFLOW |
| | ASSEMBLY DOES NOT IMPEDE PEDESTRIAN TRAFFIC. |
| | -SHEET C6.04: CLEARLY LABEL PROPERTY LINE. ALSO CANNOT |
| | CLEARLY DISTINGUISH WHAT THE DASHED AND DOTTED LINES |
| | JUST EAST OF THE BACKFLOW ASSEMBLY ARE ??? PLEASE |
| | LABEL. |
| | -SHEET C6.06: THERE APPEARS TO BE MULTIPLE RIGHT OF WAY |
| | LINES. IS THAT AN ERROR, OR IS THE RIGHT OF WAY |
| | BOUNDARIES CHANGING? |
| | -SHEET C6.06: ON THE LABEL OF 3 INCH MASTER WATER |
| | METER, ADD WORDING ABOVE-GROUND AND REFERENCE WATER |
| | SERVICE STANDARD DETAIL WS3. THE RPPA CALLOUT SHOULD |
| | ALSO HAVE SIZE AND REFERENCE WS7. |
| | -SHEET C6.06: WPB UTILITIES RECOMMENDS DUAL/PARALLEL |
| | BACKFLOW ASSEMBLIES ON IMPORTANT DOMESTIC WATER |
| | SERVICES TO MINIMIZE WATER OUTAGES DURING BACKFLOW |
| | MAINTENANCE AND TESTING. CONSIDER ADDING ANOTHER RPPA |
| | FOR THE 3 INCH METER IF WATER OUTAGE WOULD BE |
| | PROBLEMATIC. |
| | -SHEET C6.06: WHY IS 3 INCH METER NOT PROPOSED IN 10 |
| | FOOT UTILITY EASEMENT? |
| | -SHEET C6.06: THERE SHOULD BE A CONTAINMENT FIRELINE |
| | BACKFLOW ASSEMBLY FURTHER UPSTREAM OF THE FIRELINE |
| | PIPING NEAR THE PROPERTY LINE, BUT SHOULD NOT BE IN AN |
| | EASEMENT. IF ADDING ADDITIONAL DCDA, BE AWARE OF THE |
| | ADDITIONAL PRESSURE REDUCTION. |
| | -SHEET C6.06: ADDITION DOWNSTREAM ISOLATION BACKFLOW |
| | ASSEMBLIES MAY BE REQUIRED. RECOMMEND VERIFYING AHEAD |
| | OF TIME IF REQUIRED FOR PLUMBING. |
| | -SHEET C6.010: ADD WPB WATER SERVICE STANDARD DETAILS |
| | FOR LARGE DOMESTIC BACKFLOW ASSEMBLY, LARGE |
| | ABOVE-GROUND METER, AND DOMESTIC SERVICE LOCATION. ADD |
| | ADDITIONAL SHEET IF NEEDED. |
| | RESPECTFULLY, |
| | MARK HURLEY [email protected] |
| |