2022-09-23 13:40:10PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING.
 -PRIOR REVIEW COMMENT: PROPOSED WATER METERS AND
 BACKFLOW ASSEMBLIES NEED TO BE ADJACENT THE WESTERN
 PROPERTY LINE AND NOT FAR ON INTERIOR OF PROPERTY. ANY
 INTERIOR LOOPED SYSTEM WOULD BE PLUMBING AND CAN BE
 MASTER METERED AS NEEDED. RESPONSE LETTER STATED NOTED,
 BUT UTILITY PLANS SUCH AS SHEET C5.06 HAVE NOT BEEN
 REVISED. THIS WOULD ALSO AFFECT FIRE SERVICES AND
 HYDRANTS. IF NEED CLARIFICATION CAN CONTACT
 [email protected].
 -C5.01: INVERTS SAY PVC BUT CALLOUT HAS VCP.
 -C3.05 AND C3.09: LABEL ANY UTILITY EASEMENTS.
 -C3.01: CALLOUT SAYS FORCEMAIN BUT SEEMS TO BE GRAVITY
 SEWER.
 -C3.01: THERE IS A STREETLIGHT IN DRIVEWAY EXIT.
 -C3.01: IS A DO NOT ENTER SIGN NEEDED AT DRIVEWAY EXIT?
 -C3.03: 10 FOOT CONCRETE SIDEWALK SEEMS TO ABRUPTLY
 END. CANNOT TELL WHAT MATERIAL THE GRAY SHADED AREA IS.
 PLEASE LABEL BETTER, ADD TO LEGEND, OR ADD REFERENCE TO
 OTHER SHEET SHOWING MORE DETAIL.
 -C3.03: IS A BUILDING STRUCTURE PROPOSED OVER SANITARY
 SEWER MAIN?
 -C3.03: SHOULD FORCEMAIN CALLOUTS BE GRAVITY INSTEAD?
 -C3.03: SHOWS SOME WATER MAINS, BUT THOUGHT THEY WERE
 BEING REMOVED.
 -PLEASE SHOW MORE CLEARLY ON DEMO PLANS THE LIMITS OF
 THE WATER MAIN REMOVAL.
 -C3.04: THERE IS A STORM STRUCTURE IN A SEATWALL.
 -C3.05: FORCE MAIN SHOWING GOING INTO WATERWAY. PLEASE
 VERIFY IF THAT IS CORRECT.
 -C3.05: THERE ARE SOME LIGHTS IN CLOSE PROXIMITY TO
 WATER AND SEWER MAINS. PLEASE MAKE SURE ANY PROPOSED
 LIGHT POLES ARE AT LEAST 5 HORIZONTAL FEET AWAY FROM
 WATER AND SEWER MAINS.
 -C3.06: TENNIS COURT IS ENCROACHING INTO UTILITY
 EASEMENT.
 -C5.02: CALLOUT UTILITY EASEMENTS.
 -C5.01 AND C5.03: UTILITIES ARE NOT SHOWN IN THE GREY
 AREA. WHY?
 -C5.04: CANNOT INSTALL A BACKFLOW ASSEMBLY IN A
 SIDEWALK.
 -C5.04: RPPA LEADER LINE IS POINTED TO VALVE SYMBOL.
 PLEASE UPDATE.
 -SHOW METER BOXES ON UTILITY PLANS AND MAKE SURE METER
 SIZE IS LABELED.
 -C5.05: WHAT TYPE OF 20 FOOT EASEMENT IS RUNNING ACROSS
 THE WATERWAY?
 -CITY SEWER LATERALS ARE TYPICALLY MINIMUM 6 INCH SIZE.
 -C5.07: SANITARY DRAIN SEEMS TO BE LOCATED IN A
 DUMPSTER AREA. THIS IS NOT BE ALLOWED IF STORMWATER
 WOULD GO INTO IT, AND MAY ALSO NOT BE ALLOWED
 OTHERWISE.
 -ON LANDSCAPING PLANS SUCH AS L3.02, PLEASE LABEL
 STREETS AND SIDE STREETS.
 -WILL ANY AUXILIARY WATER SUPPLIES BE CONNECTED TO
 PRIVATE FIRE SYSTEMS?