| Date |
Text |
| 2022-09-23 13:40:10 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING. |
| | -PRIOR REVIEW COMMENT: PROPOSED WATER METERS AND |
| | BACKFLOW ASSEMBLIES NEED TO BE ADJACENT THE WESTERN |
| | PROPERTY LINE AND NOT FAR ON INTERIOR OF PROPERTY. ANY |
| | INTERIOR LOOPED SYSTEM WOULD BE PLUMBING AND CAN BE |
| | MASTER METERED AS NEEDED. RESPONSE LETTER STATED NOTED, |
| | BUT UTILITY PLANS SUCH AS SHEET C5.06 HAVE NOT BEEN |
| | REVISED. THIS WOULD ALSO AFFECT FIRE SERVICES AND |
| | HYDRANTS. IF NEED CLARIFICATION CAN CONTACT |
| | [email protected]. |
| | -C5.01: INVERTS SAY PVC BUT CALLOUT HAS VCP. |
| | -C3.05 AND C3.09: LABEL ANY UTILITY EASEMENTS. |
| | -C3.01: CALLOUT SAYS FORCEMAIN BUT SEEMS TO BE GRAVITY |
| | SEWER. |
| | -C3.01: THERE IS A STREETLIGHT IN DRIVEWAY EXIT. |
| | -C3.01: IS A DO NOT ENTER SIGN NEEDED AT DRIVEWAY EXIT? |
| | -C3.03: 10 FOOT CONCRETE SIDEWALK SEEMS TO ABRUPTLY |
| | END. CANNOT TELL WHAT MATERIAL THE GRAY SHADED AREA IS. |
| | PLEASE LABEL BETTER, ADD TO LEGEND, OR ADD REFERENCE TO |
| | OTHER SHEET SHOWING MORE DETAIL. |
| | -C3.03: IS A BUILDING STRUCTURE PROPOSED OVER SANITARY |
| | SEWER MAIN? |
| | -C3.03: SHOULD FORCEMAIN CALLOUTS BE GRAVITY INSTEAD? |
| | -C3.03: SHOWS SOME WATER MAINS, BUT THOUGHT THEY WERE |
| | BEING REMOVED. |
| | -PLEASE SHOW MORE CLEARLY ON DEMO PLANS THE LIMITS OF |
| | THE WATER MAIN REMOVAL. |
| | -C3.04: THERE IS A STORM STRUCTURE IN A SEATWALL. |
| | -C3.05: FORCE MAIN SHOWING GOING INTO WATERWAY. PLEASE |
| | VERIFY IF THAT IS CORRECT. |
| | -C3.05: THERE ARE SOME LIGHTS IN CLOSE PROXIMITY TO |
| | WATER AND SEWER MAINS. PLEASE MAKE SURE ANY PROPOSED |
| | LIGHT POLES ARE AT LEAST 5 HORIZONTAL FEET AWAY FROM |
| | WATER AND SEWER MAINS. |
| | -C3.06: TENNIS COURT IS ENCROACHING INTO UTILITY |
| | EASEMENT. |
| | -C5.02: CALLOUT UTILITY EASEMENTS. |
| | -C5.01 AND C5.03: UTILITIES ARE NOT SHOWN IN THE GREY |
| | AREA. WHY? |
| | -C5.04: CANNOT INSTALL A BACKFLOW ASSEMBLY IN A |
| | SIDEWALK. |
| | -C5.04: RPPA LEADER LINE IS POINTED TO VALVE SYMBOL. |
| | PLEASE UPDATE. |
| | -SHOW METER BOXES ON UTILITY PLANS AND MAKE SURE METER |
| | SIZE IS LABELED. |
| | -C5.05: WHAT TYPE OF 20 FOOT EASEMENT IS RUNNING ACROSS |
| | THE WATERWAY? |
| | -CITY SEWER LATERALS ARE TYPICALLY MINIMUM 6 INCH SIZE. |
| | -C5.07: SANITARY DRAIN SEEMS TO BE LOCATED IN A |
| | DUMPSTER AREA. THIS IS NOT BE ALLOWED IF STORMWATER |
| | WOULD GO INTO IT, AND MAY ALSO NOT BE ALLOWED |
| | OTHERWISE. |
| | -ON LANDSCAPING PLANS SUCH AS L3.02, PLEASE LABEL |
| | STREETS AND SIDE STREETS. |
| | -WILL ANY AUXILIARY WATER SUPPLIES BE CONNECTED TO |
| | PRIVATE FIRE SYSTEMS? |
| | RESPECTFULLY, |
| | MARK HURLEY [email protected] |
| |