| 2022-10-13 17:06:05 | CASE NO. 1895 - SEPTEMBER 21, 2022 RESUBMITTAL |
| | NORTHWOOD COMMONS - NMUD ANCHOR SITE |
| | BROADWAY & 24TH STREET |
| | |
| | - CONTACT ERIC SCHNEIDER @ (561) 822-1446, |
| | [email protected] |
| | |
| | - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN |
| | WRITTEN FORMAT. |
| | |
| | - WHEN RESUBMITTING, PLEASE PROVIDE THREE (3) PAPER |
| | COPIES AND AN ELECTRONIC COPY IN .PDF AND .PNG FORMAT |
| | OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE |
| | RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS |
| | TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL |
| | COMMENTS. |
| | |
| | - ONCE THE COMMENTS ARE RESUBMITTED AND DEEMED |
| | SUFFICIENTLY ADDRESSED, THE CASE WILL BE SCHEDULED FOR |
| | THE NEXT AVAILABLE PLANNING BOARD MEETING. |
| | |
| | - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT |
| | RECEIVED A RESPONSE TO THE COMMENTS WITHIN 60 DAYS FROM |
| | THE DATE OF THESE COMMENTS (BY DECEMBER 12, 2022), THE |
| | PLANNING DIVISION MAY NOTIFY THE APPLICANT THAT THE |
| | CASE IS CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL |
| | REQUIRE A NEW DEVELOPMENT APPLICATION. |
| | |
| | - PLEASE NOTE THAT PREVIOUSLY ISSUED COMMENTS CONTINUE |
| | WERE NOT ADDRESSED, SO THE APPLICANT IS ASSESSED A |
| | RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF THE ORIGINAL |
| | APPLICATION FEE ($600). |
| | |
| | - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED |
| | IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION |
| | 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT |
| | REGULATIONS. |
| | |
| | THIS APPLICATION WILL BE REVIEWED BY THE PLANNING BOARD |
| | AS A SPECIAL REVIEW, WHICH INCLUDES THEIR ABILITY TO |
| | GRANT WAIVERS AND VARIANCES. PRIOR TO SCHEDULING A |
| | HEARING BEFORE THE PLANNING BOARD AN UPDATED |
| | JUSTIFICATION STATEMENT MUST BE PROVIDE FOR EACH WAIVER |
| | AND VARIANCE REQUESTED/REQUIRED. ONCE THE FINAL NUMBER |
| | OF VARIANCES/WAIVERS IS DETERMINED, THE FEES WILL BE |
| | ADJUSTED BASED ON WHAT HAS BEEN PAID TO DATE VS WHAT IS |
| | STILL OWED. STAFF ANTICIPATES THAT BASED ON THE NUMBER |
| | OF VARIANCES/WAIVERS IDENTIFIED THERE WILL BE |
| | ADDITIONAL MONEY OWED TO THE CITY. |
| | |
| | 1) UPDATED COMMENT: PROVIDE A COPY OF THE TRAFFIC |
| | IMPACT STUDY, DATED AUGUST 24, 2022, THAT IS REFERENCED |
| | IN THE TPS LETTER ISSUED BY PBC ENGINEERING ON |
| | SEPTEMBER 12, 2022. THE LETTER HAS SCALED BACK THE |
| | RECOMMENDED CONDITIONS, SPECIFICALLY THE LEFT TURN ON |
| | 25TH STREET, THAT WERE IN THE PREVIOUS LETTER AND THE |
| | PRIOR TRAFFIC IMPACT ANALYSIS. PLEASE EXPLAIN WHAT |
| | CHANGED. STAFF HAS ALSO NOTED THAT THE PROJECT HAS |
| | SCALED BACK FROM WHAT IS APPROVED ON THE TPS LETTER - |
| | TRAFFIC PERFORMANCE STANDARDS APPROVAL LETTER FROM THE |
| | PALM BEACH COUNTY TRAFFIC DIVISION 66,200 SF RETAIL AND |
| | 382 DU VS ACTUAL 64,200 SF & 381 DU. |
| | |
| | 2) UPDATED COMMENT: THANK YOU FOR SHOWING THE |
| | RECONFIGURATION OF 23RD STREET TO TWO-WAY WEST OF THE |
| | BROADWAY EXTENSION. PLEASE CHECK THE LOCATION OF THE |
| | NEW CROSSWALK OF 23RD STREET ON THE EAST END OF THE |
| | PROJECT. WHEN COMPARING THE PLANS TO THE AERIAL, THE |
| | CROSSWALK IS DIRECTLY INTO THE MIDDLE OF THE DRIVEWAY |
| | APRON FOR THE SINGLE-FAMILY HOUSE ON THE SOUTH SIDE OF |
| | 23RD STREET, WHICH IS NOT PERMITTED. |
| | |
| | 3) REPEAT COMMENT: PROVIDE A PREDETERMINATION LETTER |
| | FROM FDOT FOR THE IMPROVEMENTS WITHIN THE FDOT |
| | RIGHTS-OF-WAY OF BROADWAY AND 24TH AND 25TH STREETS |
| | ADJACENT TO THE PROJECT. *** THIS IS REQUIRED PRIOR TO |
| | SCHEDULING A PLANNING BOARD HEARING. |
| | |
| | 4) REPEAT COMMENT: THE UNIT COUNT HAS INCREASED, SO AN |
| | UPDATED SCAD IS REQUIRED. |
| | |
| | 5) BUILDING C: THE CIVIL PLANS INDICATE THAT THERE WILL |
| | BE AN ACCESS AND UTILITY EASEMENT WHERE THE CURRENT |
| | ALLEY EXISTS. THIS HAS NEVER BEEN DISCUSSED AS BEING |
| | ABANDONED. THIS IS ALSO NOT REFLECTED ON THE OTHER |
| | DISCIPLINE'S PLANS. |
| | |
| | 6) UPDATED COMMENT: ELEMENTS OF THE NORTHEAST CORNER OF |
| | BUILDING B ENCROACHES INTO THE REQUIRED 10-FOOT PRIMARY |
| | A SETBACK FROM BROADWAY. THIS NEEDS TO BE CORRECTED OR |
| | A VARIANCE REQUESTED. SHEET A301 STILL SHOWS THE CORNER |
| | OF THE BUILDING ON THE 1ST FLOOR ENCROACHING. PLEASE |
| | CLARIFY. |
| | |
| | 7) THE SOUTHEAST CORNER OF BUILDING B IS SHOWN |
| | DIFFERENTLY WITH DIFFERING WALL LOCATION AND COLORS |
| | HIGHLIGHTING ON THE VARIOUS GROUND FLOOR SHEETS. PLEASE |
| | PROVIDE CONSISTENT PLANS AND UPDATED ANY TABLES |
| | ACCORDINGLY. |
| | |
| | 8) UPDATED COMMENT: ZONING INFORMATION TABLE ON SHEET |
| | A0.02 BASES THE AVERAGE TOWER FLOOR PLATE ON THE TOTAL |
| | SELLABLE SQUARE FOOTAGE, INSTEAD OF ON THE GROSS SQUARE |
| | FOOTAGE AS REQUIRED. PLEASE UPDATE THE NUMBERS |
| | ACCORDINGLY. SECTION 94-210.I.2.C OF THE NMUD |
| | REGULATIONS LIMIT THE TOWER FLOOR PLATE TO 30,000 |
| | SQUARE FEET FOR ANY SINGLE FLOORPLATE WITH AND AVERAGE |
| | FLOORPLATE OF UP TO 20,000 SQUARE FEET. THE MAXIMUM |
| | TOWER FLOORPLATES ARE SHOWN AT 48,335 SQUARE FEET. THE |
| | NMUD FLOOR PLATE AVERAGE ONLY APPLIES TO THE TOWER |
| | LEVELS OF BUILDING A. PLEASE PROVIDE THE GROSS SQUARE |
| | FOOTAGE FOR EACH LEVEL INDIVIDUALLY FOR LEVELS 3-9. THE |
| | TABLE ON SHEET A0.03 COMBINES THE INFORMATION FOR |
| | LEVELS 3 AND 3.5, WHICH DOES NOT PERMIT STAFF TO |
| | CALCULATE THE AVERAGE TOWER FLOOR PLATE SQUARE FOOTAGE. |
| | THE INFORMATION ON THE TABLE ON SHEET A0.02 IS |
| | INCORRECT. |
| | |
| | TOWER FLOOR PLATE: 48,335 SQUARE FEET = VARIANCE |
| | REQUIRED |
| | AVERAGE TOWER FLOOR PLATE: UNABLE TO DETERMINE EXACT |
| | AVERAGE; HOWEVER, WILL EXCEED 20,000 SQUARE FEET = |
| | VARIANCE REQUIRED |
| | |
| | 9) THE FLOOR PLAN SHEETS THAT SHOW LEVEL 1.5 FOR |
| | BUILDING B ARE NOT ACCURATE (SHEETS A103.1, A104.1, |
| | A305.1) WHEN COMPARED TO THE ELEVATION DRAWINGS. |
| | BUILDING B HAS NO LEVEL 1.5. THE LEVEL 1.5 PLANS |
| | INACCURATELY SHOW THE FLOOR PLAN LAYOUTS FROM LEVEL 2, |
| | INCLUDING THE LANDING POINT OF THE PEDESTRIAN BRIDGE. |
| | THE AREA FOR LEVEL 1.5 IS THE DOUBLE HIGH CEILING OF |
| | LEVEL 1 FOR THE NON-RESIDENTIAL AND THE 2ND FLOOR OF |
| | THE TOWNHOUSES. THE INCORRECT LOCATION OF THE |
| | PEDESTRIAN BRIDGE RESULTS IN THE LEVEL 2 FLOOR PLAN |
| | BEING SHOWN INCORRECTLY. |
| | |
| | 10) THE FLOOR PLAN SHEETS THAT SHOW LEVEL 1.5 FOR |
| | BUILDING C ARE NOT ACCURATE (SHEETS A103.1, A104.1, |
| | A305.1) WHEN COMPARED TO THE ELEVATION DRAWINGS. |
| | BUILDING B IS NOT PERMITTED TO HAVE A LEVEL 1.5 AS THIS |
| | WOULD EXCEED THE ALLOWED NUMBER OF STORIES. THE AREA |
| | FOR LEVEL 1.5 IS THE DOUBLE HIGH CEILING OF LEVEL 1 FOR |
| | THE NON-RESIDENTIAL PORTION OF THE BUILDING. AS |
| | DISCUSSED IN THE LAST MEETING WITH STAFF, THIS ARE IS |
| | PERMITTED TO BE A MEZZANINE FOR THE RESIDENTIAL UNITS |
| | BUT MAY NOT BE A 2ND FLOOR FOR A TOWNHOUSE PRODUCT. THE |
| | INFORMATION TO VERIFY THAT IT COMPLIES WITH THE |
| | MEZZANINE REQUIREMENTS MUST BE PROVIDED. |
| | |
| | 11) THE BUILDING INFORMATION TABLE ON SHEET A0.02 |
| | INCORRECTLY LISTS THE STUDIO UNITS AS 500 SQUARE FEET, |
| | WHICH WOULD NOT COMPLY WITH NMUD MINIMUM UNIT SIZE. |
| | |
| | 12) SHEET A200 IS MISSING THE TITLE BLOCK INFORMATION. |
| | |
| | 13) UPDATED COMMENT: THE ARCHITECTURAL PLANS SHOW A |
| | SUPPORT COLUMN ALONG THE EAST SIDE OF NEW PINEWOOD THAT |
| | IS NOT SHOWN ON THE LANDSCAPE AND CIVIL PLANS. PLEASE |
| | REVIEW AND CORRECT AS NECESSARY. |
| | |
| | DESIGN STANDARDS |
| | |
| | 14) UPDATED COMMENT: ACTIVE USE STANDARDS, INCLUDING |
| | TRANSPARENCY. THE PROPOSED NMUD CORE CODE AMENDMENT HAS |
| | UPDATED THE REQUIREMENTS. STAFF HAS REVIEWED THE |
| | BUILDINGS IN LIGHT OF THE NEW REQUIREMENTS AND |
| | COMMENTED BELOW. THE STAFF CALCULATIONS ARE BASED ON |
| | WHAT COULD BE DETERMINED FROM THE PLAN SHEETS. ACCURATE |
| | TABLES MUST BE INCLUDED ON THE PLANS. *** PLEASE NOTE |
| | THAT THE TRANSPARENCY/FENESTRATION IS BASED ON THE |
| | ACTIVE USES PROVIDED, NOT THE FACADE AREA. THIS WILL |
| | NOT HAVE AREAS SUCH AS THE TRASH ROOMS/BOH COUNT |
| | AGAINST YOUR TRANSPARENCY REQUIREMENT. HOWEVER, THE |
| | FULL HEIGHT OF THE GROUND FLOOR IS COUNTED INTO BOTH |
| | CALCULATIONS, SO THE DOUBLE HEIGHT PORTIONS OF |
| | BUILDINGS B AND C WHERE THERE IS ACTIVE USE, BUT NO |
| | FENESTRATION WILL COUNT AGAINST THE PERCENTAGE |
| | PROVIDED. RECOMMENDATION: YOU SHOULD ELABORATE IN YOUR |
| | VARIANCE JUSTIFICATION ON THIS AS IT RELATES TO THE |
| | ARCHITECTURAL DESIGN OF THESE BUILDINGS. |
| | |
| | ACTIVE USE: REQUIRED ALONG 23RD STREET, BROADWAY |
| | (CORE), 25TH STREET - GROUND FLOOR - 80%, UPPER FLOORS |
| | 100% |
| | REQUIRED ALONG NEW PINEWOOD - GROUND FLOOR - 30%, |
| | UPPER FLOORS - N/A |
| | REQUIRED ALONG BROADWAY EXTENSION - GROUND FLOOR - |
| | 80%, UPPER FLOORS - N/A |
| | REQUIRED ALONG PUBLIC OPEN SPACE - GROUND FLOOR - |
| | 75%, UPPER FLOORS - 75% |
| | REQUIRED ALONG PUBLIC PASEO - GROUND FLOOR - 80%, |
| | UPPER FLOORS - N/A |
| | REQUIRED ALONG 24TH STREET, BROADWAY (TRANSITION), |
| | NORTHWOOD ROAD - ALL FLOORS 100% |
| | |
| | BUILDING A ACTIVE USE |
| | |
| | BROADWAY GROUND FLOOR: 90% COMPLIES |
| | BROADWAY UPPER FLOORS: ALL LEVELS 100% COMPLIES |
| | 25TH STREET GROUND FLOOR: 94% COMPLIES |
| | 25TH STREET LEVELS 1.5 & 2: 11% PROVIDED = VARIANCE |
| | REQUIRED SECTION 94-209.2.E.2.B.I. |
| | 25TH STREET LEVEL 3 & ABOVE: 100% COMPLIES |
| | NEW PINEWOOD EAST: 64% COMPLIES |
| | NEW PINEWOOD WEST: 37% COMPLIES |
| | PUBLIC OPEN SPACE GROUND FLOOR: 92% COMPLIES |
| | PUBLIC OPEN SPACE UPPER FLOORS: 100% COMPLIES |
| | PUBLIC PASEO: 100% COMPLIES |
| | |
| | BUILDING B ACTIVE USE |
| | |
| | BROADWAY EXTENSION: 100% COMPLIES |
| | 23RD STREET GROUND FLOOR: 85% COMPLIES |
| | 23RD STREET UPPER FLOORS: 100% COMPLIES |
| | NEW PINEWOOD: 100% COMPLIES |
| | PUBLIC OPEN SPACE GROUND FLOOR: 97% COMPLIES |
| | PUBLIC OPEN SPACE UPPER FLOORS: 100% COMPLIES |
| | |
| | BUILDING C ACTIVE USE |
| | |
| | BROADWAY ALL FLOORS: 100% COMPLIES |
| | 24TH STREET ALL FLOORS: 100% COMPLIES |
| | NORTHWOOD GROUND FLOOR: 92% PROVIDED = VARIANCE |
| | REQUIRED SECTION 94-209.2.J.H.I.1 |
| | NORTHWOOD UPPER FLOOR: 100% COMPLIES |
| | |
| | TRANSPARENCY: REQUIRED ALONG 23RD STREET, BROADWAY |
| | (CORE), 25TH STREET - GROUND FLOOR NON-RESIDENTIAL - |
| | 70%, GROUND FLOOR RESIDENTIAL - 30%, UPPER FLOORS - N/A |
| | FOR ALL ACTIVE USE AREAS |
| | REQUIRED ALONG NEW PINEWOOD - 50% OF GROUND FLOOR |
| | ACTIVE USE AREAS |
| | REQUIRED ALONG BROADWAY EXTENSION - 70% OF GROUND |
| | FLOOR ACTIVE USE AREAS |
| | REQUIRED ALONG PUBLIC OPEN SPACE - 70% OF ALL ACTIVE |
| | USE AREAS |
| | REQUIRED ALONG PUBLIC PASEO - 70% OF ALL ACTIVE USE |
| | AREAS |
| | REQUIRED ALONG 24TH STREET, BROADWAY (TRANSITION), |
| | NORTHWOOD ROAD - GROUND FLOOR NON-RESIDENTIAL - 70%, |
| | UPPER FLOORS - N/A FOR ALL ACTIVE USE AREAS |
| | |
| | BUILDING A TRANSPARENCY |
| | |
| | BROADWAY GROUND FLOOR: 100% COMPLIES |
| | 25TH STREET GROUND FLOOR: 100% COMPLIES |
| | NEW PINEWOOD EAST: APPEARS TO EXCEED 50%, BUT NO |
| | TABULAR/GRAPHIC INFORMATION PROVIDED |
| | NEW PINEWOOD WEST: APPEARS TO EXCEED 50%, BUT NO |
| | TABULAR/GRAPHIC INFORMATION PROVIDED |
| | PUBLIC OPEN SPACE GROUND FLOOR: 100% COMPLIES |
| | PUBLIC OPEN SPACE UPPER FLOORS: TABULAR/GRAPHIC |
| | INFORMATION REQUIRED FOR LEVELS 1.5 AND 2 ONLY |
| | PUBLIC PASEO: APPEARS TO EXCEED 70%, BUT NO |
| | TABULAR/GRAPHIC INFORMATION PROVIDED |
| | |
| | THE NON-ACTIVE USE AREAS ON THE BUILDING A FENESTRATION |
| | DRAWINGS NEED TO BE SHOWN EXCLUDED FROM THE TABLE AND |
| | DRAWINGS. |
| | |
| | THE FENESTRATION TABLE INCORRECTLY LISTS THE NORTH |
| | ELEVATION OF BUILDING A AS HAVING NO FENESTRATION. THE |
| | 100% IS SHOWN UNDER THE SOLID COLUMN. |
| | |
| | BUILDING B TRANSPARENCY |
| | |
| | BROADWAY EXTENSION GROUND FLOOR: SEE COMMENTS BELOW |
| | VARIANCE REQUIRED SECTION 94-210.M.5 |
| | 23RD STREET GROUND FLOOR: SEE COMMENTS BELOW VARIANCE |
| | REQUIRED SECTIONS 94-210.P.1.II & III |
| | NEW PINEWOOD GROUND FLOOR: 46% PROVIDED = VARIANCE |
| | REQUIRED SECTION 94-210.M.4 |
| | PUBLIC OPEN SPACE GROUND FLOOR: 47% PROVIDED = VARIANCE |
| | REQUIRED SECTION 94-210.K.1.N |
| | PUBLIC OPEN SPACE UPPER FLOORS: 28% PROVIDED = VARIANCE |
| | REQUIRED SECTION 94-210.K.1.N |
| | |
| | BUILDING B COMMENTS |
| | I. BROADWAY EXTENSION (EAST ELEVATION). THE EAST |
| | ELEVATION FRONTS ON BROADWAY EXTENSION, WHICH REQUIRES |
| | A MINIMUM OF 70% OF THE ACTIVE USE TO BE HAVE |
| | TRANSPARENCY. THE TABLE LISTS 48% GROUND FLOOR |
| | TRANSPARENCY, YET THE ELEVATION DRAWING DOES NOT MATCH |
| | THE SITE PLAN AND DOES NOT SHOW THE FULL EXTENT OF THE |
| | OF THE SOUTHEAST CORNER OF THE BUILDING. *** VARIANCE |
| | REQUIRED |
| | II. 23RD STREET GROUND FLOOR (SOUTH ELEVATION). THE NEW |
| | REGULATIONS SEPARATE THE REQUIREMENTS FOR |
| | NON-RESIDENTIAL (MIN 70%) AND RESIDENTIAL (30%). SINCE |
| | THIS FACADE HAS BOTH, PLEASE PROVIDE THE TABLE |
| | ACCORDINGLY. IT APPEARS THAT THE RESIDENTIAL PORTION OF |
| | THE BUILDING WILL MEET CODE; HOWEVER, THE |
| | NON-RESIDENTIAL LOOKS LOW (DUE TO THE DOUBLE HEIGHT |
| | FLOOR) AND WOULD REQUIRE A VARIANCE. STAFF NEEDS THE |
| | FINAL NUMBER TO PROCEED TO THE PLANNING BOARD. PLEASE |
| | REMEMBER THAT THE TRANSPARENCY IS A PERCENTAGE OF THE |
| | ACTIVE USE, SO THE BOH AND TRASH ROOMS WOULD NOT BE |
| | INCLUDED AS THE BASE ACTIVE USE AREA. *** VARIANCE |
| | REQUIRED |
| | |
| | BUILDING C TRANSPARENCY |
| | |
| | BROADWAY GROUND FLOOR: 49% PROVIDED = VARIANCE REQUIRED |
| | SECTION-209.2.J.1.H.I.4 |
| | 24TH STREET GROUND FLOOR: 52% PROVIDED = VARIANCE |
| | REQUIRED SECTION-209.2.J.1.H.I.4 |
| | NORTHWOOD GROUND FLOOR: 43% PROVIDED = VARIANCE |
| | REQUIRED SECTION-209.2.J.1.H.I.4 |
| | |
| | 15) UPDATED COMMENT: STAFF HAS REVIEWED THE INFORMATION |
| | PROVIDED FOR THE PLANAR BREAKS AND HAD THE FOLLOWING |
| | COMMENTS. |
| | |
| | BUILDING A PLANAR BREAKS |
| | |
| | BROADWAY GROUND FLOOR: 21% COMPLIES |
| | BROADWAY LEVEL 1.5: 13% THAT IS A MINIMUM OF 3 FEET IN |
| | DEPTH (PASEO) *** ADDITIONAL 35% OF THE FRONTAGE HAS A |
| | PLANAR BREAK THAT DOES NOT COMPLY WITH THE MINIMUM |
| | 3-FOOT DEPTH = VARIANCE REQUIRED SECTION 94-209.2.J.1.A |
| | BROADWAY LEVEL 2: 42% COMPLIES *** DOES NOT COMPLY WITH |
| | THE MINIMUM 3-FOOT DEPTH = VARIANCE REQUIRED SECTION |
| | 94-209.2.J.1.A |
| | BROADWAY LEVELS 3 & ABOVE: ALL LEVELS 43% COMPLIES |
| | 25TH STREET GROUND FLOOR: 21% COMPLIES |
| | 25TH STREET LEVELS 1.5 & 2: 52% COMPLIES *** DOES NOT |
| | COMPLY WITH THE MINIMUM 3-FOOT DEPTH = VARIANCE |
| | REQUIRED SECTION 94-209.2.J.1.A |
| | 25TH STREET LEVEL 3 & ABOVE: 50% COMPLIES |
| | |
| | BUILDING B PLANAR BREAKS |
| | |
| | 23RD STREET GROUND FLOOR: 24% COMPLIES |
| | 23RD STREET UPPER FLOORS: 43% COMPLIES |
| | |
| | BUILDING C PLANAR BREAKS |
| | |
| | BROADWAY GROUND FLOOR: ** THIS IS INCORRECTLY |
| | CALCULATED; HOWEVER, SINCE THE ALLEY GAP IS 28% OF THE |
| | FRONTAGE, THE PLANAR BREAK COMPLIES. |
| | BROADWAY LEVELS 2 & 3: ** THIS IS INCORRECTLY |
| | CALCULATED, BOTH THE LENGTH OF THE BUILDING AND WHAT IS |
| | A PLANAR BREAK. THE ONLY PLANAR BREAK IS AT THE SOUTH |
| | END AT THE ANGLE AND RESULTS IN AN APPROXIMATELY 3% |
| | PLANAR BREAK. SECTION 94-209.2.J.1.A |
| | |
| | 16) UPDATED COMMENT: PLANAR BREAKS ARE REQUIRED TO BE A |
| | MINIMUM OF THREE FEET IN DEPTH. THE DEPTH SHOWN FOR THE |
| | PLANAR BREAKS ON LEVELS 1.5 AND 2 OF BUILDING A ALONG |
| | 25TH STREET AND BROADWAY ARE ONLY 1.6 FEET IN DEPTH, |
| | WHICH REQUIRES THE APPROVAL OF A VARIANCE. STAFF IS NOT |
| | PREPARED TO SUPPORT THE NEEDED VARIANCE REQUEST ALONG |
| | 25TH STREET. THE SUGGESTIONS MADE BY ANA MARIA APONTE, |
| | CRA DEPUTY DIRECTOR, TO LESSEN THE VARIANCES THAT WOULD |
| | BE NEEDED WERE NOT IMPLEMENTED, SO THE STANDARD THAT |
| | THE, "VARIANCE GRANTED IS THE MINIMUM VARIANCE THAT |
| | WILL MAKE POSSIBLE THE REASONABLE USE OF THE LAND, |
| | BUILDING, OR STRUCTURE", HAS NOT BEEN MET. |
| | |
| | STREETSCAPE |
| | |
| | 17) REPEAT COMMENT: THANK YOU FOR PROVIDING THE LIGHT |
| | POLE LOCATIONS ON THE SITE PLAN; HOWEVER, THERE IS ONE |
| | THAT IS IN DIRECT CONFLICT WITH A TREE AND MULTIPLE |
| | THAT ARE SHOWN IN PARKING SPACES AND THE TRAVEL LANE |
| | (ON ALL PLANS). THE POLES NEED TO BE SHOWN IN THE |
| | CORRECT LOCATION. |
| | |
| | 18) THE POLE TYPE ALONG 25TH STREET NEEDS TO BE THE "S" |
| | TYPE TO MATCH THE POLES ON 25TH STREET EAST OF |
| | BROADWAY. |
| | |
| | 19) THE CRA MUST APPROVE THE USE OF TWO DIFFERENT POLE |
| | STYLES ALONG BROADWAY BETWEEN 25TH STREET AND 23RD |
| | STREET. THEY ARE CURRENTLY "T" TYPE. |
| | |
| | PARKING/LOADING |
| | |
| | 20) REPEAT COMMENT: PROVIDE VEHICLE TURNING RADIUS |
| | DRAWING FOR MOVING TRUCKS INTO/OUT OF THE LOADING |
| | AREAS. **** SHEET C4.02 ONLY SHOWS A MOVING TRUCK |
| | ACCESSING PINEWOOD, BUT NOT THE ACTUAL LOADING AREAS. |
| | |
| | 21) THE PARKING REQUIRED AND PROVIDED TABLES AND THE |
| | TOTAL PARKING SPACES LINE BOTH CONTAIN ERRORS. |
| | |
| | A. SHEETS A103.1 AND SHEET A301.5 - THERE ARE ONLY 233 |
| | PARKING SPACES, NOT 235 ON THIS LEVEL. ALSO ON SHEET |
| | A301.5 THE PARKING SPACE TYPE BREAKDOWN IS INCORRECT. |
| | B. THE L1.5 CRA LINE STATES THAT THERE ARE SPACES, BUT |
| | ONE OF THEM IS A DOUBLE COUNTED ADA SPACE THAT IS SHOWN |
| | IN THE ADA LINE. |
| | C. THE L1.5 PUBLIC PARKING LINE STATES THAT THERE ARE |
| | 108 PARKING SPACES, WHEN THERE ARE 109 LABELED. |
| | D. SHEET A302 LISTS AN INCORRECT NUMBER OF PARKING |
| | SPACES. |
| | E. THE PARKING REQUIRED TABLE INCORRECTLY LISTS 384 |
| | SPACES PROVIDED FOR THE RESIDENTIAL, WHEN 403 ARE |
| | PROVIDED AND 181 SPACES PROVIDED FOR THE COMMERCIAL, |
| | WHEN ONLY 128 ARE PROVIDED. |
| | F. ENSURE ALL TABLES AND INFORMATION ON ALL SHEETS |
| | SHOWS CONSISTENT, ACCURATE INFORMATION. |
| | |
| | 22) THERE ARE SEVEN PARKING SPACES ON LEVEL 2 THAT SHOW |
| | COLUMN ENCROACHMENTS, WHICH ARE NOT PERMITTED. |
| | |
| | 23) THANK YOU FOR PROVIDING THE DIMENSIONS FOR THE |
| | PARKING SPACES ALONG WALLS. THERE IS ONE PP SPACE AT |
| | THE NORTHWEST CORNER OF LEVEL 1.5 THAT DOES NOT HAVE |
| | THE EXTRA ROOM. THIS SPACE NEEDS TO BE MARKED AS |
| | COMPACT AND THE PARKING TABLE UPDATED WITH IT AS A LINE |
| | ITEM. NOTE: IF AT TIME OF CONSTRUCTION/PARKING SPACE |
| | STRIPING ADDITIONAL SPACES ARE IDENTIFIED AS LESS THAN |
| | A FOOT FROM THE WALL, THEY WILL ALSO NEED TO BE MARKED |
| | AS COMPACT WITH AN AMENDMENT TO THE SITE PLAN AT THAT |
| | TIME. |
| | |
| | 24) THERE ARE 19 PARKING SPACES (18 PP & 1 ADA) LOCATED |
| | OUTSIDE OF THE GATES ON LEVEL 1.5 THAT APPEAR TO BE THE |
| | GUEST PARKING SPACES. PLEASE LABEL THESE AS THE GUEST |
| | SPACES ON THE PLANS. NOTE: THE NON-ADA SPACES WILL NEED |
| | TO BE MARKED AS GUEST WHEN CONSTRUCTED. |
| | |
| | 25) SHEETS A103.1 AND A301.5 SHOW DIFFERING LOCATIONS |
| | FOR THE ADA VAN SPACES. ALL SHEETS NEED TO SHOW THE |
| | SAME CONDITION. PLEASE MAKE SURE THAT THE ADA GUEST |
| | SPACE IS AN ADA VAN SPACE SO THAT THERE IS ONE ADA VAN |
| | SPACE AVAILABLE OUTSIDE THE GATED AREA. |
| | |
| | 26) THE PARKING SPACES TYP DETAIL SHOWS COLUMNS IN THE |
| | PARKING SPACES, WHICH IS NOT PERMITTED. THE DETAIL |
| | NEEDS TO BE CORRECTLY SHOWN. |
| | |
| | 27) THE ADA PARKING SPACE DETAIL CONTAINS A BLOW UP OF |
| | THE SPACE BETWEEN THE STRIPING THAT DOES NOT CONFORM TO |
| | CITY CODE. THE CITY REQUIRES 12 INCHES BETWEEN THE |
| | STRIPES. A DETAIL CAN BE PROVIDED IF NEEDED. |
| | |
| | 28) REPEAT COMMENT: THANK YOU FOR PROVIDING THE BICYCLE |
| | RACK MODEL DETAIL AND DIMENSIONS THAT WILL BE USED IN |
| | THE BICYCLE STORAGE ROOMS. THIS MODEL NEEDS TO BE SHOWN |
| | IN THE BICYCLE STORAGE ROOMS TO INCLUDE THE DIMENSIONS |
| | OF THE ROOM AND THE RACKS IN THE ROOM. **** THE BICYCLE |
| | ROOM DETAILS DO NOT SHOW THE SAME RACK OR THE |
| | DIMENSIONS THAT ARE ON THE DETAIL. ADDITIONALLY, STAFF |
| | ATTEMPTED TO CALCULATE THE NUMBER OF BICYCLES THAT |
| | COULD BE STORED, AND THEY DO NOT MATCH THE NUMBER OF |
| | RACKS IN EITHER THE RESIDENTIAL OR THE COMMERCIAL |
| | ROOMS. |
| | |
| | 29) UPDATED COMMENT: THANK YOU FOR SHOWING BICYCLE |
| | FACILITIES AT 13 LOCATIONS (MOSTLY IN GROUPS OF THREE |
| | RACKS FOR SIX BICYCLES AT EACH LOCATION) THROUGHOUT THE |
| | SITE AS WELL AS THE POST AND HITCH MODEL. PLEASE |
| | PROVIDE THE PAD DETAIL SHOWING THE DIMENSIONS BASED ON |
| | THE NUMBER OF POSTS THAT WILL BE INSTALLED. THE PAD |
| | DETAIL MUST INCLUDE THE RACK(S) AND THE DIMENSIONS FROM |
| | THE RACKS TO THE EDGE OF THE PAD. ADDITIONALLY, |
| | DIMENSIONED PAD BOX NEEDS TO BE INCLUDED ON THE PLAN SO |
| | THAT STAFF CAN VERIFY THAT PARKED BICYCLES WILL NOT |
| | IMPEDE THE PEDESTRIAN TRAVEL PATHS OR BE WITHIN A |
| | LANDSCAPE ISLAND OR OTHERWISE HAVE NONFUNCTIONING |
| | BICYCLE PARKING. FOR CLARITY THIS DETAIL SHALL BE |
| | PROVIDED AT A BIGGER SCALE. STAFF HAS NOTED THAT THE |
| | HARDSCAPE DETAIL PLAN CALLS OUT A QUANTITY OF 10 POSTS, |
| | WHICH WOULD NOT PERMIT THE INSTALLATION OF BICYCLE |
| | PARKING AT ALL THE LOCATION SHOWN NOR AT THE QUANTITY |
| | OF BICYCLE PARKING SHOWN. |
| | |
| | LANDSCAPE |
| | |
| | 30) THE PUBLIC OPEN SPACE DIAGRAMS ARE NOT CORRECTLY |
| | DEPICTED AND DO NOT CLEARLY SHOW COMPLIANCE WITH THE |
| | PUBLIC OPEN SPACE REQUIREMENTS. STAFF WILL PROVIDE A |
| | MARK-UP UNDER SEPARATE COVER HIGHLIGHTING WHAT NEEDS TO |
| | BE SHOWN. |
| | |
| | 31) THE MINIMUM 10% PERVIOUS REQUIREMENT IS NOT SHOWN |
| | AS BEING MET ON THE LANDSCAPE PLAN FOR BOTH THE |
| | BUILDING A & B PARCEL AND THE BUILDING C PARCEL. WHILE |
| | BUILDING C IS A CONSTRAINED SITE, THE PROVISION OF THE |
| | PUBLIC OPEN SPACE, THE BUFFER ALONG THE RAILROAD TRACK |
| | AND THE AREA ON THE EAST SIDE OF THE BROADWAY EXTENSION |
| | SEEM TO OFFER SUFFICIENT AREA TO MEET THE 10% MINIMUM. |
| | IF THERE IS INSUFFICIENT DIRECT PERVIOUS AREA DUE TO |
| | LANDSCAPE, YOU WILL NEED TO INSTALL A PERVIOUS PAVER |
| | SYSTEM TO GET TO THE MINIMUM 10%. BUILDING C = VARIANCE |
| | REQUIRED SECTION 94-210.I.3. PLANNING STAFF DOES NOT |
| | SUPPORT WAIVING THE MINIMUM PERVIOUS SURFACE |
| | REQUIREMENT FOR BUILDING A & C. |
| | |
| | WAIVERS/VARIANCES |
| | |
| | 32) SECTION 94-209.2.J.1.A - THE MAXIMUM HORIZONTAL |
| | DIMENSION OF A BUILDING WITHIN THE MIXED-USE DISTRICTS |
| | IS 250 FEET. BUILDING A EXCEEDS THIS ON ALL FRONTAGES. |
| | STAFF IS UNABLE TO LOCATE THE FULL NORTH/SOUTH |
| | DIMENSION FOR LEVEL 2 AS THIS IS THE LARGEST |
| | FLOORPLATE. PLEASE CLEARLY PROVIDE ON ONE OF THE LEVEL |
| | 2 SITE PLANS. **** VARIANCE REQUIRED. |
| | |
| | 33) SECTION 94-210.I.3.A - THE MAXIMUM LOT WIDTH FOR |
| | FLEX BUILDINGS IS 200 FEET AND TOWER BUILDINGS IS 250 |
| | FEET. |
| | |
| | BROADWAY LOT WIDTH: 554.75 FEET = VARIANCE REQUIRED. |
| | |
| | 34) SECTION 94-209.2.K.1 - THE MAXIMUM BLOCK LENGTH IS |
| | 600 FEET. THE CURRENT BLOCK LENGTH IS 810 FEET (SPRUCE |
| | TO PINEWOOD) WITH THE ABANDONMENT OF PINEWOOD EXTENDING |
| | THIS TO 965 FEET AT ITS FURTHEST POINT WEST AT 25TH |
| | STREET AND THE FEC RR. |
| | |
| | EAST/WEST BLOCK LENGTH: 965 FEET = VARIANCE REQUIRED. |
| | |
| | 35) SECTION 94-209.2.K.2 - THE MAXIMUM BLOCK PERIMETER |
| | LENGTH IS 1,900 FEET. THE ABANDONMENT OF THE |
| | RIGHTS-OF-WAY RESULT IN A BLOCK WITH A PERIMETER OF |
| | SPRUCE, 23RD, FEC RR, 25TH, BROADWAY AND NORTHWOOD THAT |
| | IS 2,192 FEET IN LENGTH. |
| | |
| | 36) SECTION 94-210.I.2.B - A SETBACK OF 15 FEET FROM |
| | THE ALLEY IS REQUIRED FOR BUILDING C. THIS IS MET ON |
| | THE GROUND FLOOR BUT NOT ON THE UPPER FLOORS WHERE THE |
| | PLANS SHOW THE BUILDING STRADDLING THE ALLEY. |
| | |
| | 37) CONDITION: ACCESS EASEMENT REQUIRED FOR ANY |
| | PORTIONS OF SIDEWALKS ON PRIVATE PROPERTY AND THE |
| | ROADWAYS TRAVERSING THE SITE AND THE PARKING SPACES ON |
| | PRIVATE PROPERTY. |
| | |
| | 38) CONDITION: AREAL EASEMENT REQUIRED WHERE BUILDING C |
| | STRADDLES THE ALLEY. |
| | |
| | |
| |