| 2022-08-17 15:33:49 | CASE NO. 1895 ? JULY 19, 2022 RESUBMITTAL |
| | NORTHWOOD COMMONS - NMUD ANCHOR SITE |
| | BROADWAY & 24TH STREET |
| | |
| | - CONTACT ERIC SCHNEIDER @ (561) 822-1446, |
| | [email protected] |
| | |
| | - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN |
| | WRITTEN FORMAT. |
| | |
| | - WHEN RESUBMITTING, PLEASE PROVIDE THREE (3) PAPER |
| | COPIES AND AN ELECTRONIC COPY IN .PDF AND .PNG FORMAT |
| | OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE |
| | RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS |
| | TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL |
| | COMMENTS. |
| | |
| | - ONCE THE COMMENTS ARE RESUBMITTED AND DEEMED |
| | SUFFICIENTLY ADDRESSED, THE CASE WILL BE SCHEDULED FOR |
| | THE NEXT AVAILABLE PLANNING BOARD MEETING. |
| | |
| | - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT |
| | RECEIVED A RESPONSE TO THE COMMENTS WITHIN 60 DAYS FROM |
| | THE DATE OF THESE COMMENTS (BY OCTOBER 17, 2022), THE |
| | PLANNING DIVISION MAY NOTIFY THE APPLICANT THAT THE |
| | CASE IS CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL |
| | REQUIRE A NEW DEVELOPMENT APPLICATION. |
| | |
| | - PLEASE NOTE THAT PREVIOUSLY ISSUED COMMENTS CONTINUE |
| | WERE NOT ADDRESSED, SO THE APPLICANT IS ASSESSED A |
| | RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF THE ORIGINAL |
| | APPLICATION FEE ($600). |
| | |
| | - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED |
| | IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION |
| | 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT |
| | REGULATIONS. |
| | |
| | THE PROPOSED DEVELOPMENT REQUIRES AMENDMENTS TO THE |
| | ZONING AND LAND DEVELOPMENT REGULATIONS, WHICH MUST BE |
| | ADOPTED PRIOR TO THE FINAL SITE PLAN APPROVAL. THE |
| | RECENTLY ADOPTED CHANGE TO THE NMUD APPROVAL PROCESS |
| | WILL SEE THIS APPLICATION BE REVIEWED BY THE PLANNING |
| | BOARD AS A SPECIAL REVIEW, WHICH INCLUDES THEIR ABILITY |
| | TO GRANT WAIVERS AND VARIANCES. STAFF HAS IDENTIFIED |
| | MORE THAN THE THREE LISTED ON SHEET A0.02. NO |
| | JUSTIFICATION WAS PROVIDED FOR EACH WAIVER AND VARIANCE |
| | REQUESTED/REQUIRED. UNTIL ALL INFORMATION IS PROVIDED, |
| | STAFF IS WITHHOLDING DETERMINATION ON SUPPORT/NOT |
| | SUPPORT OF EACH INDIVIDUAL WAIVER AND VARIANCE. |
| | |
| | 1) UPDATED COMMENT: PROVIDE A REVISED TRAFFIC |
| | PERFORMANCE STANDARDS APPROVAL LETTER FROM THE PALM |
| | BEACH COUNTY TRAFFIC DIVISION FOR THE SCOPE OF THE |
| | PROPOSED DEVELOPMENT BASED ON THE UPDATED PLANS AND |
| | TRAFFIC IMPACT ANALYSIS (66,200 SF RETAIL AND 381 DU). |
| | THE TRAFFIC LETTER NEEDS TO REFLECT THAT THE ANCHOR |
| | SITE PROJECT BOUNDARIES ARE NOT VACANT, BUT THAT THE |
| | CONTAIN BUILDINGS (3) AS SHOWN ON THE SURVEY. *** THE |
| | LATEST TIA SHOWS THE NEW USE MIX HAVING LESS IMPACT |
| | THAN WHAT THE CURRENT TPS LETTER, DATED MAY 13, 2022, |
| | SHOWS; HOWEVER, THAT UNDER THE NEW SPECIAL REVIEW |
| | PROCESS, THE PLANNING BOARD IS THE APPROVING AUTHORITY, |
| | SO THE TPS LETTER IS REQUIRED PRIOR TO SCHEDULING THE |
| | CASE BEFORE THE PLANNING BOARD. |
| | |
| | 2) THE PLANS DO NOT SHOW THE FOLLOWING ITEMS THAT ARE |
| | LISTED IN THE TRAFFIC IMPACT ANALYSIS: |
| | |
| | A. ADDITION OF 80-FOOT EASTBOUND AND WESTBOUND LEFT |
| | TURN LANES ON 25TH STREET, AT THE INTERSECTION OF 25TH |
| | STREET AND PINEWOOD AVENUE. |
| | B. CONVERSION OF 23RD STREET FROM ONE-WAY FLOW TO |
| | TWO-WAY FLOW BETWEEN PINEWOOD AVENUE AND THE PROPOSED |
| | BROADWAY EXTENSION. |
| | |
| | 3) REPEAT COMMENT: PROVIDE A PREDETERMINATION LETTER |
| | FROM FDOT FOR THE IMPROVEMENTS WITHIN THE FDOT |
| | RIGHTS-OF-WAY OF BROADWAY AND 24TH AND 25TH STREETS |
| | ADJACENT TO THE PROJECT. *** THIS IS REQUIRED PRIOR TO |
| | SCHEDULING A PLANNING BOARD HEARING. |
| | |
| | 4) THE UNIT COUNT HAS INCREASED, SO AN UPDATED SCAD IS |
| | REQUIRED. |
| | |
| | 5) BUILDING C: PLANNING STAFF HAS NOTED THAT THE |
| | COMMENT BY THE CITY SURVEYOR REQUIRING 25-FOOT |
| | CLEARANCE OVER THE ALLEY HAS NOT BEEN MET. THIS |
| | CLEARANCE IS REQUIRED SO THAT THERE IS ADEQUATE |
| | CLEARANCE FOR ANY UTILITY MAINTENANCE WITHIN THE ALLEY. |
| | PLEASE REMEMBER THAT THE MAXIMUM FIRST STORY HEIGHT IS |
| | 20 FEET. |
| | |
| | 6) ELEMENTS OF THE NORTHEAST CORNER OF BUILDING B |
| | ENCROACHES INTO THE REQUIRED 10-FOOT PRIMARY A SETBACK |
| | FROM BROADWAY. THIS NEEDS TO BE CORRECTED OR A VARIANCE |
| | REQUESTED. |
| | |
| | 7) THE WAIVER/VARIANCE TABLE ON SHEET A0.02 NEEDS TO |
| | CORRECTLY SHOW THAT THE MAXIMUM AVERAGE FLOORPLATE IS |
| | DEPENDENT ON THE TOWER'S PRIMARY USE, WHICH IS |
| | RESIDENTIAL - 30,000 SQUARE FEET FOR ANY SINGLE |
| | FLOORPLATE WITH AND AVERAGE FLOORPLATE OF UP TO 20,000 |
| | SQUARE FEET. |
| | |
| | 8) THE BUILDING B ELEVATION DRAWINGS SHOW THE |
| | PEDESTRIAN BRIDGE WITH A BASE ELEVATION OF 20 FEET IN |
| | LINE WITH LEVEL 2; HOWEVER, THE BUILDING A ELEVATION |
| | DRAWINGS SHOW THE PEDESTRIAN BRIDGE WITH A BASE |
| | ELEVATION OF 27 FEET. PLEASE PROVIDE THE CROSS SLOPES |
| | SO THAT ADA COMPLIANCE CAN BE VERIFIED. |
| | |
| | DESIGN STANDARDS |
| | |
| | 9) UPDATED COMMENT: ACTIVE USE STANDARDS - |
| | |
| | A. BUILDING B - THE ELEVATION LABELS AND THE SCALE ARE |
| | INCORRECT ON SHEET A101.2. BY DEFINITION, THE ENTIRE |
| | GROUND FLOOR IS DEFINED AS STOREFRONT, REGARDLESS OF |
| | THE USE; THEREFORE, THE RESIDENTIAL PORTION OF THE |
| | BUILDING MUST BE INCLUDED IN THE STOREFRONT GLAZING |
| | CALCULATIONS. |
| | B. BUILDING C - THE RESIDENTIAL PORTION OF THE BUILDING |
| | MUST BE INCLUDED IN THE STOREFRONT GLAZING |
| | CALCULATIONS. THE NORTHWEST CORNER NEEDS TO BE |
| | INCLUDED. THE EAST ELEVATION TABLE INFORMATION IS |
| | BACKWARDS (NOT 100% FENESTRATION). |
| | C. CODE TEXT WILL INCLUDE CLARIFICATION THAT ACTIVE |
| | USES ARE NOT REQUIRED ALONG THE RR. |
| | |
| | 10) UPDATED COMMENT: SECTION 94-209.J.A. REQUIRES THE |
| | PROVISION OF PLANAR BREAKS FOR FRONTAGES EXCEEDING 150 |
| | FEET IN LENGTH. THE PLANAR BREAK CALCULATIONS FOR THE |
| | FRONTAGES OF BUILDINGS B AND C THAT EXCEED 150 FEET |
| | WERE NOT PROVIDED. THE PLANAR BREAK CALCULATIONS WERE |
| | NOT PROVIDED FOR THE GROUND FLOOR OF BUILDING A. PLANAR |
| | BREAKS ARE REQUIRED, REGARDLESS OF THIS BEING |
| | STOREFRONT. |
| | |
| | 11) PLANAR BREAKS ARE REQUIRED TO BE A MINIMUM OF THREE |
| | FEET IN DEPTH. THE DEPTH SHOWN FOR THE PLANAR BREAKS ON |
| | LEVELS 1.5 AND 2 OF BUILDING A ALONG 25TH STREET AND |
| | BROADWAY ARE ONLY 1.6 FEET IN DEPTH, WHICH REQUIRES THE |
| | APPROVAL OF A VARIANCE. STAFF IS NOT PREPARED TO |
| | SUPPORT THIS VARIANCE REQUEST AS NO JUSTIFICATION HAS |
| | BEEN PROVIDED FOR WHY THESE CANNOT MEET THE MINIMUM |
| | REQUIREMENT. IF THE PLAN IS TO PROCEED WITH A VARIANCE |
| | REQUEST, THEN YOU MUST PROVIDE NOT ONLY THE |
| | JUSTIFICATION FOR THE VARIANCE, BUT ALSO BETTER DETAILS |
| | AS TO WHAT THE ELEVATIONS WILL LOOK LIKE IF THE |
| | VARIANCE IS APPROVED, TO INCLUDE THE SPECIFIC |
| | ARCHITECTURAL TREATMENT THAT WILL OFFSET THE REDUCED |
| | DEPTH DIMENSION. |
| | |
| | 12) REPEAT COMMENT: PROVIDE THE DIMENSIONS OF THE |
| | PROJECTIONS AND ENCROACHMENTS (EX. BALCONIES AND OTHER |
| | ARCHITECTURAL FEATURES) ON THE PLANS AND ELEVATIONS SO |
| | THAT STAFF CAN VERIFY COMPLIANCE WITH THE NMUD |
| | REGULATIONS. THIS HAS NOT BEEN PROVIDED FOR ALL THE |
| | FACADES ON ALL THE BUILDINGS. **** THE FOLLOWING ARE |
| | FEATURES THAT DID NOT HAVE DIMENSIONS PROVIDED. ANY |
| | FEATURES THAT DO NOT MEET MINIMUM OR MAXIMUM |
| | ENCROACHMENT ALLOWANCE WILL REQUIRE A VARIANCE. |
| | |
| | A. THE NORTH AND EAST ELEVATION DRAWINGS FOR BUILDING A |
| | CALL OUT AN ALUMINUM CANOPY ON THE UPPER PORTION OF THE |
| | GROUND LEVEL; HOWEVER, NO DETAILS OF THIS CANOPY, TO |
| | INCLUDE DIMENSIONS, ARE PROVIDED SO THAT STAFF CAN |
| | VERIFY CODE COMPLIANCE. ADDITIONALLY, THE CANOPY IS NOT |
| | SHOWN ON THE SIDES OF THESE ELEVATION DRAWINGS |
| | EXTENDING FROM THE BUILDING. |
| | B. THE BALCONY THAT WRAPS BUILDING B. |
| | C. THE CANOPY ON BUILDING C. NOTE: THE CANOPY IS SHOWN |
| | ON THE ELEVATION DRAWINGS, BUT NOT THE SITE/FLOOR |
| | PLANS. ADDITIONALLY, IT IS SHOWN ENCROACHING INTO THE |
| | RIGHT-OF-WAY. |
| | |
| | 13) THE AREA WITH THE UNITS SUPPORTED OVER THE |
| | ABANDONED PORTION OF NORTHWOOD ROAD IS LABELED AS A |
| | COLONNADE. PLEASE REMOVE THIS NOMENCLATURE AS BY THE |
| | NMUD REGULATIONS THIS DOES NOT MEET THE COLONNADE |
| | ALLOWANCES, SPECIFICALLY, THE DEPTH EXCEEDS THE HEIGHT |
| | AND COLONNADES ARE NOT PERMITTED TO HAVE ENCLOSED USED |
| | ABOVE. |
| | |
| | 14) SECTION 94-209.2.J.1.H REQUIRES ARCHITECTURAL |
| | FEATURES OR ARCHITECTURAL TREATMENT ON ALL FACADE |
| | ELEVATIONS. THE BLANK WALL SHOWN ON THE EAST ELEVATION |
| | OF BUILDING C IS NOT PERMITTED. |
| | |
| | 15) AS PART OF THE REALIGNMENT OF PINEWOOD AS A PRIVATE |
| | DRIVE, STAFF WILL BE ADDING THE FOLLOWING PROVISION TO |
| | THE NMUD REGULATIONS TO ENSURE THAT ACTIVE USES AND |
| | TRANSPARENCY ARE MAINTAINED ALONG THE DRIVE. PLEASE |
| | PROVIDE THE DIMENSIONS ALONG THE WEST SIDE OF NEW |
| | PINEWOOD TO VERIFY THAT THE LANGUAGE MATCHES THE |
| | PROPOSED BUILDING DESIGN. |
| | |
| | "THE REALIGNED PORTION OF PINEWOOD AVENUE SHALL HAVE A |
| | MINIMUM OF 60 FEET BETWEEN BUILDING FACADES AND THE |
| | TRAVEL LANES SHALL NOT TOTAL MORE THAN 20 FEET IN |
| | WIDTH. SIDEWALKS AND ON-STREET PARKING SHALL BE |
| | PROVIDED. A MINIMUM OF 50 PERCENT OF THE BUILDING |
| | FRONTAGES ALONG EACH SIDE THE REALIGNED PORTION OF |
| | PINEWOOD AVENUE SHALL CONFORM TO THE GROUND FLOOR |
| | ACTIVE USE REQUIREMENTS." |
| | |
| | 16) ACCESS EASEMENT REQUIRED FOR ANY PORTIONS OF |
| | SIDEWALKS ON PRIVATE PROPERTY AND THE ROADWAYS |
| | TRAVERSING THE SITE AND THE PARKING SPACES ON PRIVATE |
| | PROPERTY. |
| | |
| | 17) SHEET A400 CUTS OFF THE ELEVATION HEIGHT DIMENSIONS |
| | UNDER THE TITLE BLOCK. PLEASE REVISE. |
| | |
| | 18) THE BUILDING A ELEVATION DRAWINGS FAIL TO SHOW THE |
| | COLUMNS/BALCONY SEPARATORS THAT ARE SHOWN ON THE FLOOR |
| | PLANS RUNNING THE FULL HEIGHT OF THE BUILDING. NOTE: |
| | THE RENDERINGS AND THE ELEVATION DRAWINGS FOR BUILDING |
| | A SHOW A NUMBER OF DIFFERENCES. |
| | |
| | STREETSCAPE |
| | |
| | 19) UPDATED COMMENT: THE SITE PLAN NEEDS TO SHOW THE |
| | ABOVE GROUND UTILITIES AND SITE FEATURES SUCH AS THE |
| | FIRE HYDRANTS, LIGHT POLES, VERIZON POLE, BOLLARDS, |
| | ETC. TO ACCURATELY REFLECT THE SITE CONDITIONS. |
| | |
| | 20) REPEAT COMMENT: NO DETAILS WERE PROVIDED ON THE |
| | SITE LIGHTING TO VERIFY COMPLIANCE WITH THE NMUD |
| | REGULATIONS. *** THIS IS REQUIRED PRIOR TO SCHEDULING A |
| | PLANNING BOARD HEARING SO THAT STAFF CAN VERIFY THAT |
| | THERE IS NO INCONSISTENCY WITH THE CODE REQUIREMENTS. |
| | THE MIXED-USE DEVELOPMENT REGULATIONS REQUIRE THAT |
| | STREETLIGHTS BE PROVIDED ALONG PUBLIC RIGHTS-OF-WAY |
| | ADJACENT TO THE SITE. CLEARLY SHOW THE PEDESTRIAN |
| | ORIENTED LIGHTING FOR THE SIDEWALKS ALONG THE SITE AND |
| | WITHIN THE PASEO ON THE PLANS. THE LANDSCAPE AND CIVIL |
| | PLANS INDICATE THAT SOME EXISTING LIGHTS WILL REMAIN, |
| | BUT NOT ALL OF THE SITE IS COVERED. |
| | |
| | 21) REPEAT COMMENT: THANK YOU FOR INCLUDING A NOTE |
| | STATING WHERE THE SIDEWALKS OR WALKWAYS CROSS THE |
| | DRIVEWAY ENTRANCES TO THE PARKING FACILITIES, LOADING |
| | AREAS, OR STREETS (BOTH PRIVATE AND PUBLIC), THE |
| | SIDEWALK OR WALKWAY IS CONTINUOUS AND REMAINS AT A |
| | CONSTANT LEVEL; HOWEVER, THIS NEEDS TO BE SHOWN IN |
| | CROSS-SECTION (OR OTHER GRAPHIC METHOD) ON THE PLANS, |
| | PREFERABLY THE CIVIL PLANS. **** STAFF IS UNABLE TO |
| | LOCATE THE CROSS-SECTION DEMONSTRATING THE CONTINUOUS |
| | SIDEWALK AT A CONSTANT LEVEL ON SHEET C2.05 AS STATED |
| | IN THE KIMLEY HORN RESPONSE LETTER. |
| | |
| | 22) UPDATED COMMENT: THE LANE WIDTH DIMENSIONS ON |
| | EITHER SIDE OF THE MEDIANS IN BROADWAY NEED TO BE |
| | PROVIDED. NEITHER THE CIVIL PLANS NOR THE ARCHITECTURAL |
| | PLANS INCLUDE THIS DIMENSION. NOTE: THE LINE WEIGHT ON |
| | SOME OF THE LAYERS ON THE ARCHITECTURAL PLANS ARE SO |
| | FAINT THAT THEY ARE UNREADABLE ? AN EXAMPLE IS THE |
| | CURBS ALONG BROADWAY. |
| | |
| | 23) UPDATED COMMENT: ROADWAY CROSS-SECTIONS. |
| | |
| | A. SECTION A-A ON SHEET C2.05 SHOWS 9.5-FOOT WIDE |
| | SIDEWALKS, WHILE THE SAME LOCATION ON SHEET A-301 SHOWS |
| | 10-FOOT WIDE SIDEWALKS. ALL PLANS MUST SHOW THE SAME, |
| | ACCURATE CONDITIONS. |
| | B. SECTION E-E ON SHEET A2.05 SHOWS A 16.5-FOOT SETBACK |
| | FOR BUILDING A, WHILE SHEET A301 SHOWS A 16-FOOT |
| | SETBACK. A 5.2-FOOT SETBACK IS SHOWN TO BUILDING B IN |
| | SECTION E-E, WHILE SHEET A200 SHOWS THE BUILDING AT THE |
| | 5-FOOT SETBACK LINE. ALL PLANS MUST SHOW THE SAME, |
| | ACCURATE CONDITIONS. |
| | C. PROVIDE THE DIMENSION FROM THE EDGE OF THE PARKING |
| | SPACES TO BUILDING B THAT IS SHOWN ON SECTION F-F ON |
| | SHEET A2.05 ON A301. NOTE: SOME OF THE DIMENSION LINES |
| | THAT WERE PREVIOUSLY SHOWN ON SHEET A301 ARE NO LONGER |
| | INCLUDED. |
| | D. SECTION E-E ON SHEET A2.05 SHOWS A 16.6-FOOT SETBACK |
| | FOR BUILDING A, WHILE SHEET A301 SHOWS A 16-FOOT |
| | SETBACK. ALL PLANS MUST SHOW THE SAME, ACCURATE |
| | CONDITIONS. |
| | |
| | 24) REPEAT COMMENT: THE EXTENSION OF BROADWAY AND |
| | CONCURRENT CLOSING OF THE VEHICULAR CONNECTIONS BETWEEN |
| | BROADWAY AND PINEWOOD RESULTS IN MORE TRAFFIC BEING |
| | ROUTED TO 23RD STREET SOUTH OF THE PROJECT. CURRENTLY |
| | 23RD STREET WEST OF THE BROADWAY EXTENSION IS ONE-WAY |
| | WEST WITH A BULB OUT TO RESTRICT THE EASTWARD FLOW OF |
| | TRAFFIC. THIS WILL NEED TO BE REMOVED AND THIS SECTION |
| | OF 23RD STREET REOPENED TO TWO-WAY TRAFFIC, WITH |
| | APPROPRIATE TRAFFIC MARKINGS. **** THE COMMENT RESPONSE |
| | STATES THAT THIS IS SHOWN ON THE CIVIL PLANS, YET IT IS |
| | NOT DEFINED IN THIS AREA. THE TRAFFIC IMPACT STATEMENT |
| | LISTS THIS A REQUIREMENT. |
| | |
| | 25) CHECK THE CLEARANCES BETWEEN THE BOLLARDS AND PASEO |
| | COLUMNS WHERE THE PASEO CROSSES PINEWOOD. YOU MAY WANT |
| | TO ADJUST THE SPACING TO ALLOW A MORE COMFORTABLE |
| | PEDESTRIAN EXPERIENCE WALKING NORTH/SOUTH. |
| | |
| | PARKING/LOADING |
| | |
| | 26) REPEAT COMMENT: PROVIDE VEHICLE TURNING RADIUS |
| | DRAWING FOR MOVING TRUCKS INTO/OUT OF THE LOADING |
| | AREAS. **** SHEET C4.01 IS THE GARBAGE TRUCK PLAN, NOT |
| | THE MOVING TRUCK PLAN. |
| | |
| | 27) THERE ARE A FEW PARKING SPACES THAT ARE ADJACENT TO |
| | WALLS THAT DO NOT APPEAR TO HAVE AN ADDITIONAL ONE FOOT |
| | TO ALLOW FOR THE OPENING OF DOORS. EITHER PROVIDE THAT |
| | THESE SPACES HAVE ADEQUATE CLEARANCE, OR THEY WILL NEED |
| | TO BE DESIGNATED AS COMPACT PARKING SPACES. THE PARKING |
| | TABLE WILL NEED TO BE UPDATED ACCORDINGLY. |
| | |
| | 28) UPDATED COMMENT: THERE ARE TWO SPACE LABELS IN THE |
| | NORTHEAST CORNER OF LEVEL 2 THAT ARE SHOWN IN CONFLICT |
| | WITH THE ELEVATOR/STAIRS. THIS NEEDS TO BE CORRECTLY |
| | SHOWN. |
| | |
| | 29) UPDATED COMMENT: DEAD END PARKING ROWS FOR CRA |
| | PARKING IS NOT PERMITTED WITHOUT A TURNAROUND SPACE. |
| | THE DEAD-END PARKING ROW ON LEVEL 1.5 THAT IS LABELED |
| | AS CRA MUST CONTAIN A TURNAROUND SPACE, DUE TO THE |
| | GATE. IT DOES NOT APPEAR THAT THE OPEN AREA ADJACENT TO |
| | THE GATE OPPOSITE THE LAST PARKING SPACE HAS SUFFICIENT |
| | AREA TO ACT AS A TURN AROUND. |
| | |
| | 30) THE NEWLY SHOWN CRA PARKING AREA ON LEVEL 1.5 IS |
| | GATED AND DOES NOT HAVE AN ADA COMPLIANT PARKING SPACE |
| | AND ACCESSIBLE ACCESS TO THE GROUND LEVEL. PROVIDE AN |
| | ADA SPACE AND ACCESSIBLE ROUTE TO THE ELEVATOR THAT |
| | DOES NOT REQUIRE THE USER TO TRAVEL BEHIND PARKED CARS. |
| | THIS WILL REQUIRE THE REMOVAL OF TWO PARKING SPACES |
| | (ONE CRA AND ONE DP). NOTE: THE ADA PARKING SPACE AND |
| | AISLE BETWEEN THE CRA AND PP ON THE NORTH HALF OF THE |
| | GARAGE MAY BE REPLACED WITH THE OTHER REMOVED CRA |
| | SPACES. |
| | |
| | 31) THE RETAIL REQUIRES 132 PARKING SPACES. THE PLAN |
| | DOES NOT SHOW SUFFICIENT PP SPACES (CRA SPACES MAY NOT |
| | BE USED) TO ACCOMMODATE THE MINIMUM REQUIREMENT. NOTE: |
| | THIS WOULD BE FURTHER REDUCED IF FDOT DOES NOT APPROVE |
| | THE DESIGN FOR BROADWAY. |
| | |
| | REGULAR PP SPACES LEVEL 1.5: 89 |
| | ADA PP SPACES LEVEL 1.5: 5 |
| | ON-STREET PP SPACES: 34 |
| | TOTAL PP SPACES: 128 |
| | |
| | 32) WHERE ARE THE 19 GUEST SPACES LOCATED WITHIN THE |
| | GARAGE AND HOW ARE THEY ACCESSED BY GUESTS? THERE IS NO |
| | CALL BOX SHOWN ON THE PLANS THAT WOULD ALLOW THE GUESTS |
| | TO CONTACT A UNIT OWNER TO BE GRANTED ACCESS TO THE |
| | GATE-CONTROLLED AREA. ANY CALL BOX NEEDS TO BE LOCATED |
| | SUCH THAT TRAFFIC FLOW AND PARKING IS NOT INHIBITED |
| | WHILE GUESTS ARE AWAITING ENTRANCE. |
| | |
| | 33) THE PARKING TABLE ON SHEET A103.3 DOES NOT MATCH |
| | THE PARKING TABLE ON SHEET A103.1, WHICH SEEMS TO |
| | CORRECTLY DEPICT WHAT IS SHOWN ON THE PLANS. ALL PAGES |
| | MUST SHOW CONSISTENT, ACCURATE, CODE COMPLIANT |
| | INFORMATION. |
| | |
| | 34) UPDATED COMMENT: THE PARKING REQUIREMENT MULTIPLIER |
| | FOR THE RESIDENTIAL PORTION OF THE PROJECT IS |
| | INCORRECTLY SHOWN AS 1 PER 20 INSTEAD OF 1 PER 10 ON |
| | THE PARKING REQUIRED TABLE. THE PROJECT REQUIRES 14 |
| | BICYCLE SPACES FOR THE COMMERCIAL PORTION (ROUND UP |
| | PARTIAL SPACES). |
| | |
| | 35) UPDATED COMMENT: THANK YOU FOR PROVIDING THE |
| | BICYCLE RACK MODEL DETAIL AND DIMENSIONS THAT WILL BE |
| | USED IN THE BICYCLE STORAGE ROOMS. THIS MODEL NEEDS TO |
| | BE SHOWN IN THE BICYCLE STORAGE ROOMS TO INCLUDE THE |
| | DIMENSIONS OF THE ROOM AND THE RACKS IN THE ROOM. |
| | |
| | 36) UPDATED COMMENT: ON-STREET BICYCLE FACILITIES ARE |
| | REQUIRED. THE DEVELOPMENT COVERS A LARGE AREA AND WHILE |
| | EMPLOYEES AND RESIDENTIAL VISITORS CAN BE EXPECTED TO |
| | USE THE BICYCLE PARKING ROOM AT THE NORTHWEST PORTION |
| | OF THE SIDE, STORE CUSTOMERS ARRIVING VIA BICYCLE WILL |
| | LOOK FOR BICYCLE PARKING CLOSE TO THE ENTRANCE OF THE |
| | STORE THEY ARE VISITING. IF NOT BICYCLE FACILITY IS |
| | IMMEDIATELY AVAILABLE, THE USER WILL CHAIN THEIR |
| | BICYCLE TO LIGHT POLES, TREES, ETC., AND OFTEN BLOCK |
| | THE PEDESTRIAN NETWORK. ON-STREET BICYCLE PAD |
| | DIMENSIONS MUST BE CLEARLY SHOWN ON THE PLANS SO THAT |
| | STAFF CAN VERIFY THAT THERE IS SUFFICIENT ROOM AND THAT |
| | SIDEWALKS ARE NOT BLOCKED. THE PADS MUST INCLUDE THE |
| | RACK(S) AND THE DIMENSIONS FROM THE RACKS TO THE EDGE |
| | OF THE PAD. FOR CLARITY THIS DETAIL SHALL BE PROVIDED |
| | AT A BIGGER SCALE. NOTE: THE HARDSCAPE PLAN SHOWS |
| | ON-STREET BICYCLE RACKS; HOWEVER, NO DIMENSIONS ARE |
| | PROVIDED TO VERIFY THE COMMENTS ABOVE. |
| | |
| | 37) REPEAT COMMENT: PROVIDE THE DIMENSIONS FROM THE |
| | MICRO MOBILITY STATIONS TO THE PROPOSED PLAZA LANDSCAPE |
| | AREAS SO STAFF CAN VERIFY THE PEDESTRIAN CLEARANCES. |
| | **** THE DIMENSIONS WERE NOT PROVIDED SO STAFF IS |
| | UNABLE TO VERIFY THE PEDESTRIAN CLEARANCE. |
| | |
| | LANDSCAPE |
| | |
| | 38) UPDATED COMMENT: THE ARCHITECTURAL, LANDSCAPE AND |
| | CIVIL PLANS DO NOT SHOW THE SAME BASE PLANTING |
| | CONDITIONS FOR THE COLUMNS ALONG PINEWOOD. ALL OF THE |
| | COLUMNS NEED TO HAVE THE BASE PLANTINGS. |
| | |
| | 39) PUBLIC OPEN SPACE CALCULATION ON SHEET A102.0 |
| | COUNTS MORE AREA THAN IS DEFINED AS PUBLIC OPEN SPACE. |
| | THE BREAKDOWN ON SHEET L1.02 NEEDS TO BE PROVIDED ON |
| | SHEET A102.0 SO THAT IT IS CLEAR THAT THERE IS 10,000+ |
| | SF OF COMPLIANT PUBLIC OPEN SPACE. |
| | |
| | WAIVERS/VARIANCES |
| | |
| | 40) THE MAXIMUM HORIZONTAL DIMENSION OF A BUILDING |
| | WITHIN THE MIXED USE DISTRICTS IS 250 FEET. BUILDING A |
| | EXCEEDS THIS ON ALL FRONTAGES. PLEASE PROVIDE THE FULL |
| | DIMENSION OF LEVEL 2 ON ALL ELEVATIONS AS THIS IS THE |
| | LARGEST FLOORPLATE. **** VARIANCE REQUIRED. |
| | |
| | 41) THE MAXIMUM LOT WIDTH FOR FLEX BUILDINGS IS 200 |
| | FEET AND TOWER BUILDINGS IS 250 FEET. THE LOT |
| | CONTAINING BUILDINGS A AND B EXCEEDS THIS BASED ON THE |
| | ABANDONMENT OF PINEWOOD AND NORTHWOOD ROAD AND THE |
| | BLOCK NO LONGER BOUNDED ON ALL SIDES BY STREETS OR RR. |
| | **** VARIANCE REQUIRED. |
| | |
| | 42) THE ADDITIONAL ABANDONMENT OF PINEWOOD AND |
| | NORTHWOOD ROAD RESULTS IN EXCEEDING THE MAXIMUM BLOCK |
| | LENGTH AND PERIMETER DIMENSION. PROVIDE THE PERIMETER |
| | DIMENSION OF THE PARCEL THAT CONTAINS BUILDINGS A AND |
| | B. **** VARIANCE REQUIRED. |
| | |
| | 43) THE NMUD REGULATIONS LIMIT THE TOWER FLOOR PLATE TO |
| | 30,000 SQUARE FEET FOR ANY SINGLE FLOORPLATE WITH AND |
| | AVERAGE FLOORPLATE OF UP TO 20,000 SQUARE FEET. THE |
| | MAXIMUM TOWER FLOORPLATES ARE SHOWN AT 45,450 SQUARE |
| | FEET. THE NMUD FLOOR PLATE AVERAGE ONLY APPLIES TO THE |
| | TOWER PORTION OF BUILDINGS WITHIN THE CORE SUBDISTRICT. |
| | **** VARIANCE REQUIRED. |
| | |
| | 44)THE ACTIVE USE LINER REQUIRED BY SECTION |
| | 94-209.J.1.G.II. REQUIRED FOR THE FULL LENGTH OF THE |
| | GROUND FLOOR IS NOT ACHIEVED FOR THE AREAS LISTED |
| | BELOW. **** VARIANCES REQUIRED. |
| | |
| | A. BUILDING A ALONG 25TH STREET AT THE FIRE COMMAND |
| | ROOM. PROVIDE THE DIMENSION OF THIS AREA ALONG 25TH |
| | STREET. |
| | B. BUILDING A ALONG THE GARDEN PLAZA AT THE STAIRS. |
| | PROVIDE THE DIMENSION OF THIS AREA ALONG THE SOUTH SIDE |
| | OF THE STAIRS AS WELL AS THE SOUTH SIDE OF THE ADJACENT |
| | RETAIL AREA. |
| | C. BUILDING B ALONG 23RD STREET AT THE BOH AND TRASH |
| | ROOM. PROVIDE THE DIMENSION OF THIS AREA ALONG 23RD |
| | STREET. |
| | |
| | 45) UPDATED COMMENT: SECTION 94-209.E.2.B.I. REQUIRES |
| | THAT ALL LEVELS OF THE PARKING GARAGE MUST BE SCREENED |
| | BY A LINER BUILDING CONTAINING A MINIMUM DEPTH OF 20 |
| | FEET OF HABITABLE SPACE. THIS IS NOT MET ALONG THE FULL |
| | LENGTH OF 25TH STREET. **** A VARIANCE FROM THIS CODE |
| | REQUIREMENT IS NEEDED. PLEASE PROVIDE THE DIMENSION FOR |
| | PARKING LEVELS 1.5 AND 2, MEASURED FROM THE WEST SIDE |
| | OF THE CORRIDOR TO THE WESTERN BUILDING WALL. ALSO |
| | PROVIDE THE DIMENSION FORM THE WEST SIDE OF THE |
| | CORRIDOR TO THE WEST WALL OF UNIT 18. THE REMAINDER IS |
| | THE UNSCREENED PORTION OF THE GARAGE AND WILL BE THE |
| | WAIVER THAT YOU ARE REQUESTING FROM THE 100% SCREENING |
| | REQUIREMENT. PLEASE ALSO PROVIDE THE DEPTH OF UNIT 18 |
| | FROM 25TH STREET SO THAT STAFF CAN VERIFY THAT YOU ARE |
| | MEETING THE 20 FOOT OF HABITABLE SPACE AND THAT ANOTHER |
| | WAIVER IS NOT REQUIRED. |
| | |
| | 46) UPDATED COMMENT: SECTION 94-209.2.A.IV. REQUIRES |
| | THAT ALL PARKING GARAGES MUST HAVE DIRECT PEDESTRIAN |
| | ACCESS TO A PUBLIC WALKWAY. NONE OF THE PARKING SPACES |
| | APPEAR TO HAVE DIRECT ACCESS TO A PUBLIC WALKWAY. THE |
| | PP AND CRA SPACES ON THE NORTH SIDE OF THE GARAGE LEVEL |
| | 1.5 USE AN ELEVATOR THAT THE FUTURE PUBLIC ACCESS |
| | EASEMENT ALONG THE NEW PINEWOOD. THE CRA SPACE ON THE |
| | SOUTH SIDE OF THE GARAGE LEVEL 1.5 HAVE EMERGENCY |
| | ACCESS TO THE RAILROAD, WHICH IS NOT A PUBLIC WALKWAY. |
| | EVEN UPON MODIFICATION TO ACCOMMODATE ADA, THESE USERS |
| | WILL GO THROUGH THE LOBBY PRIOR TO GETTING TO A PUBLIC |
| | ACCESS EASEMENT AREA (PASEO OR PINEWOOD). WHILE THE |
| | RESIDENTS THAT HAVE ACCESS TO THE LINER UNIT CORRIDOR |
| | WILL HAVE ACCESS TO THE JUMP LOBBIES, WHICH ARE |
| | DIRECTLY ON A PUBLIC WALKWAY, IT IS UNCLEAR IF THE |
| | RESIDENTS OF THE TOWER WILL HAVE ACCESS TO THESE AREAS |
| | AS WELL. THE RESIDENT ONLY, LIMITED ACCESS TO THE JUMP |
| | LOBBIES DOES NOT QUALIFY AS THE GARAGES HAVING DIRECT |
| | ACCESS. **** A WAIVER OF THIS CODE PROVISION IS |
| | REQUIRED. AS PART OF THE WAIVER, ALL UNIT OWNERS WOULD |
| | NEED TO BE ABLE TO UTILIZE THE ELEVATORS AND STAIRS |
| | THAT ACCESS THE JUMP LOBBIES. |
| | |
| |