| 2022-07-01 14:13:24 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE |
| | 5/27/2022 SUBMITTAL. |
| | |
| | 1. [PARTIALLY SATISFIED] LABEL ALL THE STREETS ON ALL |
| | OF THE SHEETS. FOR EXAMPLE, SHEET C1.01 ONLY LABELS |
| | PINEWOOD AVE. NONE OF THE EAST-WEST STREETS ARE |
| | LABELED. NEW COMMENT ? ON SHEET C3.01 LABEL PINEWOOD |
| | AVE NORTH AND SOUTH OF 25TH ST. |
| | |
| | 2. [SATISFIED] COMPLETE THE PAVING, GRADING AND |
| | DRAINAGE NOTES ON THE PGD PLAN SHEETS. SOME OF THE |
| | NOTES DO NOT AGREE WITH THE VERTICAL DATUM LABEL AT THE |
| | BOTTOM OF THE SHEETS. |
| | |
| | 3. [SATISFIED - EXFILTRATION TRENCH ON THE EAST SIDE OF |
| | BROADWAY AVE SHOULD BE SET BACK FROM THE RIGHT OF WAY |
| | TO ENSURE THE TRENCH DOES NOT ENCROACH INTO THE RIGHT |
| | OF WAY DURING CONSTRUCTION.] EXFILTRATION TRENCH FOR |
| | TREATING RUNOFF FROM ONSITE AREAS SHALL NOT BE LOCATED |
| | WITHIN THE RIGHT OF WAY. |
| | |
| | 4. [SATISFIED] ON SHEET C2.03 THERE IS A NEW DRAINAGE |
| | STRUCTURE ON THE EAST SIDE OF PINEWOOD AVE ABOUT 40 |
| | FEET NORTH OF THE CENTERLINE OF NORTHWOOD ROAD. THIS |
| | INLET IS SHOWN NEXT TO AN EXISTING INLET THAT IS BEING |
| | CONVERTED TO A VALLEY GUTTER INLET. IS THE NEW INLET |
| | NEEDED? |
| | |
| | 5. [SATISFIED] WHAT WILL BE THE MAXIMUM CROSS SLOPE OF |
| | THE ON-STREET PARKING SPACES? |
| | |
| | 6. [SATISFIED - REVIEW SECTION F-F] LABEL THE PARKING |
| | AREAS ON THE CROSS SECTIONS. |
| | |
| | 7. [SATISFIED] ADVISE IF THE WEST DROP CURB ON PINEWOOD |
| | AVE WILL BE PARALLEL TO THE WEST RIGHT OF WAY. THE 9.0 |
| | FT DIMENSION ON SECTION B-B DOES NOT APPEAR TO REACH |
| | THE 2 FEET DROP CURB. |
| | |
| | 8. [SATISFIED] SIDEWALK CROSS SLOPES SHALL NOT EXCEED 2 |
| | PERCENT. |
| | |
| | 9. [SATISFIED] THE DIMENSIONS FOR THE PARKING AREAS ON |
| | SECTION D-D AND SECTION E-E (FOR BROADWAY AVE) APPEAR |
| | TO INCLUDE THE TYPE 'D' CURB. |
| | |
| | 10. [SATISFIED] EXTEND SECTION F-F TO THE PARKING LOT |
| | ON THE WEST SIDE OF PINEWOOD AVE. DIMENSION THE |
| | SIDEWALKS, CURB AND GUTTER, TRAVEL LANES AND PARKING |
| | AREA. |
| | |
| | 11. [SATISFIED] DIMENSION MINIMUM BUILDING SETBACKS ON |
| | THE CROSS SECTIONS. |
| | |
| | 12. [SATISFIED - SHOW CROSS SECTION SYMBOL ON SHEET |
| | C2.04] PROVIDE CROSS SECTION OF BROADWAY AVE SOUTH OF |
| | NORTHWOOD ROAD. EXTEND SECTION FROM FACE OF BUILDING TO |
| | FACE OF BUILDING. DIMENSION SIDEWALKS, CURB AND GUTTER, |
| | PARKING AREAS, TRAVEL LANES, SETBACKS FROM R/W, ETC. |
| | |
| | 13. [NOT SATISFIED - INCLUDE PARKING STRIPING DETAIL |
| | WITH THE ENGINEERING PERMIT SUBMITTAL] REVISE THE |
| | PARKING SPACE STRIPING DETAIL TO MATCH CITY CODE. |
| | |
| | 14. [SATISFIED] THE CITY DOES NOT ALLOW THE USE OF |
| | BLEEDERS WITH EXFILTRATION TRENCHES. |
| | |
| | 15. [SATISFIED - CAN HATCHING OR BOLD BORDER BE ADDED |
| | ON SHEET C1.00 SHOWING THE ROWS TO BE ABANDONED?] LABEL |
| | RIGHT OF WAYS PROPOSED TO BE ABANDONED ON THE PLAN |
| | SHEETS. |
| | |
| | 16. [NOT SATISFIED] RCP PIPE (MINIMUM 15 INCHES IN |
| | DIAMETER) TO BE INSTALLED WITHIN THE RIGHT OF WAY. NEW |
| | COMMENT ? NOT ALL PIPES ARE LABELED. PROPOSED STORM |
| | PIPES ON 25TH ST AT BROADWAY, ON BROADWAY AVE AT 24TH |
| | ST., BROADWAY AT NORTHWOOD RD LABELED AS 18" HDPE. |
| | |
| | NEW COMMENTS: |
| | |
| | 17. INDICATE HOW THE EXISTING CATCH BASIN ON THE SOUTH |
| | SIDE OF 23RD ST EAST OF PINEWOOD DRIVE WILL CONNECT TO |
| | THE MS4. |
| | |
| | 18. PROVIDE PRE- AND POST-DEVELOPMENT HGL CALCULATIONS |
| | FOR THE DRAINAGE SYSTEM ON BROADWAY AND 23RD STREET |
| | WITH THE ENGINEERING PERMIT SUBMITTAL. |
| | |
| | 19. REVIEW DESIGN PLANS IN SFWMD PERMITS FOR 24TH ST |
| | AND 25TH ST AND OTHER PROJECTS IN THE VICINITY FOR |
| | STORM PIPE CONNECTIVITY. THE INLET ON THE SOUTH SIDE OF |
| | 24TH ST EAST OF BROADWAY MAY BE CONNECTED TO A MANHOLE |
| | SOUTH OF THE STRUCTURE INSTEAD OF THE MANHOLE ON |
| | BROADWAY AVE. |
| | |
| | 20. ADDITIONAL GRADES WILL BE NEEDED FOR THE |
| | ENGINEERING PERMIT SUBMITTAL. |
| | |
| | 21. THE FINISHED FLOOR ELEVATIONS AND SPOT GRADES ON |
| | THE PGD PLANS PROVIDED WHERE THE CROSS SECTION SYMBOLS |
| | ARE WILL RESULT IN CROSS SLOPES STEEPER THAN THE MAX. |
| | 2% SHOWN ON THE CROSS SECTIONS FOR THE PARKING AREA AND |
| | ALLOWED FOR THE SIDEWALK AREA. |
| | |
| | 22. WILL THERE BE PEDESTRIAN ACCESS TO THE SOUTH SIDE |
| | OF 23RD STREET AT THE PINEWOOD AND BROADWAY |
| | INTERSECTIONS? SHOW CROSS WALKS AND CURB RAMPS. |
| | |
| | 23. ALL CURB RAMPS WILL NEED TO BE BROUGHT UP TO |
| | CURRENT ADA STANDARDS IF THE PAVEMENT ADJACENT TO THE |
| | CURB RAMP IS DISTURBED OR OVERLAID. |
| | |
| | 24. ADA MATS MAY BE NEEDED WHERE THE SIDEWALKS MEET |
| | DRIVEWAYS FOR THE GARAGES OR ALLEYS. |
| | |
| | 25. SHEET C3.05: |
| | A. BUILDING A (NORTHWEST) SERVICE - |
| | 1. CONFIRM PROPOSED 3" WATER SERVICE WILL CROSS AN 8" |
| | PVC SANITARY SEWER MAIN. |
| | 2. CONFIRM TAP IS TO A 24" WM. |
| | |
| | B. BUILDING A (NORTHEAST) SERVICE - SHOW THE |
| | EXFILTRATION TRENCH. |
| | |
| | C. BUILDING A (SOUTHWEST) SERVICE - CONFIRM THE WATER |
| | SERVICE WILL CROSS 15" RCP STORM AND 8" PVC SEWER. |
| | |
| | D. BUILDING B SERVICE - SHOW PROPOSED STORM PIPE |
| | BETWEEN EXISTING INLETS. |
| | |
| | E. BUILDING A (SOUTHWEST) SERVICE - |
| | 1. SHOULD BE LABELED SOUTHEAST? |
| | 2. CONFIRM RCP STORM VS. HDPE STORM. |
| | |
| | 26. SHOW BREAKS IN THE EXFILTRATION TRENCH IF WATER OR |
| | SEWER SERVICE LINES WILL CROSS IN THE ENVELOPE OF THE |
| | EXFILTRATION TRENCH. |
| | |
| | 27. PROVIDE DETAILS OF THE CONTROL STRUCTURES WITH THE |
| | ENGINEERING PERMIT SUBMITTAL. |
| | |
| | 28. SECTION B-B - LEFT SIDE OF SECTION IS LABELED AS |
| | 18.4 FEET LANDSCAPING. WILL THERE BE A CONTINUOUS |
| | SIDEWALK ON THE WEST SIDE OF THE STREET? |
| | |
| | 29. SECTION E-E - CONFIRM 2.5 FEET DIMENSION FOR THE |
| | TYPE 'F' CURB. SUM OF DIMENSIONS ACROSS RIGHT OF WAY IS |
| | LESS THAN 75 FEET. |
| | |
| | 30. SECTION H-H - CONFIRM 2.5 FEET DIMENSION FOR THE |
| | TYPE 'F' CURB. SUM OF DIMENSIONS ACROSS RIGHT OF WAY IS |
| | MORE THAN 55 FEET. |
| | |
| | TRACY WARD, PE |
| | SENIOR STORMWATER ENGINEER |
| | ENGINEERING SERVICES DEPARTMENT |
| | 561-494-1120 (O) |
| | [email protected] |
| | |
| |