Plan Review Notes
Plan Review Notes For Project Z21080015
Project Number Z21080015
Review Stop PU-CS
Sequence Number 3
Notes
Date Text
2022-07-29 08:26:38PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
  
 -SEE IF CAN ADJUST NORTHWEST PROPOSED SEWER LATERAL
 SLIGHTLY TO THE EAST TO ELIMINATE EXTRA ROOT BARRIER AT
 TREE TRUNK.
 -AT BOTTOM OF L1.00 THERE IS A LEADER LINE WITH NO
 LABEL. ADD LABEL AND VERIFY OBJECT DOES NOT CONFLICT
 WITH PROPOSED METERED WATER SERVICE THERE.
 -IN PRIOR REVISIONS OF CIVIL PLANS THERE WAS A SEPARATE
 8 INCH FIRELINE WITH DCDA FOR THE NORTHWEST BUILDING,
 BUT CURRENT REVISION DOES NOT SHOW IT ANYMORE. PLEASE
 PROVIDE MORE INFORMATION ON WHY IT IS NOT THERE
 ANYMORE.
 -METERS 2 INCHES AND SMALLER ARE INSTALLED UNDERGROUND
 IN A METER BOX. CAN UPDATE CIVIL PLANS AT ENGINEERING
 DEVELOPMENT SUBMITTAL.
 -AT ENGINEERING DEVELOPMENT SUBMITTAL: PROVIDE PROFILES
 FOR FIRELINES; UPDATE VALVE AND REDUCER ON C3.04 SO NOT
 IN CROSSWALK AND PROPERLY LABELED.
 -LANDSCAPE PLAN SHOWS PLANTS OVER NORTHEAST FPL VAULT.
 -L2.00 SHOWS AT LEAST A COUPLE PROPOSED BIKE RACKS ON
 TOP OF FPL VAULTS. RECOMMEND SHOWING FPL VAULTS IN
 BACKGROUND OF L2.00.
  
 RESPECTFULLY,
 MARK HURLEY
 [email protected]