Plan Review Notes
Plan Review Notes For Project Z21080015
Project Number Z21080015
Review Stop ENG - PPRC
Sequence Number 3
Notes
Date Text
2022-06-12 12:38:18COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR, ENG.
 SERVICES DEPT., 561-494-1098 [email protected] :
  
 PLEASE ADDRESS SECOND PART OF COMMENT 6: VERIFY THAT
 THERE ARE NO STRUCTURES WITHIN EASEMENT.
 PLEASE LABEL ALL STREETS AND ALLEYS ON ALL CIVIL
 SHEETS.
 DEMO SHEETS:
 UPDATE DEMO NOTE 13 TO REFER TO CITY OF WEST PALM
 BEACH.
 ADD NOTE TO ALL DEMO SHEETS TO PROTECT STORMWATER
 INLETS USING BMPS.
 PLEASE PROVIDE A SUMMARY OF SCOPE CHANGE IN THE NEXT
 RESUBMITTAL.
  
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-494-2262 OR
 [email protected]:
  
 -SHEET C3.01. SOME CALLOUTS ARE GOING OFF TOP OF SHEET
 AND UNREADABLE. PLEASE CORRECT.
  
 -CALLOUT REPLACEMENT OF FIRE HYDRANT AND PIPE LEADING
 TO IT AT FAR NORTH SIDE OF SHEET C3.01. ALSO SHOW GATE
 VALVE AND LABEL THE FITTING AT WATER MAIN.
  
 -AT FORMAL ENGINEERING SUBMITTAL: LABEL ALL WATER
 SERVICES WITH PIPE SIZE AND MATERIAL TYPE; ADD GATE
 VALVE AT 25TH ST WHERE PROPOSED 8 INCH DIP RUNNING WEST
 TIES INTO EXISTING NORTH SOUTH DIP; LABEL EXISTING FM
 NORTH OF 25TH ST WITH PIPE SIZE AND MATERIAL TYPE; SHOW
 ALL WATER MAIN GATE VALVES AT 25TH AND PINEWOOD
 INTERSECTION; ADD INVERT AND RIM ELEVATIONS TO ALL
 EXISTING AND PROPOSED SANITARY SEWER MANHOLES; SHOW ALL
 EXISTING WATER SERVICES AND LABEL WHAT IS HAPPENING TO
 THEM (ESPECIALLY WATER SERVICE TAPS FOR NEIGHBORS THAT
 MAY RESTRICT PROPOSED TAPS); VERIFY FORCE MAIN
 DIRECTION OF FLOWL;
  
 -EXISTING 8 INCH DIP IN 25TH ST INTERSECTION SHOWS AS
 1926 8 INCH CAS IN WPB GIS. PLEASE VERIFY AT FORMAL
 ENGINEERING SUBMITTAL. IF 1926 MAY NEED TO BE REPLACED
 UPON REVIEW AND DIRECTION OF CITY OR EOR.
  
 -DCDAS ON 25TH ST ARE IN THE RIGHT OF WAY. THEY ARE
 SUPPOSED TO BE ON PRIVATE PROPERTY.
  
 -VERIFY ALL PROPOSED FDC LOCATIONS ARE ACCEPTABLE
 DISTANCE FROM FIRE HYDRANTS. SEE AT LEAST ONE THAT MAY
 NOT BE.
  
 -EXISTING SANITARY SEWER MANHOLE AND PIPING NORTH OF IT
 AT INTERSECTION OF 25TH AND PINEWOOD SAYS 1926 IN WPB
 GIS MAY NEED TO BE IMPROVED UPON REVIEW OF CITY OR EOR
 AT FORMAL ENGINEERING SUBMITTAL.
  
 -METER SIZE IS NOT CLEARLY SHOWN, BUT 3 INCH METERS
 SHOULD HAVE 4 INCH TAPS AND SERVICE LINES PER WPB
 STANDARD DETAILS.
  
 -THE NE AREA OF BROADWAY AND 25TH INTERSECTION APPEARS
 TO BE FDOT ROW.
  
 -FIRE HYDRANT GATE VALVE LOCATED ADJACENT TACTILE PAD
 ON BROADWAY. PLEASE RELOCATE. PREFER ADJACENT FIRE
 HYDRANT IN LANDSCAPING IF POSSIBLE.
  
 -CHECK POSITION OF FPL MANHOLE AT INTERSECTION OF 25TH
 AND BROADWAY TO CONFIRM WILL NOT CONFLICT WITH
 STORMWATER PIPING NEXT TO IT.
  
 -FIRELINE BACKFLOW ON 24TH ST EAST OF BROADWAY IS IN
 PEDESTRIAN TRAFFIC AND ALSO IN THE RIGHT OF WAY.
 RELOCATE TO PRIVATE PROPERTY AND OUT OF PEDESTRIAN
 TRAFFIC.
  
 -SHOW PAVEMENT RESTORATION ON 24TH ST EAST OF BROADWAY.
  
 -FIRELINE BACKFLOW ON BROADWAY IS IN RIGHT OF WAY.
 RELOCATE TO PRIVATE PROPERTY.
  
 -PAVEMENT RESTORATION BOUNDARIES ON 23RD ST ARE NOT
 SUFFICIENT FOR THE PROPOSED UTILITY WORK.
  
 -FOR FAR SOUTHWEST WATER SERVICE, WILL NEED TO GO TO
 THE MAIN. EXISTING WATER SERVICE IS SMALL DIAMETER.
  
 -EXISTING 24 INCH WATER MAIN ON 23RD ST NEAR AREAS OF
 PROPOSED WATER SERVICE TAPS IS LABELED 1926 AGE IN WPB
 GIS AND A LARGER WATER MAIN. WOULD NEED APPROVAL FROM
 MICHAEL TECHNOW TO CONNECT TO THE WATER MAINS THERE,
 AND EXISTING 24 INCH WATER MAIN MAY NEED TO BE REPLACED
 UPON REVIEW OF CITY OR EOR AT FORMAL ENGINEERING
 SUBMITTAL.
  
 -SHEET C3.03. PROPOSED WATER SERVICES AND DOMESTIC
 METER EAST OF PINEWOOD APPEAR TO BE IN CONFLICT WITH A
 UTILITY POLE.
  
 -SHOW AND LABEL UTILITY EASEMENTS FOR DOMESTIC METERED
 WATER SERVICES. MANY ARE MISSING.
  
 -FIRE HYDRANT AND PIPE TO IT WILL NEED REPLACEMENT.
 CONSIDER RELOCATING IT TO DIFFERENT LANDSCAPING AREA
 OUT OF SIDEWALK.
  
 -CALLOUT HORIZONTAL DISTANCE BETWEEN FM AND WM ON 23RD
 ST.
  
 -FOOTPRINT OF ABOVE GROUND METERS MAY BE LARGER THAN
 SHOWN ON PLANS. MAY BE NECESSARY TO ROTATE THEM OR
 INCREASE PLANTER WIDTH SO THEY WILL FIT.
  
 -THERE ARE SOME WATER UTILITY CONFLICTS WITH
 LANDSCAPING ON BROADWAY. SEE A TREE ON TOP OF A WATER
 PIPE AS WELL AS A FIRELINE BACKFLOW IN CLOSE PROXIMITY
 TO A TREE TRUNK. PLEASE CHECK PLANS FOR UTILITY
 LANDSCAPING CONFLICTS AND RESOLVE.
  
 -SHOW AND LABEL THE PROPOSED ROAD AREA BETWEEN 23RD AND
 NORTHWOOD THAT IS INTENDED TO BE DEDICATED TO THE CITY.
  
 -COULD NOT FIND ANY INFORMATION ON IRRIGATION WATER.
 WILL IRRIGATION BE FED FROM THE DOMESTIC WATER
 SERVICES?
  
 -CLEARLY SHOW AND LABEL ALL DOMESTIC BACKFLOW
 ASSEMBLIES. THEY SHOULD ALL BE ON PRIVATE PROPERTY,
 CLOSE TO METERS, OUTSIDE OF BUILDINGS, OUT OF UTILITY
 EASEMENTS, AND AWAY FROM PEDESTRIAN TRAFFIC. FOR
 IMPORTANT WATER SERVICES CONSIDER DUAL/PARALLEL
 ASSEMBLIES TO MINIMIZE WATER OUTAGES DURING BACKFLOW
 MAINTENANCE.
  
  Print


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved