| 2022-06-12 12:38:18 | COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR, ENG. |
| | SERVICES DEPT., 561-494-1098 [email protected] : |
| | |
| | PLEASE ADDRESS SECOND PART OF COMMENT 6: VERIFY THAT |
| | THERE ARE NO STRUCTURES WITHIN EASEMENT. |
| | PLEASE LABEL ALL STREETS AND ALLEYS ON ALL CIVIL |
| | SHEETS. |
| | DEMO SHEETS: |
| | UPDATE DEMO NOTE 13 TO REFER TO CITY OF WEST PALM |
| | BEACH. |
| | ADD NOTE TO ALL DEMO SHEETS TO PROTECT STORMWATER |
| | INLETS USING BMPS. |
| | PLEASE PROVIDE A SUMMARY OF SCOPE CHANGE IN THE NEXT |
| | RESUBMITTAL. |
| | |
| | |
| | COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE |
| | SUPER., WPB PUBLIC UTILITIES, 561-494-2262 OR |
| | [email protected]: |
| | |
| | -SHEET C3.01. SOME CALLOUTS ARE GOING OFF TOP OF SHEET |
| | AND UNREADABLE. PLEASE CORRECT. |
| | |
| | -CALLOUT REPLACEMENT OF FIRE HYDRANT AND PIPE LEADING |
| | TO IT AT FAR NORTH SIDE OF SHEET C3.01. ALSO SHOW GATE |
| | VALVE AND LABEL THE FITTING AT WATER MAIN. |
| | |
| | -AT FORMAL ENGINEERING SUBMITTAL: LABEL ALL WATER |
| | SERVICES WITH PIPE SIZE AND MATERIAL TYPE; ADD GATE |
| | VALVE AT 25TH ST WHERE PROPOSED 8 INCH DIP RUNNING WEST |
| | TIES INTO EXISTING NORTH SOUTH DIP; LABEL EXISTING FM |
| | NORTH OF 25TH ST WITH PIPE SIZE AND MATERIAL TYPE; SHOW |
| | ALL WATER MAIN GATE VALVES AT 25TH AND PINEWOOD |
| | INTERSECTION; ADD INVERT AND RIM ELEVATIONS TO ALL |
| | EXISTING AND PROPOSED SANITARY SEWER MANHOLES; SHOW ALL |
| | EXISTING WATER SERVICES AND LABEL WHAT IS HAPPENING TO |
| | THEM (ESPECIALLY WATER SERVICE TAPS FOR NEIGHBORS THAT |
| | MAY RESTRICT PROPOSED TAPS); VERIFY FORCE MAIN |
| | DIRECTION OF FLOWL; |
| | |
| | -EXISTING 8 INCH DIP IN 25TH ST INTERSECTION SHOWS AS |
| | 1926 8 INCH CAS IN WPB GIS. PLEASE VERIFY AT FORMAL |
| | ENGINEERING SUBMITTAL. IF 1926 MAY NEED TO BE REPLACED |
| | UPON REVIEW AND DIRECTION OF CITY OR EOR. |
| | |
| | -DCDAS ON 25TH ST ARE IN THE RIGHT OF WAY. THEY ARE |
| | SUPPOSED TO BE ON PRIVATE PROPERTY. |
| | |
| | -VERIFY ALL PROPOSED FDC LOCATIONS ARE ACCEPTABLE |
| | DISTANCE FROM FIRE HYDRANTS. SEE AT LEAST ONE THAT MAY |
| | NOT BE. |
| | |
| | -EXISTING SANITARY SEWER MANHOLE AND PIPING NORTH OF IT |
| | AT INTERSECTION OF 25TH AND PINEWOOD SAYS 1926 IN WPB |
| | GIS MAY NEED TO BE IMPROVED UPON REVIEW OF CITY OR EOR |
| | AT FORMAL ENGINEERING SUBMITTAL. |
| | |
| | -METER SIZE IS NOT CLEARLY SHOWN, BUT 3 INCH METERS |
| | SHOULD HAVE 4 INCH TAPS AND SERVICE LINES PER WPB |
| | STANDARD DETAILS. |
| | |
| | -THE NE AREA OF BROADWAY AND 25TH INTERSECTION APPEARS |
| | TO BE FDOT ROW. |
| | |
| | -FIRE HYDRANT GATE VALVE LOCATED ADJACENT TACTILE PAD |
| | ON BROADWAY. PLEASE RELOCATE. PREFER ADJACENT FIRE |
| | HYDRANT IN LANDSCAPING IF POSSIBLE. |
| | |
| | -CHECK POSITION OF FPL MANHOLE AT INTERSECTION OF 25TH |
| | AND BROADWAY TO CONFIRM WILL NOT CONFLICT WITH |
| | STORMWATER PIPING NEXT TO IT. |
| | |
| | -FIRELINE BACKFLOW ON 24TH ST EAST OF BROADWAY IS IN |
| | PEDESTRIAN TRAFFIC AND ALSO IN THE RIGHT OF WAY. |
| | RELOCATE TO PRIVATE PROPERTY AND OUT OF PEDESTRIAN |
| | TRAFFIC. |
| | |
| | -SHOW PAVEMENT RESTORATION ON 24TH ST EAST OF BROADWAY. |
| | |
| | -FIRELINE BACKFLOW ON BROADWAY IS IN RIGHT OF WAY. |
| | RELOCATE TO PRIVATE PROPERTY. |
| | |
| | -PAVEMENT RESTORATION BOUNDARIES ON 23RD ST ARE NOT |
| | SUFFICIENT FOR THE PROPOSED UTILITY WORK. |
| | |
| | -FOR FAR SOUTHWEST WATER SERVICE, WILL NEED TO GO TO |
| | THE MAIN. EXISTING WATER SERVICE IS SMALL DIAMETER. |
| | |
| | -EXISTING 24 INCH WATER MAIN ON 23RD ST NEAR AREAS OF |
| | PROPOSED WATER SERVICE TAPS IS LABELED 1926 AGE IN WPB |
| | GIS AND A LARGER WATER MAIN. WOULD NEED APPROVAL FROM |
| | MICHAEL TECHNOW TO CONNECT TO THE WATER MAINS THERE, |
| | AND EXISTING 24 INCH WATER MAIN MAY NEED TO BE REPLACED |
| | UPON REVIEW OF CITY OR EOR AT FORMAL ENGINEERING |
| | SUBMITTAL. |
| | |
| | -SHEET C3.03. PROPOSED WATER SERVICES AND DOMESTIC |
| | METER EAST OF PINEWOOD APPEAR TO BE IN CONFLICT WITH A |
| | UTILITY POLE. |
| | |
| | -SHOW AND LABEL UTILITY EASEMENTS FOR DOMESTIC METERED |
| | WATER SERVICES. MANY ARE MISSING. |
| | |
| | -FIRE HYDRANT AND PIPE TO IT WILL NEED REPLACEMENT. |
| | CONSIDER RELOCATING IT TO DIFFERENT LANDSCAPING AREA |
| | OUT OF SIDEWALK. |
| | |
| | -CALLOUT HORIZONTAL DISTANCE BETWEEN FM AND WM ON 23RD |
| | ST. |
| | |
| | -FOOTPRINT OF ABOVE GROUND METERS MAY BE LARGER THAN |
| | SHOWN ON PLANS. MAY BE NECESSARY TO ROTATE THEM OR |
| | INCREASE PLANTER WIDTH SO THEY WILL FIT. |
| | |
| | -THERE ARE SOME WATER UTILITY CONFLICTS WITH |
| | LANDSCAPING ON BROADWAY. SEE A TREE ON TOP OF A WATER |
| | PIPE AS WELL AS A FIRELINE BACKFLOW IN CLOSE PROXIMITY |
| | TO A TREE TRUNK. PLEASE CHECK PLANS FOR UTILITY |
| | LANDSCAPING CONFLICTS AND RESOLVE. |
| | |
| | -SHOW AND LABEL THE PROPOSED ROAD AREA BETWEEN 23RD AND |
| | NORTHWOOD THAT IS INTENDED TO BE DEDICATED TO THE CITY. |
| | |
| | -COULD NOT FIND ANY INFORMATION ON IRRIGATION WATER. |
| | WILL IRRIGATION BE FED FROM THE DOMESTIC WATER |
| | SERVICES? |
| | |
| | -CLEARLY SHOW AND LABEL ALL DOMESTIC BACKFLOW |
| | ASSEMBLIES. THEY SHOULD ALL BE ON PRIVATE PROPERTY, |
| | CLOSE TO METERS, OUTSIDE OF BUILDINGS, OUT OF UTILITY |
| | EASEMENTS, AND AWAY FROM PEDESTRIAN TRAFFIC. FOR |
| | IMPORTANT WATER SERVICES CONSIDER DUAL/PARALLEL |
| | ASSEMBLIES TO MINIMIZE WATER OUTAGES DURING BACKFLOW |
| | MAINTENANCE. |
| | |
| |