2022-04-13 15:15:38-CORRECT PIPE DIMENSIONS ON PINEWOOD. THERE IS AN
 EXISTING 8? WM.
 -UPSIZE THE 6? WM ON 25TH ST. (SMALL STRETCH OF PIPE)
 -THE EXISTING BUSINESSES ON 23RD ST ARE SENDING FLOW TO
 THE SANITARY SYSTEM. THE ONLY WAY THE SANITARY SYSTEM
 CAN BE PRIVATE IS IF FLOW FROM THESE PROPERTIES IS
 DIVERTED.
 -WILL NEED TO UPSIZE THE SANITARY SYSTEM DOWNSTREAM DUE
 TO ADDITIONAL IMPACTS ON THE SYSTEM. THE EXISTING
 SYSTEM HAS THE GRAVITY SEWER BEHIND THE PROPERTIES ON
 25TH, THE PROPOSED IMPROVEMENTS SHOULD BE WITHIN THE
 25TH ST ROW.
 -WILL NEED TO SEE ALL THE EXISTING DRY UTILITIES TO
 FINALIZE THE PROPOSED CITY OWNED UTILITIES.
 -SHOW THE EXISTING 14? CAS FM ON PINEWOOD AND PROVIDE A
 PLAN TO ALLOW ACCESS FOR O&M OR PROPOSE THE MAIN BE
 RELOCATED. IT CANNOT HAVE A BUILDING ON TOP OF IT.
 -IS THE WATER MAIN PRIVATE AND ARE YOU PROPOSING A
 MASTER METER?
  